Self-Test/Self-Diagnostics (G2) with Numeric Display

I M P O R T A N T:

 Once all emergency lamps have been connected to the unit equipment, apply normal AC power and

charge for 48 hours.

CAUTION:

 This equipment provides reduced current levels when higher voltage loads are connected. The derangement 

signal requires calibration to ensure proper operation.

Operation

The purpose of this option is to provide Self-testing and Self-diagnostic capabilities to the emergency unit. At 

predetermined intervals, the emergency unit will automatically switch into battery mode. Refer to the 

Automatic Self-Test 

Feature

 section below for timing details. The emergency unit will also perform various Self-diagnostic tests to determine if 

there are any faults. Visual signaling will alert maintenance personnel to a fault of the emergency unit electronics, battery, 

and/or battery charger. The circuitry continuously monitors the operating condition of the emergency unit and battery 

charging circuit/battery supply voltage. Refer to the 

Numeric Indicator

 section below for fault reporting details.

Automatic Self-Test Feature

• The unit equipment will automatically switch to battery mode every month for a period of 1 minute.

• The unit equipment will automatically switch to battery mode every year for a period of 90 minutes.

Numeric Indicator

The numeric indicator of the emergency unit will display a visual signal indicating the status of the unit. Refer to Table 2 for 

units equipped with a numeric indicator.

Test Button Features

MANUAL TEST – Pressing the test button will switch the unit into battery mode for a set amount of time. The desired 

length of the test is determined by the length of time that the test button is pressed.

• Pressing and holding the test button until the 

numeric indicator shows “7” 

will switch the unit into battery mode for a 

period of 1 minute.

• Pressing and holding the test button until the 

numeric indicator shows “8” 

will switch the unit into battery mode for a 

period of 90 minutes.

Use in accordance with local building codes.

 

CHARGED 

0     Float charging

CHARGING 

1     Hi rate charging

EM/BATT 

2     Discharging

CHRG FAIL 

3     Charger failure

DISC BATT 

4     Battery not connected 

LAMP FAIL 

5     Lamp failure 

LOW BATT 

6     Low battery voltage

1 MIN TEST 

7     Running 1 min test

90 MIN TEST  8     Running 90 min test

STATUS LEDGE    Condition

Table 2 - Numeric Indicator 

Numeric Display 

 

10070166 

R

EV 7 - 08/22

5

800-533-3948 www.barronltg.com

CRL Series

Installation Instructions

Summary of Contents for EXITRONIX CRL Series

Page 1: ...r electrical heaters Do not use outdoors Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product liability Do not use this equipment for ot...

Page 2: ...of the T bar Fig 2a b a Additional chains or cabling shall be used for enclosure securement 3 Remove the 4 6 32 x 3 4 flat head screws from cover Fig 3 4 Remove the cover and connect the lanyards to the lanyard hooks found inside the enclosure Fig 4a b 5 Connect flexible conduit to one of the three available conduit knockouts Fig 5 Wing Nuts Ceiling Bracket Fig 1 Fig 2b Fig 2a 6 32 x 3 4 Flat Head...

Page 3: ... 6 32 x 1 4 screw 8 Verify connections are in place such as lamps LED and test button 9 Replace the enclosure cover and secure in place with the cover screws 10 Open the battery door by unscrewing the captive thumb screw Fig 7 11 Connect the battery and close the battery door 12 Secure the battery door in place by retightening the thumb screw 13 Cut the ceiling tile to correct size as needed Fig 8...

Page 4: ...s The unit equipment will automatically switch to battery mode every 6 months for a period of 30 minutes The unit equipment will automatically switch to battery mode every year for a period of 90 minutes LED Indicator The LED indicator of the emergency unit will display a visual signal indicating the status of the unit Refer to Table 1 for units equipped with a tri color LED indicator Test Button ...

Page 5: ...ill automatically switch to battery mode every month for a period of 1 minute The unit equipment will automatically switch to battery mode every year for a period of 90 minutes Numeric Indicator The numeric indicator of the emergency unit will display a visual signal indicating the status of the unit Refer to Table 2 for units equipped with a numeric indicator Test Button Features MANUAL TEST Pres...

Reviews: