SECTION B: GENERAL INFORMATION

B-1) To the Purchaser:

 

Congratulations! You are the owner of one of the fi nest pumps 
on  the  market  today.  CP&S  pumps  are  products  engineered 
and  manufactured  of  high  quality  components.  Over  one 
hundred  years  of  pump  building  experience  along  with  a 
continuing  quality  assurance  program  combine  to  produce  a 
pump  which  will  stand  up  to  the  toughest  applications.  This 
manual will provide helpful information concerning installation, 
maintenance, and proper service guidelines.

B-2) Receiving:

 

Upon receiving the pump, it should be inspected for damage 
or shortages. If damage has occurred, fi le a claim immediately 
with  the  company  that  delivered  the  pump.  If  the  manual 
is  removed  from  the  packaging,  do  not  lose  or  misplace.

B-3) Storage:
Short  Term-

  CP&S  Pumps  are  manufactured  for  effi cient 

performance  following  short  inoperative  periods  in  storage. 
For best results, pumps can be retained in storage, as factory 
assembled,  in  a  dry  atmosphere  with  constant  temperatures 
for  up  to  six  (6)  months.  Long  Term-  Any  length  of  time 
exceeding six (6) months, but not more than twenty-four (24) 
months. The unit should be stored in a temperature controlled 
area, a roofed over walled enclosure that provides protection 
from  the  elements  (rain,  snow,  wind-blown  dust,  etc.),  and 
whose  temperature  can  be  maintained  between  +40  deg.  F 
and  +120  deg.  F.  (4.4  -  49°C).  Pump  should  be  stored  in  its 
original  shipping  container.  On  initial  start  up,  rotate  impeller 
by  hand  to  assure  seal  and  impeller  rotate  freely.  If  it  is 
required that the pump be installed and tested before the long 
term storage begins, such installation will be allowed provided:

1.)  The pump is not installed under water for more than
 

one (1) month.

2.)  Immediately upon satisfactory completion of the test,
 

the pump is removed, thoroughly dried, repacked in the

 

original shipping container, and placed in a temperature

 

controlled storage area.

B-4) Service Centers:

 

For the location of the nearest Barnes Service Center, check 
your Barnes representative or Crane Pumps & Systems, Inc., 
Service Department in Piqua, Ohio, telephone (937) 778-8947 
or  Crane  Pumps  &  Systems  Canada,  in  Brampton,  Ontario, 
(905) 457-6223.

SECTION C: INSTALLATION

C-1) Location:

 

These pumping units are self-contained and are recommended 
for use in a sump, lift station or basin that is free of hard debris 
like  gravel,  stones,  sand  or  earth.  The  sump,  lift  station  or 
basin shall be vented in accordance with local plumbing codes. 
This  pump  is  designed  to  pump  sewage,  effl uent,  or  other 
nonexplosive  or  noncorrosive  wastewater.  and  shall 

NOT

  be 

installed  in  locations  classifi ed  as  hazardous  in  accordance 
with the National Electrical Code (NEC), ANSI/NFPA 70 or the 
Canadian Electrical Code (CEC). Never install the pump in a 
trench, ditch or hole with gravel, stones, sand, or earth bottom; 
the  legs  will  sink  into  the  dirt  and  the  suction  will  become 
plugged, or the pump impeller will be damaged. 

C-1.1) Submergence:

It is recommended that the pump be operated in the submerged 
condition and the sump liquid level should never be lower than 
the top of the pump. (see Fig. 2)

 

C-2) Discharge:

Discharge piping should be as short as possible. Both a check 
valve  and  a  shut-off  valve  are  recommended  for  each  pump 
being  used.  The  check  valve  is  used  to  prevent  backfl ow 
into  the  sump.  Excessive  backfl ow  can  cause  fl ooding 
and/or  damage  to  the  pump.  The  shut-off  valve  is  used  to 
stop  system  fl ow  during  pump  or  check  valve  servicing.

Barnes  Pumps  supplies  a  Stainless  Rail  Package    for 
the  2”  models  and  also  a  variety  of  2”  and  3”  break-away 
fi tting  discharge  systems  (see  Fig.  1)  designed  to  allow  the 
submersible  wastewater  pump  to  be  installed  or  removed 
without requiring personnel to enter the wet well. Contact your 
local Barnes Pumps distributor for complete details.

Stainless  Rail  Package  (Not  Shown)  -  The  package  system 
comes complete and ready to place into the ground as outlined 
in the project specifi cations. The moveable portion of the Break 
Away  Fitting  (BAF),  check  valve,  piping  and  guide  bracket 
comes  assembled  on  the  pump  along  with  the  lifting  cord. 
Insert  pump  bracket  and  moveable  portion  of  BAF  into  the 
guide  channel  and  lower  pump  into  basin 

(DO  NOT  DROP)

Now  connect  power  and  control  cords  to  the  junction  box  or 
control panel depending on system design.
 

C-3) Liquid Level Controls:

The level controls are to be supported by a mounting bracket that 
is attached to the sump wall, cover or junction box. Cord grips 
are used to hold the cords in place on the mounting bracket. 
The  control  level  can  be  changed  by  loosening  the  grip  and 
adjusting the cord length as per the plans and specifi cations. 
Be certain that the level controls cannot hang up or foul in it’s 
swing and that the pump is completely submerged when the 
level control is in the “Off” mode.

FIGURE 1

Summary of Contents for SE51A

Page 1: ...program product changes may occur As such Crane Pumps Systems reserves the right to change product without prior written notification 420 Third Street 83 West Drive Bramton Piqua Ohio 45356 Ontario C...

Page 2: ...18 22 SE HT SINGLE SEAL EXPLODED VIEW Fig 19 23 3SE DS DOUBLE SEAL CROSS SECTION Fig 20 24 3SE DS DOUBLE SEAL EXPLODED VIEW Fig 21 25 PARTS LIST 26 28 RETURNED GOODS POLICY 32 WARRANTY 31 WARRANTY RE...

Page 3: ...rt fingers in pump with power connected Always wear eye protection when working on pumps Make sure lifting handles are securely fastened each time before lifting DO NOT operate pump without safety dev...

Page 4: ...Filled Reservoir Material Carbon Ceramic Buna N Hardware 300 Series Stainless CORD ENTRY 15 ft 5 m 20 ft 6 1 m Cord Plug on 120 Volt 5HP 240 Volt 1 Phase Quick connect custom molded for sealing and s...

Page 5: ...le Seal SE A SE HTA Single Seal SE AU SE HTAU Single Seal Plugs for 120 Volt and 5Hp 240 Volt Single Phase Models Plugs for 120 Volt and 5Hp 240 Volt Single Phase Models Plugs for 120 Volt and 5Hp 240...

Page 6: ...6 Plugs for 120 Volt and 5Hp 240 Volt Single Phase Models inches mm Plugs for 120 Volt and 5Hp 240 Volt Single Phase Models 3SE L Single Seal 3SE DS Double Seal...

Page 7: ...or basin that is free of hard debris like gravel stones sand or earth The sump lift station or basin shall be vented in accordance with local plumbing codes This pump is designed to pump sewage efflu...

Page 8: ...rations Automatic Plug float cord into outlet then plug pump cord into float cord Manual Plug pump cord directly int outlet C 4 Electrical Connections C 4 1 Power and Control Cable The cord assembly m...

Page 9: ...tamped on the pump identi cation plate to the available power D 2 Check Pump Rotation Before putting pump into service for the rst time the motor rotation must be checked Improper motor rotation can r...

Page 10: ...5 3 14 4 SOW 0 570 14 5 40 80 52 00 3SE554L 0 5 600 3 60 1750 H B 1 0 3 4 14 4 SOW 0 570 14 5 77 60 89 76 3SE774L 0 75 200 240 1 60 1750 G K F 7 4 7 0 21 5 25 8 14 3 SOW 0 530 13 5 1 86 10 20 2 74 10...

Page 11: ...he pressure does not hold then the leak must be located and repaired Pumps that have NOT had the oil drained from the Motor Housing The pressure test may be done with the oil at its normal level Remov...

Page 12: ...volute 1 Position lockwasher 12 on cap screw 26 and screw into volute 1 Torque to 100 in lbs Check for free rotation of motor and impeller F 3 Shaft Seal Service CAUTION Handle seal parts with extrem...

Page 13: ...ing sure it is seated on retainer and not cocked or resting on bellows tail Slide retaining ring 28d over shaft and let rest on spring 28c Replace snap ring 32 in groove of shaft Set square ring 27 in...

Page 14: ...ce station or Barnes Pumps Service department Inspect motor winding for shorts and check resistance values Check rotor for wear If rotor or the stator windings are defective the complete motor must be...

Page 15: ...eplacement parts ALWAYS furnish the following information 1 Pump serial number and date code Paragraph G 4 2 Pump model number Paragraph G 3 3 Pump part number Paragraph G 2 4 Part description 5 Item...

Page 16: ...16 FIGURE 13...

Page 17: ...17 FIGURE 13...

Page 18: ...18 FIGURE 13 CONTIUED...

Page 19: ...cutter for freedom of operation security and condition Clean cutter and inlet of any obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so t...

Page 20: ...20 FIGURE 16 SE L 3SE L Series Single Seal...

Page 21: ...21 FIGURE 17 SE L 3SE L Series Single Seal...

Page 22: ...22 FIGURE 18 SE HT High Temp Series Single Seal...

Page 23: ...23 FIGURE 19 SE HT High Temp Series Single Seal...

Page 24: ...24 FIGURE 20 3SE DS Series Double Seal...

Page 25: ...25 FIGURE 21 3SE DS Series Double Seal...

Page 26: ...BS 070963 SE774L 3SE774L SE1074L 3SE1074L 029792BD 070963 3SE774DS 3SE1074DS 071354BS None SE794L SE744L 3SE794L 3SE744L SE1094L None SE1044L 3SE1094L 3SE1044L 071354BD None 3SE794DS 3SE744DS 3SE1094D...

Page 27: ...a 084346TH 5 00 Dia 084346TJ 4 88 Dia 084346TK 4 75 Dia 084346TL 4 63 Dia 084346TM 4 50 Dia 084346TN 4 38 Dia 084346TP 4 25 Dia 084346TQ 4 13 Dia 084346TR 4 00 Dia 36 1 027344 t Gasket 39 1 014270 Pip...

Page 28: ...ABLE LENGTH ITEM 16 120 VOLT 1 PHASE STD Temp ITEM 16 120 VOLT 1 PHASE High Temp ITEM 16 240 VOLT 1 PHASE 0 5HP STD HT ITEM 16 240 VOLT 1 PHASE 0 75 1HP STD HT ITEM 16 3 PHASE ITEM 55 OPTIONAL STD Tem...

Page 29: ...29 Notes...

Page 30: ...30 Notes...

Page 31: ...s between the results of eld testing conducted by or for user and laboratory tests corrected for eld performance the latter shall control RECOMMENDATIONS FOR SPECIAL APPLICATIONS OR THOSE RESULTING FR...

Page 32: ...nt To Insure That Employees Will Not Be Exposed To Health Hazards In Handling Said Material All Applicable Laws And Regulations Shall Apply IMPORTANT WARRANTY REGISTRATION Your product is covered by t...

Reviews: