background image

14

TROUBLE SHOOTING

CAUTION !

 

Always disconnect the pump from the electrical power source before handling.

If the system fails to operate properly, carefully read instructions and perform maintenance recommendations.
If operating problems persist, the following chart may be of assistance in identifying and correcting them:

MATCH “CAUSE” NUMBER WITH CORRELATING “CORRECTION” NUMBER

.

NOTE:

 Not all problems and corrections will apply to each pump model.

PROBLEM

CAUSE

CORRECTION

Pump will not run

1.

 Poor electrical connection, blown fuse, tripped 

breaker or other interruption of power, improper 
power supply.

2.

 Motor or switch inoperative (to isolate cause, go 

to manual operation of pump).

2a.

 Float movement restricted.

2b.

 Switch will not activate pump or is defective.

2c.

 Defective motor

3.

 Insuffi cient liquid level.

1. Check all electrical connections for security. 
Have electrician measure current in motor leads, 
if current is within ±20% of locked rotor Amps, 
impeller is probably locked. If current is 0, 
overload may be tripped. Remove power, allow 
pump to cool, then recheck current.
2a. Reposition pump or clean basin as required to 
provide adequate clearance for fl oat.
2b. Disconnect level control. Set ohmmeter for 
a low range, such as 100 ohms full scale and 
connect to level control leads. Actuate level 
control manually and check to see that ohmmeter 
shows zero ohms for closed switch and full scale 
for open switch. (Float Switch).
2c. Check winding insulation (Megger Test) and 
winding resistance. If check is outside of range, 
dry and recheck. If still defective, replace per 
service instructions.
3. Make sure liquid level is at least equal to 
suggested turn-on point.
4. Recheck all sizing calculations to determine 
proper pump size.
5. Check discharge line for restrictions, including 
ice if line passes through or into cold areas.
6. Remove and examine check valve for proper 
installation and freedom of operation.
7. Open valve.
8. Check impeller for freedom of operation, 
security and condition. Clean impeller and inlet of 
any obstruction.
9. Loosen union slightly to allow trapped air to 
escape.Verify that turn-off level of switch is set so 
that the suction is always fl ooded. Clean vent hole.
10. Check rotation. If power supply is three phase, 
reverse any two of three power supply leads to 
ensure proper impeller rotation.
11. Repair fi xtures as required to eliminate 
leakage.
12. Check pump temperature limits & fl uid 
temperature.
13. Replace portion of discharge pipe with fl exible 
connector.
14. Turn to automatic position.
15. Check for leaks around basin inlet and outlets.

Pump will not turn off

2a. Float movement restricted.
2b. Switch will not activate pump or is defective.
4. Excessive infl ow or pump not properly sized for 
application.
9. Pump may be airlocked
14. H-O-A switch on panel is in “HAND” position

Pump hums but does not run

1. Incorrect voltage
8. Impeller jammed or loose on shaft, worn or 
damaged, impeller cavity or inlet plugged.

Pump delivers insuffi cient capacity

1. Incorrect voltage.
4. Excessive infl ow or pump not properly sized for 
application.
5. Discharge restricted.
6. Check valve stuck closed or installed backwards.
7. Shut-off valve closed.
8. Impeller jammed or loose on shaft, worn or 
damaged, impeller cavity or inlet plugged.
9. Pump may be airlocked.
10. Pump running backwards

Pump cycles too frequently or runs 
periodically when fi xtures are not in use

6. Check valve stuck closed or installed backwards.
11. Fixtures are leaking.
15. Ground water entering basin.

Pump shuts off and turns on independent of 
switch, (trips thermal overload protector). 

CAUTION!

  Pump may start unexpectedly. 

Disconnect power supply.

1. Incorrect voltage.
4. Excessive infl ow or pump not properly sized for 
application.
8. Impeller jammed, loose on shaft, worn or dam-
aged, impeller cavity or inlet plugged.
12. Excessive water temperature. 
(internal protection only)

Pump operates noisily or vibrates excessively

2c. Worn bearings, motor shaft bent.
5. Debris in impeller cavity or broken impeller
10. Pump running backwards
13. Piping attachments to buiding structure too 
rigid or too loose.

Summary of Contents for 3SE-L Series

Page 1: ... product improvement program product changes may occur As such Crane Pumps Systems reserves the right to change product without prior written notification 420 Third Street 83 West Drive Brampton Piqua Ohio 45356 Ontario Canada L6T 2J6 Phone 937 778 8947 Phone 905 457 6223 Fax 937 773 7157 Fax 905 457 2650 www cranepumps com Form No 132724 Rev C Series 3SE L 1 5 2HP 1750RPM 60Hz Single Seal Manual I...

Page 2: ... Figure 11 15 EXPLODED VIEW Figure 12 16 PARTS LIST 17 18 WARRANTY 19 WARRANTY REGISTRATION 20 RETURNED GOODS POLICY 20 SPECIAL TOOLS AND EQUIPMENT INSULATION TESTER MEGGER DIELECTRIC TESTER SEAL TOOL KIT see parts list PRESSURE GAUGE KIT see parts list Other brand and product names are trademarks or registered trademarks of their respective holders Barnes is a registered trademark of Crane Pumps ...

Page 3: ...sert fingers in pump with power connected Always wear eye protection when working on pumps Make sure lifting handles are securely fastened each time before lifting DO NOT operate pump without safety devices in place Always replace safety devices that have been removed during service or repair Secure the pump in its operating position so it can not tip over fall or slide DO NOT exceed manufacturers ...

Page 4: ...tion Class B for 1 5 2HP Class F on selected models SINGLE PHASE Permanent Split Capacitor PSC includes overload protection in motor THREE PHASE 200 230 460 60Hz is Tri voltage motor 575V Requires overload protection to be included in control panel OPTIONAL EQUIPMENT Seal Material Impeller Trims Additional Cord Normally Closed Temperature Sensors with cord for 3 phase pumps Requires relay in contr...

Page 5: ...use in a sump lift station or basin The sump lift station or basin shall be vented in accordance with local plumbing codes This pump is designed to pump sewage effluent or other nonexplosive or noncorrosive wastewater and shall NOT be installed in locations classified as Class I Division 1 hazardous in accordance with the National Electrical Code NEC ANSI NFPA 70 or The Canadian Electrical Code Neve...

Page 6: ...LOAD CONDITION OCCURS If current through the temperature sensor exceeds the values listed an intermediate control circuit relay must be used to reduce the current or the sensor will not work properly TEMPERATURE SENSOR ELECTRICAL RATINGS Volts Continuous Amperes Inrush Amperes 220 240 1 50 15 0 440 480 0 75 7 5 575 600 0 60 6 0 C 4 4 Wire Size Consult a qualified electrician for proper wire size if...

Page 7: ...5 8 84 8 92 3SE1554L 1 5 575 3 60 1750 G B 4 6 16 4 14 4 SOOW SOW 0 57 14 5 13 79 13 95 3SE2024L 2 0 230 1 60 1750 A F 19 0 44 6 10 3 SOOW SOW 0 66 16 8 1 21 2 80 1 35 4 20 3SE2094L 2 0 200 230 3 60 1750 B D F 15 2 13 2 35 8 41 2 12 4 SOOW SOW 0 68 17 4 2 21 2 23 3SE2044L 2 0 460 3 60 1750 D F 6 6 20 6 14 4 SOOW SOW 0 57 14 5 8 84 8 92 3SE2054L 2 0 575 3 60 1750 D B 5 2 16 4 14 4 SOOW SOW 0 57 14 ...

Page 8: ...Use soap solution around the sealed areas and inspect joints for air bubbles If after five minutes the pressure is still holding constant and no bubbles are observed slowly bleed the pressure and remove the gauge assembly Replace oil as described in paragraph F 1 4 If the pressure does not hold then the leak must be located and repaired Pumps that have NOT had the oil drained from the Motor Housing...

Page 9: ... the terminal block 23 Be sure to leave slack on the motor leads connected underneath Use needle nose pliers to pull each female connector off of the pins on the underside of the terminal block 23 see Figure 5 The unit voltage should be noted Repeat cable and terminal block removal procedure for any control cables 32 if equipped Remove socket head cap screws 9 Vertically lift the motor housing 5 f...

Page 10: ...ring 40 into groove in terminal block and lubricate with dielectric oil Press the terminal block 23 38 optional into the housing so it seats completely below the snap ring groove Place snap ring 41 into groove in cable entry bore of housing Repeat terminal block installation for control cable if equipped F 3 4 Cable Assemblies Power Control Cable Refill the cooling oil as outlined in paragraph F 1 ...

Page 11: ...see Figure 8 With polished surface of rotating member 31b facing inward toward stationary member 31a slide rotating member 31b over bullet and onto shaft using seal pusher until polished faces of 31a and 31b are together see Figure 9 It is extremely important to keep seal faces clean during assembly Dirt particles lodged between these faces will cause the seal to leak Place spring 31c over shaft a...

Page 12: ... design configuration This number is used for ordering and obtaining information G 3 MODEL NUMBER This designation consists of numbers and letters which represent the discharge size series horsepower motor phase and voltage speed and pump design This number is used for ordering and obtaining information G 4 SERIAL NUMBER The serial number block will consist of a six digit number which is specific to...

Page 13: ...13 FIGURE 10 ...

Page 14: ...k impeller for freedom of operation security and condition Clean impeller and inlet of any obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so that the suction is always flooded Clean vent hole 10 Check rotation If power supply is three phase reverse any two of three power supply leads to ensure proper impeller rotation 11 Repair fixtures...

Page 15: ...15 FIGURE 11 ...

Page 16: ...16 FIGURE 12 ...

Page 17: ...e 18 3 105149A Wire Assemblies 3 Phase 230V 19 1 014270 Pipe Plug 375 NPT 20 1 084382MA Motor 3SE1524L 3SE2024L 084383MA 3SE1594L 3SE1544L 084383MA 3SE2094L 3SE2044L 092856 3SE1554L 3SE2054L 21 1 036391 Capacitor 1 phase 370V 45MFD 22 1 039858 Capacitor Bracket 1 phase 23 1 See Table 2 Terminal Block 24 1 084399 Volute 25 1 625 02117 Sleeve Fiberglass 230V 1 Phase 460V 3 Phase 575V 3 Phase 2 625 0...

Page 18: ...ENSOR TERMINAL BLOCK TEMP SENSOR 3SE1524L None None None None 3SE1594L 103741XC 103741XF 103741XL 103584 3SE1544L 113288XC 113288XF 113288XL 113272 3SE1554L 113288XC 113288XF 113288XL 113272 3SE2024L None None None None 3SE2094L 103741XC 103741XF 103741XL 103584 3SE2044L 113288XC 113288XF 113288XL 113272 3SE2054L 113288XC 113288XF 113288XL 113272 TABLE 3 IMPELLER ITEM 29 DIAMETER 1 5 2HP 7 00 0844...

Page 19: ...es between the results of eld testing conducted by or for user and laboratory tests corrected for eld performance the latter shall control RECOMMENDATIONS FOR SPECIAL APPLICATIONS OR THOSE RESULTING FROM SYSTEMS ANALYSES AND EVALUATIONS WE CONDUCT WILL BE BASED ON OUR BEST AVAILABLE EXPERIENCE AND PUBLISHED INDUSTRY INFORMATION SUCH RECOMMENDATIONS DO NOT CONSTITUTE A WARRANTY OF SATISFACTORY PERF...

Page 20: ...ent To Insure That Employees Will Not Be Exposed To Health Hazards In Handling Said Material All Applicable Laws And Regulations Shall Apply IMPORTANT WARRANTY REGISTRATION Your product is covered by the enclosed Warranty To complete the Warranty Registration Form go to http www cranepumps com ProductRegistration If you have a claim under the provision of the warranty contact your local Crane Pump...

Reviews: