23. MEASURING AIR TEMPERATURE
RISE
Air temperature rise (supply air temperature minus
return air temperature) must be within allowable air
temperature rise range specified on furnace rating plate
and in Table 1.
You will need 2 thermometers with 1 degree resolution
capable of reading up to 200 degrees F. Check
thermometers to make sure they agree, or compensate
accordingly.
Follow this procedure:
1. Open supply air registers and return air grilles.
Make sure the registers and grilles are free of
obstruction from rugs, carpets, drapes or furniture.
22. CONVERSION OF GAS INPUT BTUH
FROM HIGH TO LOW RATING
All the derated WG series units are produced with
maximum BTUH input orifices installed. To field
convert input, a change to main burner orifices is
required.
NOTE:
No change to air orifices is necessary. A set
of low input orifices is shipped with every
unit. They will be found packaged in a bag
behind the burner door. Refer to the unit
rating plate to confirm the proper orifice size.
Proper installation of the orifices is detailed
as follows:
A. Shut off electrical supply to the unit.
B. Shut off gas supply to the unit.
C. Remove burner access panel.
D. Disconnect gas valve from gas supply piping.
E. Disconnect the two wires from the gas valve.
F. Remove the manifold assembly so that orifices are
now accessible and remove orifices.
G. Apply a modest amount of pipe compound to the
new orifices and screw them into the manifold.
H. To assemble burner reverse steps A through G.
2. Set balancing dampers in supply duct system.
3. Check duct work for obstructions or leaks.
4. Make sure filters are clean and in place.
5. Place one thermometer in supply air plenum
approximately 2 feet from furnace. Locate
thermometer tip in center of plenum to ensure proper
temperature measurement.
6. Place second thermometer in return air duct
approximately 2 feet from furnace. Locate
thermometer tip in center of duct to ensure proper
temperature measurement.
7. Set room thermostat on highest temperature setting.
Operate furnace 10 minutes. Record supply air and
return air temperatures.
8. Calculate air temperature rise by subtracting return
air temperature from supply air temperature.
•
If air temperature rise is above the temperature
rise range on rating plate, furnace is overfired
or has insufficient airflow. Check gas input
following the instructions in Section, “Checking
Gas Input Rate”. If air temperature rise is still
above temperature rise range specified, more
heating airflow is needed. Check duct work and
grilles to make sure all are properly sized.
•
If air temperature rise is below the temperature
rise range on rating plate, furnace is underfired
or has too much airflow. Check gas input
following the instructions in Section, “Checking
Gas Input Rate”. If air temperature rise is still
below temperature rise range specified, less
heating airflow is needed. Adjust dampers or
grilles as needed.
•
After making adjustments, you must check air
temperature rise to verify that resulting air
temperature rise is within allowable range. If
air temperature rise is still outside the
temperature rise range specified on rating
plate, check duct system design with a
qualified heating engineer. It may be
necessary to re-size the duct work. Recheck
air temperature rise after revising duct systems.
9. Set room thermostat to desired setting.
10. Remove thermometers and seal duct work holes.
NOTE: Failure to seal holes could result in reduced
system performance.
WARNING
Failure to follow these instructions could
create a hazard resulting in property damage,
bodily injury, or death.
Summary of Contents for WG242DA
Page 13: ...Manual 2100 376L Page 13 of 81 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60...
Page 16: ...Manual 2100 376L Page 16 of 81 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...
Page 22: ...Manual 2100 376L Page 22 of 81 FIGURE 11 LOW VOLTAGE WIRING...
Page 23: ...Manual 2100 376L Page 23 of 81 FIGURE 11A LOW VOLTAGE WIRING...
Page 24: ...Manual 2100 376L Page 24 of 81 FIGURE 12 GAS PIPE CONNECTION...
Page 56: ...Manual 2100 376L Page 56 of 81 WG242DA 230 208 60 1...
Page 57: ...Manual 2100 376L Page 57 of 81 WG242DA WG362DA 230 208 60 1...
Page 58: ...Manual 2100 376L Page 58 of 81 WG242DB 230 208 60 3...
Page 59: ...Manual 2100 376L Page 59 of 81 WG242DB WG362DB 230 208 60 3...
Page 60: ...Manual 2100 376L Page 60 of 81 WG243DC 460 60 3...
Page 61: ...Manual 2100 376L Page 61 of 81 WG243DC 460 60 3...
Page 62: ...Manual 2100 376L Page 62 of 81 WG302DA 230 208 60 1...
Page 63: ...Manual 2100 376L Page 63 of 81 WG302DA WG482DA WG602DA 230 208 60 1...
Page 64: ...Manual 2100 376L Page 64 of 81 WG302DB 230 208 60 3...
Page 65: ...Manual 2100 376L Page 65 of 81 WG302DB WG482DB WG602DB 230 208 60 3...
Page 66: ...Manual 2100 376L Page 66 of 81 WG303DC 460 60 3...
Page 67: ...Manual 2100 376L Page 67 of 81 WG303DC 460 60 3...
Page 68: ...Manual 2100 376L Page 68 of 81 WG362DA 230 208 60 1...
Page 69: ...Manual 2100 376L Page 69 of 81 WG362DB 230 208 60 3...
Page 70: ...Manual 2100 376L Page 70 of 81 WG363DC 460 60 3...
Page 71: ...Manual 2100 376L Page 71 of 81 WG363DC 460 60 3...
Page 72: ...Manual 2100 376L Page 72 of 81 WG423DA 230 208 60 1...
Page 73: ...Manual 2100 376L Page 73 of 81 WG423DA 230 208 60 1...
Page 74: ...Manual 2100 376L Page 74 of 81 WG423DB 230 208 60 3...
Page 75: ...Manual 2100 376L Page 75 of 81 WG423DB 230 208 60 3...
Page 76: ...Manual 2100 376L Page 76 of 81 WG424DC 460 60 3...
Page 77: ...Manual 2100 376L Page 77 of 81 WG424DC 460 60 3...
Page 78: ...Manual 2100 376L Page 78 of 81 WG482DA WG602DA 230 208 60 1...
Page 79: ...Manual 2100 376L Page 79 of 81 WG482DB WG602DB 230 208 60 3...
Page 80: ...Manual 2100 376L Page 80 of 81 WG483DC WG603DC 460 60 3...
Page 81: ...Manual 2100 376L Page 81 of 81 WG483DC WG603DC 460 60 3...