13
OP:
% output power demand.
IdHi:
Deviation high alarm.
Al List
IdHi:
Deviation high alarm.
Atun List
tunE:
One-shot autotune enable.
Pid List
Pb:
Proportional band (in display units).
ti:
Integral time in seconds.
td:
Derivative time in seconds.
ACCS List Code:
Access code (Code need-
ed to enter or change the other configuration
parameters which are not normally accessi-
ble.) Not accessable.
Alarms
The controller will flash an alarm message in
the home display if an alarm condition is
detected.
2FSH:
Measured value full scale high alarm.
IdHi:
Measured value deviation high alarm.
S.br:
Sensor break: check that sensor is con-
nected correctly.
L.br:
Loop break: check that the heating cir-
cuits are working properly.
S
INGLE
S
ETPOINT
M
ODELS
& S
INGLE
S
ETPOINT
M
ODELS W
/OTP
Note
The following alarm messages are fac-
tory default settings and may vary if you
have changed the configuration of your
controller:
IDHi: = 50°C
2FSH = 1225°C