Bard WH612 Installation Instructions Manual Download Page 14

Manual 2100-480
Page

14 of 24

WIRING  –  MAIN POWER

Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR” type circuit breaker
size.  Each outdoor unit is marked with a “Minimum
Circuit Ampacity”.  This means that the field wiring
used must be sized to carry that amount of current.
Depending on the installed KW of electric heat, there
may be two  field power circuits required.  If this is the
case, the unit serial plate will so indicate.  All models
are suitable only for connection with copper wire.  Each
unit and/or wiring diagram will be marked “Use Copper
Conductors Only”.  These instructions 

must be 

adhered

to.  Refer to the National Electrical Code (NEC) for
complete current carrying capacity data on the various
insulation grades of wiring material.  All wiring must
conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°C
copper) for all models including the most commonly
used heater sizes.  Also shown are the number of field
power circuits required for the various models with
heaters.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is to
be used with the equipment.  The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.

The disconnect access door on this unit  may be locked
to prevent unauthorized access to the disconnect.  To
convert for the locking capability, bend the tab locate in
the bottom left hand corner of the disconnect opening
under the disconnect access panel straight out.  This tab
will now line up with the slot in the door.  When shut a
padlock may be placed through the hole in the tab
preventing entry.

See “Start Up” section for important information on
three phase scroll compressor start ups.

TABLE  3

THERMOSTAT WIRE SIZE

r

e

m

r

o

f

s

n

a

r

T

A

V

A

L

F

e

g

u

a

G

e

r

i

W

m

u

m

i

x

a

M

e

c

n

a

t

s

i

D

t

e

e

F

n

i

5

5

3

.

2

e

g

u

a

g

0

2

e

g

u

a

g

8

1

e

g

u

a

g

6

1

e

g

u

a

g

4

1

e

g

u

a

g

2

1

5

4

0

6

0

0

1

0

6

1

0

5

2

WIRING  –  LOW VOLTAGE WIRING

230/208V, 1-phase and 3-phase equipment dual primary
voltage transformers.  All equipment leaves the factory
wired on 240V tap.  For 208V operation, reconnect from
240V to 208V tap.  The acceptable operating voltage
range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field

power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).

If no motorized vent option is used, nine (9) wires
should be run from the thermostat subbase to the 24V
terminal board in the unit.  A nine (9) conductor, 18
gauge copper color-coded thermostat cable is
recommended.  If a motorized vent option is used,
terminal O1 on the unit low voltage terminal block will
also be used.  This requires a ten (10) conductor
thermostat cable to be run.  The connection points are
shown in Figure 9.

IMPORTANT

Only the thermostats shown in this Manual
have been tested with this equipment for
proper operation.  Proper unit operation with
thermostats not listed in this Manual, cannot
be assured.

You assume responsibility for proper
operation of the unit when using thermostats
other than those listed in this Manual.

FIGURE  9

UNIT 24V TERMINAL BOARD

Summary of Contents for WH612

Page 1: ...4 INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Model WH612 Manual 2100 480 Supersedes NEW File Volume III Tab 17 Date 12 19 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 M...

Page 2: ...ormance 23 Table 10 Maximum ESP of Operation 23 Table 11 Pressure Table Cooling 24 Table 12 Pressure Table Heating 24 Getting Other Information and Publications For More Information 3 Wall Mount Gener...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...L MODULES CAPACITY 61 5 ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISIONS KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate C Commercial Ventilator Motor...

Page 5: ...h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q A B C B 2 1 6 H W 2 4 4 1 2 2 8 7 4 9 8 7 9 8 7 9 2 8 7 5 1 8 7 9 2 8 7 3 4 9 1 8 5 1 4 0 3 6 1 1 1 2 4 7 3 4 3 4...

Page 6: ...of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance w...

Page 7: ...e Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used RFG filter is not included must order separately Contact distributor or factory for ordering information If using a...

Page 8: ...pen or vented type system to assure proper drainage FIGURE 3 CONDENSATE DRAINS CONDENSATE DRAIN CONDENSER A hole is provided in the unit base to accept a Drain Connection Kit 8620 160 This allows conn...

Page 9: ...2 x 12 See Figures 4 and 5 for details WARNING Failure to provide the 1 4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing prope...

Page 10: ...ng at time of installation MIS 796 A Top flashing detail view Attach supplied rain flashing Apply caulk between flashing and wall Foam air seal Seal with bead of caulking along entire length of top Su...

Page 11: ...is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Page 12: ...Manual 2100 480 Page 12 of 24 FIGURE 6 WALL MOUNTING INSTRUCTIONS FIGURE 7 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 13: ...Manual 2100 480 Page 13 of 24 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS...

Page 14: ...isconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See...

Page 15: ...f the heating equipment to the individual structure Utilization of the heating Application Data and the heat loss calculation of the building are useful in determining the correct set points Temperatu...

Page 16: ...ulling in second stage heat when coming off set back conditions OPTIONAL COMPRESSOR CUTOFF THERMOSTAT See Figures 10 and 11 Heat pump compressor operation at outdoor temperatures below 0 F are neither...

Page 17: ...a e h e g a t s 2 l o o c e g a t s 2 e l b a m m a r g o r P n o N c i n o r t c e l E r e v o e g n a h c l a u n a M r o o t u A 0 6 0 3 0 4 8 5 4 4 0 2 1 1 t a e H e g a t s 3 l o o C e g a t s 3...

Page 18: ...ng See the Phase Monitor section later in this manual Verification of proper rotation must be made any time a compressor is changed or rewired If improper rotation is corrected at this time there will...

Page 19: ...now in operation The second option has no Auto changeover position but instead energizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in Heat position the B...

Page 20: ...waiting for the outdoor ambient to fall into the defrost region FIGURE 15 DEFROST CONTROL BOARD By placing a jumper across the SEN JMP terminals a 1 4 inch QC terminal works best the defrost sensor m...

Page 21: ...c p m u p t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n...

Page 22: ...507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0...

Page 23: ...w o L 5 0 A 8 0 A 0 1 A 0 2 A 3 3 3 3 3 3 3 3 9 0 B 3 3 9 0 C 3 3 Rated CFM and ESP on high speed tap TABLE 8 RATED CFM RATED ESP l e d o M d e t a R M F C d e t a R P S E d e d n e m m o c e R e g n...

Page 24: ...i S h g i H 2 7 1 9 1 4 7 8 0 2 5 7 5 2 2 7 7 2 4 2 8 7 1 6 2 0 8 9 7 2 1 8 8 9 2 1 8 8 1 3 2 8 8 3 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 5 7 8 9 1 7 7 5 1 2 8 7 3 3 2 0 8 0 5 2...

Reviews: