background image

Manual    2100-441
Page      4

Air Conditioning Contractors of America (ACCA).  The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

DUCT WORK

Any heat pump is more critical of proper operating
charge and an adequate duct system than a straight air
conditioning unit.  All duct work, supply and return,
must be properly sized for the design air flow
requirement of the equipment.  Air Conditioning
Contractors of America (ACCA) is an excellent guide
to proper sizing.  All duct work or portions thereof not
in the conditioned space should be properly insulated in
order to both conserve energy and prevent condensation
or moisture damage.

Refer to Table 10 for maximum static pressure
available for duct design.

Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of the
insulation.  Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.

A 1/4 inch clearance to combustible material for the
first three feet of duct attached to the outlet air frame is
required.  See Pages Wall Mounting Instructions and
Figure 3 for further details.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture from entering
the wall cavity.

CAUTION:  Some installations may not require any
return air duct.  A metallic return air grille is
required with installations not requiring a return air
duct.  The spacing between louvers on the grille shall
not be larger than 5/8 inches.

TABLE  2

ELECTRICAL SPECIFICATIONS

T

I

U

C

R

I

C

E

L

G

N

I

S

l

e

d

o

M

d

e

t

a

R

s

t

l

o

V

d

n

a

e

s

a

h

P

d

l

e

i

F

.

o

N

r

e

w

o

P

s

t

i

u

c

r

i

C

3

m

u

m

i

n

i

M

t

i

u

c

r

i

C

y

t

i

c

a

p

m

A

1

m

u

m

i

x

a

M

l

a

n

r

e

t

x

E

r

o

e

s

u

F

t

i

u

c

r

i

C

r

e

k

a

e

r

B

2

d

l

e

i

F

r

e

w

o

P

e

z

i

S

e

r

i

W

2

d

n

u

o

r

G

e

z

i

S

e

r

i

W

Z

0

A

,

0

0

A

D

3

4

2

H

W

4

0

A

8

0

A

1

-

8

0

2

/

0

3

2

1
1
1

8

1

9

3

0

6

5

2

0

4

0

6

2

1

0

1

6

2

1

0

1

0

1

Z

0

B

,

0

0

B

D

3

4

2

H

W

6

0

B

1

-

8

0

2

/

0

3

2

1
1

5

1

3

3

0

2

5

3

2

1

8

2

1

0

1

Z

0

C

,

0

0

C

D

3

4

2

H

W

6

0

C

3

-

0

6

4

1
1

8

7

1

5

1

0

2

4

1

2

1

4

1

2

1

Maximum size of the time delay fuse or HACR type circuit breaker for protection
of field wiring conductors.

Based on 75° C copper wire.  All wiring must conform to NEC and all local
codes.

These “Minimum Circuit Ampacity” values are to be used for sizing the field
power conductors.  Refer to the National Electric Code (latest revision), article
310, for power conductor sizing.    CAUTION:  When more than one field power
conductor circuit is run through one conduit the conductors must be derated.
Pay special attention to note 89 of table 310 regarding Ampacity Adjustment
Factors when more than 3 are in a raceway.

Q

R

S

Summary of Contents for WH243D

Page 1: ...TRUCTIONS WALL MOUNTED PACKAGE HEAT PUMP Model WH243D Manual 2100 441 Supersedes File Volume III Tab 17 Date 10 23 03 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planne...

Page 2: ...11 Fan Blade Setting 18 Figure 12 Circuit Diagram H P Cooling Mode 22 Figure 13 Circuit Diagram H P Dehumidification 22 Start Up Important Installer Note 13 Crankcase Heaters 13 Service Hints 13 Seque...

Page 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washingt...

Page 4: ...red in this manual is to be installed by trained experienced service and installation technicians The refrigerant system is completely assembled and charged All internal wiring is complete The unit is...

Page 5: ...i n U h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B D 3 4 2 H W 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2...

Page 6: ...three feet of duct attached to the outlet air frame is required See Pages Wall Mounting Instructions and Figure 3 for further details Ducts through the walls must be insulated and all joints taped or...

Page 7: ...bly and sliding the brackets apart to the required width and retightening the four 4 screws FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is...

Page 8: ...airflow to the outdoor coil Additional clearance may be required to meet local or national codes WIRING MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or HACR...

Page 9: ...Manual 2100 441 Page 7 FIGURE 3 MOUNTINGINSTRUCTIONS MIS 353...

Page 10: ...Manual 2100 441 Page 8 FIGURE 5 WALLMOUNTINGINSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS MIS 549 MIS 548 FIGURE 4 WALLMOUNTINGINSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS...

Page 11: ...Manual 2100 441 Page 9 FIGURE 6 COMMONWALLMOUNTINGINSTALLATIONS MIS 550...

Page 12: ...in Table 4 will work with this equipment The thermostat and subbase must be matched and the correct operation can be assured only be proper selection and application of these parts FIGURE 7 WHXXXDX H...

Page 13: ...wn in Table 4 will work with this equipment The thermostat and subbase must be matched and the correct operation can be assured only be proper selection and application of these parts FIGURE 8 WHXXXDX...

Page 14: ...ockout output This terminal is activated on a high or low pressure trip by the electronic heat pump control This is a 24 VAC output W2 terminal is second stage heat if equipped O1 terminal is the vent...

Page 15: ...fuses or circuit breakers to be sure they are the correct rating 5 Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential SEQUENCE OF OPERATION OCCUPIED...

Page 16: ...g the compressor and reversing valve of the unit are energized to provide heat pump heating If the room temperature falls below the 2nd stage heating set point backup electric heat is energized Heat p...

Page 17: ...frost operation of the unit without waiting for the outdoor ambient to fall into the defrost region By placing a jumper across the SEN JMP terminals a 1 4 inch QC terminal works best the defrost senso...

Page 18: ...c a t n o C l i o c d e t r o h s r o n e p o r o f k c e h C g n i d n i w r o t c a t n o c e c a l p e R r o t o m r o o d t u o n a F g n i l o o c n u r t o n s e o d t p e c x e g n i t a e h r...

Page 19: ...17434 16984 16547 16122 15710 15310 14921 14544 14177 13820 13474 13137 12810 12492 12183 11883 11591 11307 11031 10762 75 0 76 0 77 0 78 0 79 0 80 0 81 0 82 0 83 0 84 0 85 0 86 0 87 0 88 0 89 0 90 0...

Page 20: ...emperature 6 from compressor as shown in Table 7 The suction line temperatures shown in Table 7 are based upon 80 F dry bulb 67 F wet bulb 50 R H temperature and rated airflow across the evaporator du...

Page 21: ...3 4 2 H W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 5 7 6 1 2 6 7 9 2 2 7 7 2 4 2 9 7 6 5 2 0 8 1 7 2 1 8 6 8 2 3 8 2 0 3 4 8 8 1 3 6 8 6 3 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L...

Page 22: ...r e p m a D r i A h s e r F c i r t e m o r a B r e p m a D r i A h s e r F d e z i r o t o M t s u a h x E h t i w r o t a l i t n e V m o o r s s a l C t s u a h x E h t i w r e z i m o n o c E r o...

Page 23: ...d e i p u c c o n U X X X X X X X X X g n i t a e H e g a t S d n 2 d e i p u c c O X X X X X X X X X X X g n i t a e H e g a t S d n 2 m u h e D W X X X X X X X X X X t a e H y c n e g r e m E d e i...

Page 24: ...V 2 THRU 3 1 2 TON USE ORIFICE OUTDOOR COIL INDOOR COIL REHEAT COIL 4 WAY VALVE CHECK VALVE CAPILLARY DRAIN ASSY 3 WAY VALVE COMPRESSOR TXV 2 THRU 3 1 2 TON USE ORIFICE OUTDOOR COIL FIGURE 12 BARD MFG...

Reviews: