Operational Instruction 

(Translation)

 

  Ex d Control Station 

Type 07-4230-..../... 

 

 

BARTEC 

GmbH  Max-Eyth-Straße 16  

97980 Bad Mergentheim 
Germany 

Tel.:  +49 7931 597-0 
Fax:  +49 7931 597-119 

[email protected] 
www.bartec.de 

Reservation  Technical data subject to change without notice. Changes, errors and 

misprints may not be used as a basis for any claim for damages. 

EN 1/5 

 

 

 

 

 

 

 

Explosion protection 

 

 

Technical data 

 

Maximum Ex protection type 

Depending on the installed components; ob-
serve the specifications on the type label. 

ATEX 

Ex protection type 

 II 2G  

 

Ex db eb ia/ib [ib] 

 

IIA, IIB resp. IIC T6, T5 resp. T4 

 

II 2(1)G  

 

Ex db eb ia/ib [ia]  

 

IIA, IIB resp. IIC T6, T5 resp. T4 

 
CE 0044 
 

Certification 

Ex d control station: PTB 03 ATEX 1138 
Empty closure: PTB 03 ATEX 1137 U 

IECEx 

Ex protection type 

 

Ex db eb ia/ib [ia] IIA, IIB resp. IIC T6, 

 

T5 resp. T4 

 

Ex db eb ia/ib [ib] IIA, IIB resp. IIC T6, 

 

T5 resp. T4 

 

 

Certification 

Ex d control station: IECEx PTB 11.0038 
Empty closure: IECEx PTB 11.0026U 

Ambient temperature 

Depending on the installed parts; observe 
specifications on the type label.  
 
-20 °C to +55 °C  
(-4 °F to +131 °F) 

Approved for zones 

1 and 2 

Components 

Only Ex-certified components may be in-
stalled in the junction box. 
Follow the components manufacturer’s 
mounting directions and safety instructions. 

Other applicable documents 

– 

Circuit diagram 

– 

Mounting instructions/operating instruc-
tions for the installed components 

– 

Delivery note 

The retention of these documents is manda-
tory. 

Electrical data 

Rated voltage: up to 690 V  
Power dissipation: max. 67 W 

Protection class 

IP 54 (IEC 60529) 

Rated cross-section of conductor 

Max. 16 mm

2

 

Weight 

Approx. 4 kg (8.82 lb) 

Mechanical strength 

Impact energy max. 7 Nm 

Enclosure material 

Aluminium  

Lid closure  

Cheesehead screws, 
ISO 4762-M8 x 25-A2-70 or A4-70  

Dimensions 

See page 4. 

 

01

-4

23

0-

7D

00

01

/C

-1

2/

12

-S

T

V

T

-2

94

26

Note on instructions 

When working in hazardous areas, the safety of 
personnel  and  equipment  depends  on  com-
pliance with the relevant safety regulations. The 
people  in  charge  of  installation  and  mainten-
ance bear a special responsibility. It is essential 
that  they  have  an  exact  knowledge  of  the 
applicable rules and regulations. 
The instructions provide a summary of the most 
important safety measures and must be read by 
everyone working with the product so that they 
will  be  familiar  with  the  correct  handling  of  the 
product. 
The  instructions  have  to  be  kept  for  future 
reference and must be available throughout the 
expected life of the product. 
 

Description 

These Ex d control stations are used wherever 
electrical components are needed in potentially 
explosive  environments  in  zone  1  (certified 
hazard  sub-groups  IIA,  IIB,  IIC,  temperature 
classes T4, T5, T6). Electrical operating equip-
ment,  such  as  contactors,  relays  and  controls 
are fitted as required. 
Electrical connections can be established either 
with a flanged-on junction  box with  “Ex e“  type 
of  protection  or  directly  with  cables  and  cable 
entries  that  are  approved  for  the  hazardous 
area. 
If the devices contain intrinsically safe circuits or 
Ex  i  components,  the  electrical  limits  that  are 
decisive for “intrinsic safety” (see accompanying 
documents) must be adhered to. 

 