Bard WH612 Installation Instructions Manual Download Page 9

Manual

2100-480

Page

9 of 24

INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

1. Two holes for the supply and return air openings

must be cut through the wall as shown in Figure 4.

2. On wood frame walls, the wall construction must be

strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.

3. Concrete block walls must be thoroughly inspected

to insure that they are capable of carrying the weight
of the installed unit.

MOUNTING THE UNIT

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides.  A bottom mounting bracket is provided
for ease of installation, but is not required.

2. The unit itself is suitable for 0 inch clearance, but

the supply air duct flange and the first 3 feet of
supply air duct require a minimum of 1/4 inch
clearance to combustible material.  If a combustible
wall use a minimum of 30½" x 10½" dimensions for
sizing.  However, it is generally recommended that a
1-inch clearance is used for ease of installation and
maintaining the required clearance to combustible
material.  The supply air opening would then be
32" x 12".  See Figures 4 and 5 for details.

        WARNING

Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
fire causing property damage, injury or death.

3. Locate and mark lag bolt locations and bottom

mounting bracket location.  See Figure 4.

4. Mount bottom mounting bracket.

5. Hook top rain flashing under back bend of top.  Top

rain flashing is shipped with unit attached to back of
unit on the right side of the supply and return
openings.

 6. Position unit in opening and secure with 5/16 lag

bolts; use 3/4 inch diameter flat washers on the lag
bolts.

7. Secure rain flashing to wall and caulk across entire

length of top.  See Figure 4.

8. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction).  Be sure to
observe required clearance if combustible wall.

9. On side-by-side installations, maintain a minimum

of 20 inches clearance on right side to allow access
to control panel and heat strips, and to allow proper
airflow to the outdoor coil.  Additional clearance
may be required to meet local or national codes.

       WARNING

Fire hazard can result if 1/4 inch clearance to
combustible materials for supply air duct is
not maintained.  See Figure 5.

Summary of Contents for WH612

Page 1: ...4 INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Model WH612 Manual 2100 480 Supersedes NEW File Volume III Tab 17 Date 12 19 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 M...

Page 2: ...ormance 23 Table 10 Maximum ESP of Operation 23 Table 11 Pressure Table Cooling 24 Table 12 Pressure Table Heating 24 Getting Other Information and Publications For More Information 3 Wall Mount Gener...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...L MODULES CAPACITY 61 5 ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISIONS KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate C Commercial Ventilator Motor...

Page 5: ...h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q A B C B 2 1 6 H W 2 4 4 1 2 2 8 7 4 9 8 7 9 8 7 9 2 8 7 5 1 8 7 9 2 8 7 3 4 9 1 8 5 1 4 0 3 6 1 1 1 2 4 7 3 4 3 4...

Page 6: ...of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance w...

Page 7: ...e Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used RFG filter is not included must order separately Contact distributor or factory for ordering information If using a...

Page 8: ...pen or vented type system to assure proper drainage FIGURE 3 CONDENSATE DRAINS CONDENSATE DRAIN CONDENSER A hole is provided in the unit base to accept a Drain Connection Kit 8620 160 This allows conn...

Page 9: ...2 x 12 See Figures 4 and 5 for details WARNING Failure to provide the 1 4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing prope...

Page 10: ...ng at time of installation MIS 796 A Top flashing detail view Attach supplied rain flashing Apply caulk between flashing and wall Foam air seal Seal with bead of caulking along entire length of top Su...

Page 11: ...is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Page 12: ...Manual 2100 480 Page 12 of 24 FIGURE 6 WALL MOUNTING INSTRUCTIONS FIGURE 7 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 13: ...Manual 2100 480 Page 13 of 24 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS...

Page 14: ...isconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See...

Page 15: ...f the heating equipment to the individual structure Utilization of the heating Application Data and the heat loss calculation of the building are useful in determining the correct set points Temperatu...

Page 16: ...ulling in second stage heat when coming off set back conditions OPTIONAL COMPRESSOR CUTOFF THERMOSTAT See Figures 10 and 11 Heat pump compressor operation at outdoor temperatures below 0 F are neither...

Page 17: ...a e h e g a t s 2 l o o c e g a t s 2 e l b a m m a r g o r P n o N c i n o r t c e l E r e v o e g n a h c l a u n a M r o o t u A 0 6 0 3 0 4 8 5 4 4 0 2 1 1 t a e H e g a t s 3 l o o C e g a t s 3...

Page 18: ...ng See the Phase Monitor section later in this manual Verification of proper rotation must be made any time a compressor is changed or rewired If improper rotation is corrected at this time there will...

Page 19: ...now in operation The second option has no Auto changeover position but instead energizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in Heat position the B...

Page 20: ...waiting for the outdoor ambient to fall into the defrost region FIGURE 15 DEFROST CONTROL BOARD By placing a jumper across the SEN JMP terminals a 1 4 inch QC terminal works best the defrost sensor m...

Page 21: ...c p m u p t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n...

Page 22: ...507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0...

Page 23: ...w o L 5 0 A 8 0 A 0 1 A 0 2 A 3 3 3 3 3 3 3 3 9 0 B 3 3 9 0 C 3 3 Rated CFM and ESP on high speed tap TABLE 8 RATED CFM RATED ESP l e d o M d e t a R M F C d e t a R P S E d e d n e m m o c e R e g n...

Page 24: ...i S h g i H 2 7 1 9 1 4 7 8 0 2 5 7 5 2 2 7 7 2 4 2 8 7 1 6 2 0 8 9 7 2 1 8 8 9 2 1 8 8 1 3 2 8 8 3 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 5 7 8 9 1 7 7 5 1 2 8 7 3 3 2 0 8 0 5 2...

Reviews: