Installation
APEX / SILAS
Pressurized Cabinet
Page 22 of 40
01-3704_7D0001_Manual_APC-SPC_20200617_jrs_en.docx
Rev.-
5
Installation
Before starting work, find out about the general safety
instructions (see Chapter 2 Safety instructions).
Requirements placed on the location
The location must be selected such as to provide good lighting at the front and
sides of the system. Good lighting is essential to allow a rapid recognition and
elimination of faults and to facilitate maintenance work. Sufficient air
circulation must also be ensured. The system may not be operated outdoors
without protection!
The APEX (SILAS) pressurized cabinet must also be freely accessible from both
left and right to allow sufficient space for maintenance and dismantling work at
a later point in time.
The floor at the location must be even and level. A mains connection with an
appropriate fuse must be available near-by.
Observe the correct dimensions of the system to allow compliance with the
necessary spacing (in this context, see the technical documents included in the
scope of supply).
Special conditions placed on the location
In general, the standard erection areas can be used for switch cabinets.
Special conditions are placed on the location in the case of APEX (SILAS)
pressurized cabinets with front display units in the form of an HMI.
Erection must ensure that the risk of mechanical danger is low.
The display unit must be protect from mechanical strain of > 4 J and of > 2J
in the area of the display
If the requirement is to be met by the selected location, the display device
must be protected by a protective door