background image

Installation

1. Loosen all (4) ceiling bracket wing nuts half way for ease of installation. Hang the fixture on the ceiling T-bars using the 

ceiling brackets. (Fig. 1)

2. Tighten all ceiling bracket wing nuts to secure the fixture in place. Adjust the slot placement of the ceiling brackets 

accordingly to adjust the enclosure opening to be level with the inside surface of the T-bar. (Fig. 2a, b)

a. Additional chains or cabling shall be used for enclosure securement.

3. Remove the (4) #6-32 x 3/4” flat head screws from cover. (Fig. 3)

4. Remove the cover and connect the lanyards to the lanyard hooks found inside the enclosure. (Fig. 4a, b)

5. Connect flexible conduit to one of the three available conduit knockouts. (Fig. 5)

Wing 

Nuts

Ceiling

Bracket

Fig. 1

Fig. 2b

Fig. 2a

6-32 x 3/4” 

Flat Head 

Screws

Fig. 3

Fig. 4a

Fig. 4b

Lanyard 

Hook

Lanyard

Flexible 

Conduit 

Fig. 5

 

10070166 

R

EV 7 - 08/22

2

800-533-3948 www.barronltg.com

CRL Series

Installation Instructions

Summary of Contents for EXITRONIX CRL Series

Page 1: ...r electrical heaters Do not use outdoors Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product liability Do not use this equipment for ot...

Page 2: ...of the T bar Fig 2a b a Additional chains or cabling shall be used for enclosure securement 3 Remove the 4 6 32 x 3 4 flat head screws from cover Fig 3 4 Remove the cover and connect the lanyards to the lanyard hooks found inside the enclosure Fig 4a b 5 Connect flexible conduit to one of the three available conduit knockouts Fig 5 Wing Nuts Ceiling Bracket Fig 1 Fig 2b Fig 2a 6 32 x 3 4 Flat Head...

Page 3: ... 6 32 x 1 4 screw 8 Verify connections are in place such as lamps LED and test button 9 Replace the enclosure cover and secure in place with the cover screws 10 Open the battery door by unscrewing the captive thumb screw Fig 7 11 Connect the battery and close the battery door 12 Secure the battery door in place by retightening the thumb screw 13 Cut the ceiling tile to correct size as needed Fig 8...

Page 4: ...s The unit equipment will automatically switch to battery mode every 6 months for a period of 30 minutes The unit equipment will automatically switch to battery mode every year for a period of 90 minutes LED Indicator The LED indicator of the emergency unit will display a visual signal indicating the status of the unit Refer to Table 1 for units equipped with a tri color LED indicator Test Button ...

Page 5: ...ill automatically switch to battery mode every month for a period of 1 minute The unit equipment will automatically switch to battery mode every year for a period of 90 minutes Numeric Indicator The numeric indicator of the emergency unit will display a visual signal indicating the status of the unit Refer to Table 2 for units equipped with a numeric indicator Test Button Features MANUAL TEST Pres...

Reviews: