Manual 2100-376
Page 28
23. MEASURING AIR TEMPERATURE
RISE
Air temperature rise (supply air temperature minus
return air temperature) must be within allowable air
temperature rise range specified on furnace rating plate
and in Table 1.
You will need 2 thermometers with 1 degree resolution
capable of reading up to 200 degrees F. Check
thermometers to make sure they agree, or compensate
accordingly.
Follow this procedure:
1. Open supply air registers and return air grilles.
Make sure the registers and grilles are free of
obstruction from rugs, carpets, drapes or furniture.
22. CONVERSION OF GAS INPUT BTUH
FROM HIGH TO LOW RATING
All the derated WG series units are produced with
maximum BTUH input orifices installed. To field
convert input, a change to main burner orifices is
required.
NOTE: No change to air orifices is necessary. A set
of low input orifices is shipped with every
unit. They will be found packaged in a bag
behind the burner door. Refer to the unit
rating plate to confirm the proper orifice
size. Proper installation of the orifices is
detailed as follows:
A. Shut off electrical supply to the unit.
B. Shut off gas supply to the unit.
C. Remove burner access panel.
D. Disconnect gas valve from gas supply piping.
E. Disconnect the two wires from the gas valve.
F. Remove the manifold assembly so that orifices are
now accessible and remove orifices.
G. Apply a modest amount of pipe compound to the
new orifices and screw them into the manifold.
H. To assemble burner reverse steps A through G.
2. Set balancing dampers in supply duct system.
3. Check duct work for obstructions or leaks.
4. Make sure filters are clean and in place.
5. Place one thermometer in supply air plenum
approximately 2 feet from furnace. Locate
thermometer tip in center of plenum to ensure
proper temperature measurement.
6. Place second thermometer in return air duct
approximately 2 feet from furnace. Locate
thermometer tip in center of duct to ensure proper
temperature measurement.
7. Set room thermostat on highest temperature setting.
Operate furnace 10 minutes. Record supply air and
return air temperatures.
8. Calculate air temperature rise by subtracting return
air temperature from supply air temperature.
•
If air temperature rise is above the temperature
rise range on rating plate, furnace is overfired
or has insufficient airflow. Check gas input
following the instructions in Section ,
"Checking Gas Input Rate". If air temperature
rise is still above temperature rise range
specified, more heating air
flow is needed.
Check duct work and grilles to make sure all
are properly sized.
•
If air temperature rise is below the temperature
rise range on rating plate, furnace is underfired
or has too much airflow. Check gas input
following the instructions in Section ,
"Checking Gas Input Rate". If air temperature
rise is still below temperature rise range
specified, less heating air flow is needed.
Adjust dampers or grilles as needed.
•
After making adjustments, you must check air
temperature rise to verify that resulting air
temperature rise is within allowable range. If
air temperature rise is still outside the
temperature rise range specified on rating
plate, check duct system design with a
qualified heating engineer. It may be
necessary to re-size the duct work. Recheck
air temperature rise after revising duct systems.
9. Set room thermostat to desired setting.
10. Remove thermometers and seal duct work holes.
NOTE: Failure to seal holes could result in reduced
system performance.
WARNING
Failure to follow these instructions could create
a hazard resulting in property damage, bodily
injury, or death.
Summary of Contents for WG241D
Page 13: ...Manual 2100 376 Page 10 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60 MIS 1472 ...
Page 16: ...Manual 2100 376 Page 13 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS MIS 1474 ...
Page 22: ...Manual 2100 376 Page 19 FIGURE 11 LOW VOLTAGE WIRING MIS 1748 ...
Page 23: ...Manual 2100 376 Page 20 FIGURE 11A LOW VOLTAGE WIRING ...
Page 24: ...Manual 2100 376 Page 21 FIGURE 12 GAS PIPE CONNECTION MIS 1683 ...
Page 34: ...Manual 2100 376 Page 31 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL ...
Page 56: ...Manual 2100 376 Page 53 WG241DA 230 208 60 1 ...
Page 57: ...Manual 2100 376 Page 54 WG241DA 230 208 60 1 ...
Page 58: ...Manual 2100 376 Page 55 WG241DB 230 208 60 3 ...
Page 59: ...Manual 2100 376 Page 56 WG241DB 230 208 60 3 ...
Page 60: ...Manual 2100 376 Page 57 WG241DC 460 60 3 ...
Page 61: ...Manual 2100 376 Page 58 WG241DC 460 60 3 ...
Page 62: ...Manual 2100 376 Page 59 WG301DA WG361DA 230 208 60 1 ...
Page 63: ...Manual 2100 376 Page 60 WG301DA WG361DA 230 208 60 1 ...
Page 64: ...Manual 2100 376 Page 61 WG301DB WG361DB 230 208 60 3 ...
Page 65: ...Manual 2100 376 Page 62 WG301DB WG361DB 230 208 60 3 ...
Page 66: ...Manual 2100 376 Page 63 WG301DC WG361DC 460 60 3 ...
Page 67: ...Manual 2100 376 Page 64 WG301DC WG361DC 460 60 3 ...
Page 68: ...Manual 2100 376 Page 65 WG422DA 230 208 60 1 ...
Page 69: ...Manual 2100 376 Page 66 WG422DA 230 208 60 1 ...
Page 70: ...Manual 2100 376 Page 67 WG422DB 230 208 60 3 ...
Page 71: ...Manual 2100 376 Page 68 WG422DB 230 208 60 3 ...
Page 72: ...Manual 2100 376 Page 69 WG422DC 460 60 3 ...
Page 73: ...Manual 2100 376 Page 70 WG422DC 460 60 3 ...
Page 74: ...Manual 2100 376 Page 71 WG481DA WG601DA 230 208 60 1 ...
Page 75: ...Manual 2100 376 Page 72 WG481DA WG601DA 230 208 60 1 ...
Page 76: ...Manual 2100 376 Page 73 WG481DB WG601DB 230 208 60 3 ...
Page 77: ...Manual 2100 376 Page 74 WG481DB WG601DB 230 208 60 3 ...
Page 78: ...Manual 2100 376 Page 75 WG481DC WG601DC 460 60 3 ...
Page 79: ...Manual 2100 376 Page 76 WG481DC WG601DC 460 60 3 ...