1. Remove (A) 6-32 X 1/4” screws securing cover and set aside (Fig. 1-1 )

2. Slide front cover (B) forward and flip down. (Fig.1-2a, b)

(A)

(A)

Fig. 1-1

Fig. 1-2a

(B)

Fig. 1-2b

3. Stem mount option (Fig. 2-0a, b and 2-1a,b)
a. Thread 2 nuts (D) approximately 1/2” onto threaded rod (G). Add 1 lock washer (C). Insert threaded rod (G) into top 

    of enclosure as shown in Fig. 2-0. 

b. Using nuts (D) to hold threaded rod (G) in place thread lock nut (F) in place. 

    

Note:

 Must thread lock nut (F) in place correctly to avoid failure. See Figures 2-0a and 2-0b. 

c. Once locknut (F) is securely in place back up 2nd nut (D) to appropriate position. Tighten 1st nut (D) securely in 

    place on top of enclosure.  

d. Thread 2nd lock washer onto carriage bolt.

e. Guide (2) mounting plates (E) onto threaded rod (G) 

f.  Thread 3rd lock washer (C) and 3rd nut (D) onto threaded rod (G)

g.  Adjust mounting brackets to desired spacing and tighten nuts.

4. Remove desired knockout on back of enclosure and mount to junction box using hardware supplied with junction box. 

5. Make electrical connections.

    All electrical connections should be made inside the J-box.

    

    Make electrical connection as follows: (Fig. 3-1)

    

Note:

 Cap unused leads to prevent shorting. 

120VAC

White - Common

Black - 120V

Green - Ground

277VAC

White - Common

Orange - 277V

Green - Ground 

Fig. 3-1a

White 

(Neutral)

Black 

(for 120V)

Orange 

(for 277V)

Green 

(Ground)

Summary of Contents for Exitronix SCL Series

Page 1: ...r electrical heaters Do not use outdoors Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product liability Do not use this equipment for ot...

Page 2: ...ely in place back up 2nd nut D to appropriate position Tighten 1st nut D securely in place on top of enclosure d Thread 2nd lock washer onto carriage bolt e Guide 2 mounting plates E onto threaded rod G f Thread 3rd lock washer C and 3rd nut D onto threaded rod G g Adjust mounting brackets to desired spacing and tighten nuts 4 Remove desired knockout on back of enclosure and mount to junction box ...

Page 3: ...ergize un switched AC power to unit 2 Verify indicator LED or numeric display is illuminated 3 Press test button and verify lamps turn on Note If lamps do not illuminate allow unit to charge for 30 min 4 Leave AC connected for rated charge time prior to performing any full length test 5 Refer to section Self Test Self Diagnostics for operation SCL Series Installation Instructions 10070159 REV 5 09...

Page 4: ...uipped with a numeric indicator Self Test Features The unit equipment will automatically switch to battery mode every 28 days for a period of 1 minute The unit equipment will automatically switch to battery mode every 6 months for a period of 90 minutes Manual Test Features Press the TEST BUTTON momentarily for a 2 second test tri color LED unit only Press the TEST BUTTON until the LED turns ORANG...

Reviews: