background image

SCL Series

Installation Instructions

10070159  REV 5 - 09/19

   4

800-533-3948 www.barronltg.com

 

SELF-TEST/SELF-DIAGNOSTIC

OPERATING INSTRUCTIONS

KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE

I M P O R T A N T:

 Once all emergency lamps have been connected to the unit equipment, apply normal AC power and 

charge for 24 hours. 
For units equipped with G2 and the tri-color LED indicator: Following installation and after AC power has been supplied, 

charge for 48 hours, then press and hold the test button until the LED indicator turns orange. This calibrates the unit 

equipment for the proper load.

Operation

The purpose of this option is to provide Self-testing and Self-diagnostic capabilities to the unit equipment. At 

predetermined intervals, the unit equipment will automatically switch into battery mode. The unit equipment will also 

perform various Self-diagnostic tests of the unit. Visual signaling will alert maintenance personnel to a fault of the unit 

equipment electronics, emergency lamp(s), battery and/or battery charger. The circuitry continuously monitors the 

operating condition of the unit equipment and battery charging circuit/battery supply voltage. Refer to Table 1 for units 

equipped with a tri-color LED indicator. Refer to Table 2 for units equipped with a numeric indicator.

Self-Test Features

• The unit equipment will automatically switch to battery mode every 28 days for a period of 1 minute.

• The unit equipment will automatically switch to battery mode every 6 months for a period of 90 minutes.

Manual Test Features

• Press the TEST BUTTON momentarily for a 2 second test. (tri-color LED unit only)
• Press the TEST BUTTON until the LED turns ORANGE or the numeric indicator shows “7” for a manual 1 minute test.
• Press the TEST BUTTON until the LED flashes RED/GREEN, (tri-color LED unit only) for manual 90 minute test.

LED Indication

Steady
Pulse
Steady
Pulse

Steady

Pulse
LED Color

LED Color

Green
Green
Red
Red

Orange

Orange
Red/Green

Unit Condition

Float Charge
Hi-Rate Charge

Low Batt Voltage

Emer Lamp Failure

No AC Power

Charge Failure

1 Minute Test

Batt Disconnected

90 Minute Test

Comment

Batt Fully Charged
Batt Under High-Rate Charge
Replace Battery

Check AC Connection

Replace Transformer

1 Min Test Every 28 Days

Check Batt Connections
90 Min Test Every 6 Months

Replace Damaged or 

Missing Lamps

Table 1 - Tri-Color LED Indicator 

CHARGED      

 

0     Float charging

CHARGING     1     Hi rate charging

EM/BATT         2     Discharging

CHRG FAIL     

 

3     Charger failure

DISC BATT    

    

4     Battery not connected 

LAMP FAIL      5     Lamp failure 

LOW BATT      6     Low battery voltage

1 MIN TEST     7     Manual testing
90 MIN TEST   8     Self testing

STATUS LEDGE    Condition

Table 2 - Numeric Indicator 

Bottom of Unit

Bottom of Unit

Numeric Indicator

Tri-Color LED

Summary of Contents for Exitronix SCL Series

Page 1: ...r electrical heaters Do not use outdoors Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product liability Do not use this equipment for ot...

Page 2: ...ely in place back up 2nd nut D to appropriate position Tighten 1st nut D securely in place on top of enclosure d Thread 2nd lock washer onto carriage bolt e Guide 2 mounting plates E onto threaded rod G f Thread 3rd lock washer C and 3rd nut D onto threaded rod G g Adjust mounting brackets to desired spacing and tighten nuts 4 Remove desired knockout on back of enclosure and mount to junction box ...

Page 3: ...ergize un switched AC power to unit 2 Verify indicator LED or numeric display is illuminated 3 Press test button and verify lamps turn on Note If lamps do not illuminate allow unit to charge for 30 min 4 Leave AC connected for rated charge time prior to performing any full length test 5 Refer to section Self Test Self Diagnostics for operation SCL Series Installation Instructions 10070159 REV 5 09...

Page 4: ...uipped with a numeric indicator Self Test Features The unit equipment will automatically switch to battery mode every 28 days for a period of 1 minute The unit equipment will automatically switch to battery mode every 6 months for a period of 90 minutes Manual Test Features Press the TEST BUTTON momentarily for a 2 second test tri color LED unit only Press the TEST BUTTON until the LED turns ORANG...