background image

Manual    2100-441
Page        13

START UP

IMPORTANT INSTALLER NOTE

For improved start up performance, wash the indoor
coil with a dish detergent.

CRANKCASE HEATERS

WH243 units are provided with compressor crankcase
heat.

These models have an insertion well-type heater located
in the lower section of the compressor housing.  This is
a self-regulating type heater that draws only enough
power to maintain the compressor at a safe temperature.

Some form of crankcase heat is essential to prevent
liquid refrigerant from migrating to the compressor
causing oil pump out on compressor start up and
possible valve failure.

The decal in Figure 9 is affixed to all outdoor units
detailing start up procedure.  This is very important.
Please read carefully.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at

all times.  Also, not to needlessly close off supply
and return air registers.  This reduces air flow
through the system which shortens equipment
service life as well as increasing operating costs.

2. Switching to heating cycle at 75° F or higher outside

temperature may cause a nuisance trip of the remote
reset high pressure switch.  Turn thermostat off,
then on, to reset the high pressure switch..

3. The heat pump wall thermostats perform multiple

functions.  Be sure that all function switches are
correctly set for the desired operating mode before
trying to diagnose any reported service problems.

4. Check all power fuses or circuit breakers to be sure

they are the correct rating.

5. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

OCCUPIED MODE

VENTILATION SEQUENCE

 –  The ERV and indoor

blower will be continuously energized when the A1
terminal is energized.

IMPORTANT

THESE PROCEDURES MUST BE
FOLLOWED AT INITIAL START UP
AND AT ANY TIME POWER HAS
BEEN REMOVED FOR 12 HOURS
OR LONGER.

TO PREVENT COMPRESSOR DAMAGE
WHICH MAY RESULT FROM THE PRESENCE
OF LIQUID REFRIGERANT IN THE COM-
PRESSOR CRANKCASE:

1. MAKE CERTAIN THE ROOM THERMOSTAT

IS IN THE “OFF” POSITION. (THE COM-
PRESSOR IS NOT TO OPERATE.)

2. APPLY POWER BY CLOSING THE SYSTEM

DISCONNECT SWITCH.  THIS ENERGIZES
THE COMPRESSOR HEATER WHICH
EVAPORATES THE LIQUID REFRIGERANT
IN THE CRANKCASE.

3. ALLOW 4 HOURS OR 60 MINUTES PER

POUND OF REFRIGERANT IN THE SYSTEM
AS NOTED ON THE UNIT RATING PLATE,
WHICHEVER IS GREATER.

4. AFTER PROPERLY ELAPSED TIME THE

THERMOSTAT MAY BE SET TO OPERATE
THE COMPRESSOR.

5. EXCEPT AS REQUIRED FOR SAFETY

WHILE SERVICING  — DO NOT OPEN
SYSTEM DISCONNECT SWITCH.

FIGURE 9

START UP LABEL

7961-061

COOLING SEQUENCE

  –  On a call for cooling, the

compressor of the unit is energized to provide cooling.
A call for cooling cancels dehumidification mode.
Cooling mode is only available when the timer  is
energized.

Circuit R-Y makes at thermostat pulling in compressor
contactor, starting the compressor and outdoor motor.
The G (indoor motor) circuit is automatically completed
on any call for cooling operation or can be energized by
manual fan switch on subbase for constant air
circulation.

Summary of Contents for WH243D

Page 1: ...TRUCTIONS WALL MOUNTED PACKAGE HEAT PUMP Model WH243D Manual 2100 441 Supersedes File Volume III Tab 17 Date 10 23 03 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planne...

Page 2: ...11 Fan Blade Setting 18 Figure 12 Circuit Diagram H P Cooling Mode 22 Figure 13 Circuit Diagram H P Dehumidification 22 Start Up Important Installer Note 13 Crankcase Heaters 13 Service Hints 13 Seque...

Page 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washingt...

Page 4: ...red in this manual is to be installed by trained experienced service and installation technicians The refrigerant system is completely assembled and charged All internal wiring is complete The unit is...

Page 5: ...i n U h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B D 3 4 2 H W 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2...

Page 6: ...three feet of duct attached to the outlet air frame is required See Pages Wall Mounting Instructions and Figure 3 for further details Ducts through the walls must be insulated and all joints taped or...

Page 7: ...bly and sliding the brackets apart to the required width and retightening the four 4 screws FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is...

Page 8: ...airflow to the outdoor coil Additional clearance may be required to meet local or national codes WIRING MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or HACR...

Page 9: ...Manual 2100 441 Page 7 FIGURE 3 MOUNTINGINSTRUCTIONS MIS 353...

Page 10: ...Manual 2100 441 Page 8 FIGURE 5 WALLMOUNTINGINSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS MIS 549 MIS 548 FIGURE 4 WALLMOUNTINGINSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS...

Page 11: ...Manual 2100 441 Page 9 FIGURE 6 COMMONWALLMOUNTINGINSTALLATIONS MIS 550...

Page 12: ...in Table 4 will work with this equipment The thermostat and subbase must be matched and the correct operation can be assured only be proper selection and application of these parts FIGURE 7 WHXXXDX H...

Page 13: ...wn in Table 4 will work with this equipment The thermostat and subbase must be matched and the correct operation can be assured only be proper selection and application of these parts FIGURE 8 WHXXXDX...

Page 14: ...ockout output This terminal is activated on a high or low pressure trip by the electronic heat pump control This is a 24 VAC output W2 terminal is second stage heat if equipped O1 terminal is the vent...

Page 15: ...fuses or circuit breakers to be sure they are the correct rating 5 Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential SEQUENCE OF OPERATION OCCUPIED...

Page 16: ...g the compressor and reversing valve of the unit are energized to provide heat pump heating If the room temperature falls below the 2nd stage heating set point backup electric heat is energized Heat p...

Page 17: ...frost operation of the unit without waiting for the outdoor ambient to fall into the defrost region By placing a jumper across the SEN JMP terminals a 1 4 inch QC terminal works best the defrost senso...

Page 18: ...c a t n o C l i o c d e t r o h s r o n e p o r o f k c e h C g n i d n i w r o t c a t n o c e c a l p e R r o t o m r o o d t u o n a F g n i l o o c n u r t o n s e o d t p e c x e g n i t a e h r...

Page 19: ...17434 16984 16547 16122 15710 15310 14921 14544 14177 13820 13474 13137 12810 12492 12183 11883 11591 11307 11031 10762 75 0 76 0 77 0 78 0 79 0 80 0 81 0 82 0 83 0 84 0 85 0 86 0 87 0 88 0 89 0 90 0...

Page 20: ...emperature 6 from compressor as shown in Table 7 The suction line temperatures shown in Table 7 are based upon 80 F dry bulb 67 F wet bulb 50 R H temperature and rated airflow across the evaporator du...

Page 21: ...3 4 2 H W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 5 7 6 1 2 6 7 9 2 2 7 7 2 4 2 9 7 6 5 2 0 8 1 7 2 1 8 6 8 2 3 8 2 0 3 4 8 8 1 3 6 8 6 3 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L...

Page 22: ...r e p m a D r i A h s e r F c i r t e m o r a B r e p m a D r i A h s e r F d e z i r o t o M t s u a h x E h t i w r o t a l i t n e V m o o r s s a l C t s u a h x E h t i w r e z i m o n o c E r o...

Page 23: ...d e i p u c c o n U X X X X X X X X X g n i t a e H e g a t S d n 2 d e i p u c c O X X X X X X X X X X X g n i t a e H e g a t S d n 2 m u h e D W X X X X X X X X X X t a e H y c n e g r e m E d e i...

Page 24: ...V 2 THRU 3 1 2 TON USE ORIFICE OUTDOOR COIL INDOOR COIL REHEAT COIL 4 WAY VALVE CHECK VALVE CAPILLARY DRAIN ASSY 3 WAY VALVE COMPRESSOR TXV 2 THRU 3 1 2 TON USE ORIFICE OUTDOOR COIL FIGURE 12 BARD MFG...

Reviews: