background image

6

C-4) Electrical Connections:
C-4.1) Power Cable:

The cord assembly mounted to the pump must not be modifi ed 
in any way except for shortening to a specifi c application. 
Any splice between the pump and the control panel must be 
made in accordance with all applicable electric codes. It is 
recommended that a junction box, if used, be mounted outside 
the sump or be of at least Nema 4 (EEMAC-4) construction if 
located within the wet well. Do not use the power cable to lift 
pump. 

NOTE: THE WHITE WIRE IS NOT A NEUTRAL OR 

GROUND LEAD, BUT A POWER CARRYING CONDUCTOR.

C-4.2)  Control Cable:

The cord assembly mounted to the pump must not be modifi ed 
in any way except for shortening to a specifi c application. 
Any splice between the pump and the control panel must be 
made in accordance with all applicable electric codes. It is 
recommended that a junction box, if used, be mounted outside 
the sump or be of at least Nema 4 (EEMAC-4) construction if 
located within the wet well. Do not use the control cable to lift 
pump. 

NOTE: THE WHITE WIRE IS NOT A NEUTRAL OR 

GROUND LEAD, BUT A POWER CARRYING CONDUCTOR.

C-4.3) Overload Protection:
C-4.3-1) Three Phase (Optional)

 - The normally closed 

(N/C) thermal sensor is embedded in the motor windings and 
will detect excessive heat in the event an overload condition 
occurs. The thermal sensor will trip when the windings become 
too hot and will automatically reset itself when the pump 
motor cools to a safe temperature. It is recommended that the 
thermal sensor be connected in series to an alarm device to 
alert the operator of an overload condition, and/or the motor 
starter coil to stop the pump. In the event of an overload, the 
source of this condition should be determined and rectifi ed 
immediately. 

DO NOT LET THE PUMP CYCLE OR RUN IF 

AN OVERLOAD CONDITION OCCURS !

C-4.3-2) Single Phase

 - The type of in-winding overload 

protector used is referred to as an inherent overheating 
protector and operates on the combined effect of temperature 
and current. This means that the overload protector will trip out 
and shut the pump off if the windings become too hot, or the 
load current passing through them becomes too high. It will 
then automatically reset and start the pump up after the motor 
cools to a safe temperature. In the event of an overload, the 
source of this condition should be determined and rectifi ed 
immediately. 

DO NOT LET THE PUMP CYCLE OR RUN IF 

AN OVERLOAD CONDITION OCCURS !

If current through the temperature sensor exceeds the values 
listed, an intermediate control circuit relay must be used to 
reduce the current or the sensor will not work properly.

TEMPERATURE SENSOR ELECTRICAL RATINGS

Volts

Continuous

Amperes

Inrush

Amperes

220-240

1.50

15.0

440-480

0.75

7.5

575-600

0.60

6.0

C-4.4) Wire Size:

Consult a qualifi ed electrician for proper wire size if additional 
power cable length is required. See table for electrical 
information.

SECTION: D START-UP OPERATION

D-1) Check Voltage and Phase:

Before operating pump, compare the voltage and phase 
information stamped on the pump identifi cation plate to the 
available power.

D-2) Check Pump Rotation:

Before putting pump into service for the fi rst time, the motor 
rotation must be checked. Improper motor rotation can result 
in poor pump performance and can damage the motor and/
or pump. To check the rotation, suspend the pump freely, 
momentarily apply power and observe the “kickback”. 
“Kickback” should always be in a counter-clockwise direction 
as viewed from the top of the pump motor housing.

D-2.1) Incorrect Rotation for Three-Phase Pumps:

In the event that the rotation is incorrect for a three-phase 
installation, interchange any two power cable leads at the 
control box. DO NOT change leads in the cable housing in the 
motor. Recheck the “kickback” rotation again by momentarily 
applying power.

D-2.2) Incorrect Rotation for Single-Phase Pumps:

In the unlikely event that the rotation is incorrect for a single 
phase pump, contact a Barnes Service Center.

D-3) Identifi cation Plate:

Record the numbers from the pump identifi cation plate for 
future reference.

D-3.1) Insulation Test:

Before the pump is put into service, an insulation (megger) 
test should be performed on the motor. The resistance values 
(ohms) as well as the voltage (volts) and current (amps) should 
be recorded.

