Manual 2100-483E
Page
16 of 59
9.
CLEARANCES
Minimum clearances, as specified in Table 2, must be
maintained from adjacent structures to provide
adequate fire protection, adequate combustion air, and
room for service personnel.
While minimum clearances are acceptable for safety
reasons, they may not allow adequate air circulation
around the unit for proper operation in the cooling
mode. Whenever possible, it is desirable to allow
additional clearance, especially around the condenser
inlet and discharge openings. DO NOT install the unit
in a location that will permit discharged air from the
condenser to recirculate to the condenser inlet.
TABLE 2
MINIMUM INSTALLATION CLEARANCES
)
s
l
a
i
r
e
t
a
m
e
l
b
i
t
s
u
b
m
o
c
m
o
r
f
(
t
c
u
D
t
e
l
t
u
O
t
e
e
f
3
t
s
r
i
f
h
c
n
i
1
)
s
l
a
i
r
e
t
a
m
e
l
b
i
t
s
u
b
m
o
c
m
o
r
f
(
l
a
n
i
m
r
e
T
t
n
e
V
*
s
e
h
c
n
i
7
1
t
e
l
t
u
O
r
e
s
n
e
d
n
o
C
s
e
h
c
n
i
0
2
p
o
T
3
e
r
u
g
i
F
e
e
S
e
c
i
v
r
e
S
r
e
n
r
u
B
s
e
h
c
n
i
0
2
B
,
A
s
s
a
l
C
r
o
d
o
o
W
(
e
s
a
B
e
l
b
i
t
s
u
b
m
o
C
)
l
a
i
r
e
t
a
m
g
n
i
r
e
v
o
c
f
o
o
r
C
r
o
s
e
h
c
n
i
0
*
3
e
r
u
g
i
F
e
e
S
FIGURE 7
LOCATION OF VENT TERMINAL IN SHIPPING
WARNING
Clearances from combustible materials must
be maintained as specified. Failure to
maintain clearances could cause fire resulting
in property damage, injury, or death.
Summary of Contents for WG3S1-A
Page 11: ...Manual 2100 483E Page 11 of 59 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG3S1 ...
Page 12: ...Manual 2100 483E Page 12 of 59 FIGURE 2B MOUNTING INSTRUCTIONS FOR WG4S1 AND WG5S1 ...
Page 15: ...Manual 2100 483E Page 15 of 59 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS ...
Page 25: ...Manual 2100 483E Page 25 of 59 FIGURE 11 GAS PIPE CONNECTION ...