AIR CONDITIONING MODULE OPTIONS
STD =
Standard equipment.
1
CCM Compressor control module has adjustable 30 second to 5 minute delay-on-break
timer. On initial power up, or any time the power is interrupted, the delay-on-make
will be 2 minutes plus 10% of the delay-on-break setting. There is no delay-on-make
during routine operation of the unit. The module also provides the lockout feature (with 1
retry) for high and/or low pressure controls, and a 2 minute timed bypass for low
pressure control.
2
HPC High pressure control is auto reset. Always used with compressor control module (CCM)
which is included. See note
1
.
3
LPC Low pressure control is auto reset. Always used with compressor control module (CCM)
which is included. See note
1
.
4
LAC Low ambient control permits cooling operation down to 0°F.
1
M
C
C
2
C
P
H
3
C
P
L
4
C
A
L
d
e
l
l
a
t
s
n
I
y
r
o
t
c
a
F
e
d
o
C
d
e
l
l
a
t
s
n
I
d
l
e
i
F
t
r
a
P
D
T
S
D
T
S
G
6
1
-
A
M
C
D
T
S
D
T
S
H
8
1
-
A
M
C
D
T
S
D
T
S
I
6
-
A
M
C
1.
IMPORTANT
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians. All duct work or portions thereof not in
the conditioned space should be properly insulated in
order to both conserve energy and prevent condensation
or moisture damage.
2. APPLICATION
This is a fan-assisted forced air gas furnace with
electric air conditioning for outdoor installation. A fan-
assisted furnace is equipped with an integral
mechanical means to draw products of combustion
through the combustion chamber and heat exchanger.
The furnace installation must conform with local
building codes and ordinances or, in their absence, with
the National Fuel Gas Code ANSI Z223.1 or CAN/
CGA-B149.1, latest edition, and the National Electrical
Code ANSI/NFPA-7 or CSA C22.1, latest edition. It is
the personal responsibility and obligation of the
purchaser to contact a qualified installer to assure that
installation is adequate and is in conformance with
governing codes and ordinances.
3.
DUCT WORK
The unit is designed for use with or without duct work.
See Warning on Page 10. Flanges are provided for
attaching the supply and return ducts. These
instructions explain the recommended method to install
the air cooled self-contained electric air conditioning
and gas heating unit and the electrical wiring
connections and gas piping to the unit. The refrigerant
system is completely assembled and charged. All
internal wiring is complete.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
heating/cooling system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
All duct work, supply and return, must be properly sized
for the design airflow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing.
Refer to Tables later in this Manual for maximum static
pressure available for duct design.
CAUTION
During the initial firing of the burners there will probably be some amount of smoke issued to the
circulating air stream as the result of residual oil burning off of the heat exchanger tubes. This oil
is required during the forming process of the stainless steel heat exchanger tubes to facilitate the
bending. OSHA or the National Toxicology Program does not list the oil as a carcinogen. In
vapor form this may be irritating to the eyes or could cause headaches. This is a one time
occurrence, and ventilation of the space may be required depending upon the space being
conditioned.
Summary of Contents for WG242DA
Page 13: ...Manual 2100 376L Page 13 of 81 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60...
Page 16: ...Manual 2100 376L Page 16 of 81 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...
Page 22: ...Manual 2100 376L Page 22 of 81 FIGURE 11 LOW VOLTAGE WIRING...
Page 23: ...Manual 2100 376L Page 23 of 81 FIGURE 11A LOW VOLTAGE WIRING...
Page 24: ...Manual 2100 376L Page 24 of 81 FIGURE 12 GAS PIPE CONNECTION...
Page 56: ...Manual 2100 376L Page 56 of 81 WG242DA 230 208 60 1...
Page 57: ...Manual 2100 376L Page 57 of 81 WG242DA WG362DA 230 208 60 1...
Page 58: ...Manual 2100 376L Page 58 of 81 WG242DB 230 208 60 3...
Page 59: ...Manual 2100 376L Page 59 of 81 WG242DB WG362DB 230 208 60 3...
Page 60: ...Manual 2100 376L Page 60 of 81 WG243DC 460 60 3...
Page 61: ...Manual 2100 376L Page 61 of 81 WG243DC 460 60 3...
Page 62: ...Manual 2100 376L Page 62 of 81 WG302DA 230 208 60 1...
Page 63: ...Manual 2100 376L Page 63 of 81 WG302DA WG482DA WG602DA 230 208 60 1...
Page 64: ...Manual 2100 376L Page 64 of 81 WG302DB 230 208 60 3...
Page 65: ...Manual 2100 376L Page 65 of 81 WG302DB WG482DB WG602DB 230 208 60 3...
Page 66: ...Manual 2100 376L Page 66 of 81 WG303DC 460 60 3...
Page 67: ...Manual 2100 376L Page 67 of 81 WG303DC 460 60 3...
Page 68: ...Manual 2100 376L Page 68 of 81 WG362DA 230 208 60 1...
Page 69: ...Manual 2100 376L Page 69 of 81 WG362DB 230 208 60 3...
Page 70: ...Manual 2100 376L Page 70 of 81 WG363DC 460 60 3...
Page 71: ...Manual 2100 376L Page 71 of 81 WG363DC 460 60 3...
Page 72: ...Manual 2100 376L Page 72 of 81 WG423DA 230 208 60 1...
Page 73: ...Manual 2100 376L Page 73 of 81 WG423DA 230 208 60 1...
Page 74: ...Manual 2100 376L Page 74 of 81 WG423DB 230 208 60 3...
Page 75: ...Manual 2100 376L Page 75 of 81 WG423DB 230 208 60 3...
Page 76: ...Manual 2100 376L Page 76 of 81 WG424DC 460 60 3...
Page 77: ...Manual 2100 376L Page 77 of 81 WG424DC 460 60 3...
Page 78: ...Manual 2100 376L Page 78 of 81 WG482DA WG602DA 230 208 60 1...
Page 79: ...Manual 2100 376L Page 79 of 81 WG482DB WG602DB 230 208 60 3...
Page 80: ...Manual 2100 376L Page 80 of 81 WG483DC WG603DC 460 60 3...
Page 81: ...Manual 2100 376L Page 81 of 81 WG483DC WG603DC 460 60 3...