D-3.2) Pump-Down Test:

After the pump has been properly wired and lowered into the 
basin, sump or lift station, it is advisable to check the system 
by fi lling with liquid and allowing the pump to operate through 
its pumping cycle. The time needed to empty the system, or 
pump-down time along with the volume of water, should be 
recorded.

SECTION E: PREVENTATIVE MAINTENANCE

As the motor is oil fi lled, no lubrication or other maintenance 
is required, and generally Barnes Pumps will give very 
reliable service and can be expected to operate for years on 
normal sewage pumping without failing. However as with any 
mechanical piece of equipment a preventive maintenance 
program is recommended and suggested to include the 
following checks:

Summary of Contents for 3SE-L Series

Page 1: ... product improvement program product changes may occur As such Crane Pumps Systems reserves the right to change product without prior written notification 420 Third Street 83 West Drive Brampton Piqua Ohio 45356 Ontario Canada L6T 2J6 Phone 937 778 8947 Phone 905 457 6223 Fax 937 773 7157 Fax 905 457 2650 www cranepumps com Form No 132724 Rev C Series 3SE L 1 5 2HP 1750RPM 60Hz Single Seal Manual I...

Page 2: ... Figure 11 15 EXPLODED VIEW Figure 12 16 PARTS LIST 17 18 WARRANTY 19 WARRANTY REGISTRATION 20 RETURNED GOODS POLICY 20 SPECIAL TOOLS AND EQUIPMENT INSULATION TESTER MEGGER DIELECTRIC TESTER SEAL TOOL KIT see parts list PRESSURE GAUGE KIT see parts list Other brand and product names are trademarks or registered trademarks of their respective holders Barnes is a registered trademark of Crane Pumps ...

Page 3: ...sert fingers in pump with power connected Always wear eye protection when working on pumps Make sure lifting handles are securely fastened each time before lifting DO NOT operate pump without safety devices in place Always replace safety devices that have been removed during service or repair Secure the pump in its operating position so it can not tip over fall or slide DO NOT exceed manufacturers ...

Page 4: ...tion Class B for 1 5 2HP Class F on selected models SINGLE PHASE Permanent Split Capacitor PSC includes overload protection in motor THREE PHASE 200 230 460 60Hz is Tri voltage motor 575V Requires overload protection to be included in control panel OPTIONAL EQUIPMENT Seal Material Impeller Trims Additional Cord Normally Closed Temperature Sensors with cord for 3 phase pumps Requires relay in contr...

Page 5: ...use in a sump lift station or basin The sump lift station or basin shall be vented in accordance with local plumbing codes This pump is designed to pump sewage effluent or other nonexplosive or noncorrosive wastewater and shall NOT be installed in locations classified as Class I Division 1 hazardous in accordance with the National Electrical Code NEC ANSI NFPA 70 or The Canadian Electrical Code Neve...

Page 6: ...LOAD CONDITION OCCURS If current through the temperature sensor exceeds the values listed an intermediate control circuit relay must be used to reduce the current or the sensor will not work properly TEMPERATURE SENSOR ELECTRICAL RATINGS Volts Continuous Amperes Inrush Amperes 220 240 1 50 15 0 440 480 0 75 7 5 575 600 0 60 6 0 C 4 4 Wire Size Consult a qualified electrician for proper wire size if...

Page 7: ...5 8 84 8 92 3SE1554L 1 5 575 3 60 1750 G B 4 6 16 4 14 4 SOOW SOW 0 57 14 5 13 79 13 95 3SE2024L 2 0 230 1 60 1750 A F 19 0 44 6 10 3 SOOW SOW 0 66 16 8 1 21 2 80 1 35 4 20 3SE2094L 2 0 200 230 3 60 1750 B D F 15 2 13 2 35 8 41 2 12 4 SOOW SOW 0 68 17 4 2 21 2 23 3SE2044L 2 0 460 3 60 1750 D F 6 6 20 6 14 4 SOOW SOW 0 57 14 5 8 84 8 92 3SE2054L 2 0 575 3 60 1750 D B 5 2 16 4 14 4 SOOW SOW 0 57 14 ...

Page 8: ...Use soap solution around the sealed areas and inspect joints for air bubbles If after five minutes the pressure is still holding constant and no bubbles are observed slowly bleed the pressure and remove the gauge assembly Replace oil as described in paragraph F 1 4 If the pressure does not hold then the leak must be located and repaired Pumps that have NOT had the oil drained from the Motor Housing...

Page 9: ... the terminal block 23 Be sure to leave slack on the motor leads connected underneath Use needle nose pliers to pull each female connector off of the pins on the underside of the terminal block 23 see Figure 5 The unit voltage should be noted Repeat cable and terminal block removal procedure for any control cables 32 if equipped Remove socket head cap screws 9 Vertically lift the motor housing 5 f...

Page 10: ...ring 40 into groove in terminal block and lubricate with dielectric oil Press the terminal block 23 38 optional into the housing so it seats completely below the snap ring groove Place snap ring 41 into groove in cable entry bore of housing Repeat terminal block installation for control cable if equipped F 3 4 Cable Assemblies Power Control Cable Refill the cooling oil as outlined in paragraph F 1 ...

Page 11: ...see Figure 8 With polished surface of rotating member 31b facing inward toward stationary member 31a slide rotating member 31b over bullet and onto shaft using seal pusher until polished faces of 31a and 31b are together see Figure 9 It is extremely important to keep seal faces clean during assembly Dirt particles lodged between these faces will cause the seal to leak Place spring 31c over shaft a...

Page 12: ... design configuration This number is used for ordering and obtaining information G 3 MODEL NUMBER This designation consists of numbers and letters which represent the discharge size series horsepower motor phase and voltage speed and pump design This number is used for ordering and obtaining information G 4 SERIAL NUMBER The serial number block will consist of a six digit number which is specific to...

Page 13: ...13 FIGURE 10 ...

Page 14: ...k impeller for freedom of operation security and condition Clean impeller and inlet of any obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so that the suction is always flooded Clean vent hole 10 Check rotation If power supply is three phase reverse any two of three power supply leads to ensure proper impeller rotation 11 Repair fixtures...

Page 15: ...15 FIGURE 11 ...

Page 16: ...16 FIGURE 12 ...

Page 17: ...e 18 3 105149A Wire Assemblies 3 Phase 230V 19 1 014270 Pipe Plug 375 NPT 20 1 084382MA Motor 3SE1524L 3SE2024L 084383MA 3SE1594L 3SE1544L 084383MA 3SE2094L 3SE2044L 092856 3SE1554L 3SE2054L 21 1 036391 Capacitor 1 phase 370V 45MFD 22 1 039858 Capacitor Bracket 1 phase 23 1 See Table 2 Terminal Block 24 1 084399 Volute 25 1 625 02117 Sleeve Fiberglass 230V 1 Phase 460V 3 Phase 575V 3 Phase 2 625 0...

Page 18: ...ENSOR TERMINAL BLOCK TEMP SENSOR 3SE1524L None None None None 3SE1594L 103741XC 103741XF 103741XL 103584 3SE1544L 113288XC 113288XF 113288XL 113272 3SE1554L 113288XC 113288XF 113288XL 113272 3SE2024L None None None None 3SE2094L 103741XC 103741XF 103741XL 103584 3SE2044L 113288XC 113288XF 113288XL 113272 3SE2054L 113288XC 113288XF 113288XL 113272 TABLE 3 IMPELLER ITEM 29 DIAMETER 1 5 2HP 7 00 0844...

Page 19: ...es between the results of eld testing conducted by or for user and laboratory tests corrected for eld performance the latter shall control RECOMMENDATIONS FOR SPECIAL APPLICATIONS OR THOSE RESULTING FROM SYSTEMS ANALYSES AND EVALUATIONS WE CONDUCT WILL BE BASED ON OUR BEST AVAILABLE EXPERIENCE AND PUBLISHED INDUSTRY INFORMATION SUCH RECOMMENDATIONS DO NOT CONSTITUTE A WARRANTY OF SATISFACTORY PERF...

Page 20: ...ent To Insure That Employees Will Not Be Exposed To Health Hazards In Handling Said Material All Applicable Laws And Regulations Shall Apply IMPORTANT WARRANTY REGISTRATION Your product is covered by the enclosed Warranty To complete the Warranty Registration Form go to http www cranepumps com ProductRegistration If you have a claim under the provision of the warranty contact your local Crane Pump...

Reviews: