33. WG DEHUMIDIFICATION UNIT RELAY LOGIC
The WG Wall Mount Gas Fired Units equipped with the Dehumidification Circuit employ several components to
control the Heating, Cooling and Dehumidification process (excluding blower control). These components include
the following:
CR1
Control Relay #1
Part # 8201-071
CR2
Control Relay #2
Part # 8201-062
CR3
Control Relay #3
Part # 8201-062
TDR1
Time Delay Relay #1
Part # 8201-089
TDR2
Time Delay Relay #2
Part # 8201-045
RAT
Return Air Thermostat
Part # 8408-037
CR1
This relay completes the “Y” or compressor signal to the CCM (Compressor Control Module) during either a call for
Cooling or a call for Dehumidification.
CR2
Part of the Bard Manufacturing Company, Inc. control strategy on Dehumidification units is that Cooling always
takes precedence over Dehumidification. This relay opens the circuit to the Dehumidification Solenoid Valve on a
call for Cooling, effectively overriding the Dehumidification function in favor of the Cooling call.
CR3
This relay terminates the signal to the Dehumidification Solenoid and also the “Y” signal to the CCM during a call
for Heat.
TDR1
This time delay relay is a 10 second Delay On Break device. On shift between Cooling and Dehumidification, this
relay assures the Compressor signal does not drop to the CCM. This will keep the CCM from going into time delay
as the unit shifts from Dehumidification mode to Cooling mode and back.
TDR2
This time delay relay is a Delay On Break device. After a call for heating is terminated, this relay assures sufficient
time for the evaporator coil and heat exchanger to cool off before allowing the compressor circuit to be completed.
This protects the system in the event of a rapid mode change from Heating to Cooling.
RAT
The Return Air Thermostat is a safety device that guards against a Low Ambient condition during Dehumidification
mode that may result in coil freeze-up or damage to the system. In the event the Return Air temperature drops below
the RAT setting, the RAT will terminate the Dehumidification call. The RAT will re-establish the call for
Dehumidification when the Return Air temperature rises sufficiently for the RAT to reset.
Summary of Contents for WG242DA
Page 13: ...Manual 2100 376L Page 13 of 81 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60...
Page 16: ...Manual 2100 376L Page 16 of 81 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...
Page 22: ...Manual 2100 376L Page 22 of 81 FIGURE 11 LOW VOLTAGE WIRING...
Page 23: ...Manual 2100 376L Page 23 of 81 FIGURE 11A LOW VOLTAGE WIRING...
Page 24: ...Manual 2100 376L Page 24 of 81 FIGURE 12 GAS PIPE CONNECTION...
Page 56: ...Manual 2100 376L Page 56 of 81 WG242DA 230 208 60 1...
Page 57: ...Manual 2100 376L Page 57 of 81 WG242DA WG362DA 230 208 60 1...
Page 58: ...Manual 2100 376L Page 58 of 81 WG242DB 230 208 60 3...
Page 59: ...Manual 2100 376L Page 59 of 81 WG242DB WG362DB 230 208 60 3...
Page 60: ...Manual 2100 376L Page 60 of 81 WG243DC 460 60 3...
Page 61: ...Manual 2100 376L Page 61 of 81 WG243DC 460 60 3...
Page 62: ...Manual 2100 376L Page 62 of 81 WG302DA 230 208 60 1...
Page 63: ...Manual 2100 376L Page 63 of 81 WG302DA WG482DA WG602DA 230 208 60 1...
Page 64: ...Manual 2100 376L Page 64 of 81 WG302DB 230 208 60 3...
Page 65: ...Manual 2100 376L Page 65 of 81 WG302DB WG482DB WG602DB 230 208 60 3...
Page 66: ...Manual 2100 376L Page 66 of 81 WG303DC 460 60 3...
Page 67: ...Manual 2100 376L Page 67 of 81 WG303DC 460 60 3...
Page 68: ...Manual 2100 376L Page 68 of 81 WG362DA 230 208 60 1...
Page 69: ...Manual 2100 376L Page 69 of 81 WG362DB 230 208 60 3...
Page 70: ...Manual 2100 376L Page 70 of 81 WG363DC 460 60 3...
Page 71: ...Manual 2100 376L Page 71 of 81 WG363DC 460 60 3...
Page 72: ...Manual 2100 376L Page 72 of 81 WG423DA 230 208 60 1...
Page 73: ...Manual 2100 376L Page 73 of 81 WG423DA 230 208 60 1...
Page 74: ...Manual 2100 376L Page 74 of 81 WG423DB 230 208 60 3...
Page 75: ...Manual 2100 376L Page 75 of 81 WG423DB 230 208 60 3...
Page 76: ...Manual 2100 376L Page 76 of 81 WG424DC 460 60 3...
Page 77: ...Manual 2100 376L Page 77 of 81 WG424DC 460 60 3...
Page 78: ...Manual 2100 376L Page 78 of 81 WG482DA WG602DA 230 208 60 1...
Page 79: ...Manual 2100 376L Page 79 of 81 WG482DB WG602DB 230 208 60 3...
Page 80: ...Manual 2100 376L Page 80 of 81 WG483DC WG603DC 460 60 3...
Page 81: ...Manual 2100 376L Page 81 of 81 WG483DC WG603DC 460 60 3...