Manual 2100-376
Page 7
See Figure 3 and clearance information in Section 9
and Table 2 for additional information.
Design the duct work according to methods given by
the Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of
the insulation. Flexible joints should be used to
connect the duct work to the equipment in order to
keep the noise transmission to a minimum.
A one inch clearance to combustible material for the
first three feet of duct attached to the outlet air frame
is required. See Wall Mounting Instructions and
Figures 2, 2A and 3 for further details.
Ducts through the walls must be insulated and all
joints taped or sealed to prevent air or moisture
entering the wall cavity.
Some installations may not require any return air duct.
A metallic return air grille is required with
installations not requiring a return air duct. The
spacing between louvers on the grille shall not be
larger than 5/8 inch.
Any grille that meets with the 5/8 inch louver criteria
may be used. It is recommended that Bard Return Air
Grille or Return Filter Grille be installed when no
return duct is used. Contact distributor or factory for
ordering information. If using a return air filter grille,
filters must be of sufficient size to allow a maximum
velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to
installation only in a single story structure.
4.
HIGH ALTITUDE APPLICATIONS
Ratings of gas utilization equipment are based on sea
level operation and need not be changed for operation
at elevations up to 6,000 feet. For operation at
elevations above 6,000 feet and in the absence of
specific recommendations from the local authority
having jurisdiction, equipment ratings shall be reduced
as specified in Section 21.
5.
TRANSPORTATION DAMAGE
All units are packed securely in shipping container.
All units should be carefully inspected upon arrival for
damage. In the event of damage, the consignee should:
1. Note on delivery receipt of any damage to container.
2. Notify carrier promptly, and request an inspection.
3. In case of concealed damage, the carrier must be
notified as soon as possible within 15 days after
delivery.
4. Claims for any damage, apparent or concealed,
should be filed with the carrier, using the following
supporting documents:
A. Original Bill of Lading, certified copy, or
indemnity bond.
B.
Original paid freight bill of indemnity in lieu
thereof.
C.
Original invoice or certified copy thereof
showing trade and other discounts or
deductions.
D. Copy of the inspection report issued by
carrier’s representative at the time damage is
reported to carrier.
6. INSTALLATION
Size of unit for proposed installation should be based
on heat loss/heat gain calculations made according to
methods of Air Conditioning Contractors of America
(ACCA). The air duct should be installed in
accordance with the Standards of the National Fire
Protection Association for the Installation of Air
Conditioning and Ventilating Systems of Other Than
Residence Type, NFPA No. 90A, and Residence Type
Warm Air Heating and Air Conditioning Systems,
NFPA No. 90B. Where local regulations are at a
variance with instructions, installer should adhere to
local codes.
WARNING
In all cases, there must be a metal duct
connection made to the supply air flange, and
a one inch clearance to combustibles must be
maintained to this duct connection.
For free blow applications, a metal sleeve
must be used in the wall opening itself, again
maintaining a one inch clearance to
combustibles.
Failure to use the sheet metal can cause
fire resulting in property damage, injury, or
death.
Summary of Contents for WG241D
Page 13: ...Manual 2100 376 Page 10 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60 MIS 1472 ...
Page 16: ...Manual 2100 376 Page 13 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS MIS 1474 ...
Page 22: ...Manual 2100 376 Page 19 FIGURE 11 LOW VOLTAGE WIRING MIS 1748 ...
Page 23: ...Manual 2100 376 Page 20 FIGURE 11A LOW VOLTAGE WIRING ...
Page 24: ...Manual 2100 376 Page 21 FIGURE 12 GAS PIPE CONNECTION MIS 1683 ...
Page 34: ...Manual 2100 376 Page 31 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL ...
Page 56: ...Manual 2100 376 Page 53 WG241DA 230 208 60 1 ...
Page 57: ...Manual 2100 376 Page 54 WG241DA 230 208 60 1 ...
Page 58: ...Manual 2100 376 Page 55 WG241DB 230 208 60 3 ...
Page 59: ...Manual 2100 376 Page 56 WG241DB 230 208 60 3 ...
Page 60: ...Manual 2100 376 Page 57 WG241DC 460 60 3 ...
Page 61: ...Manual 2100 376 Page 58 WG241DC 460 60 3 ...
Page 62: ...Manual 2100 376 Page 59 WG301DA WG361DA 230 208 60 1 ...
Page 63: ...Manual 2100 376 Page 60 WG301DA WG361DA 230 208 60 1 ...
Page 64: ...Manual 2100 376 Page 61 WG301DB WG361DB 230 208 60 3 ...
Page 65: ...Manual 2100 376 Page 62 WG301DB WG361DB 230 208 60 3 ...
Page 66: ...Manual 2100 376 Page 63 WG301DC WG361DC 460 60 3 ...
Page 67: ...Manual 2100 376 Page 64 WG301DC WG361DC 460 60 3 ...
Page 68: ...Manual 2100 376 Page 65 WG422DA 230 208 60 1 ...
Page 69: ...Manual 2100 376 Page 66 WG422DA 230 208 60 1 ...
Page 70: ...Manual 2100 376 Page 67 WG422DB 230 208 60 3 ...
Page 71: ...Manual 2100 376 Page 68 WG422DB 230 208 60 3 ...
Page 72: ...Manual 2100 376 Page 69 WG422DC 460 60 3 ...
Page 73: ...Manual 2100 376 Page 70 WG422DC 460 60 3 ...
Page 74: ...Manual 2100 376 Page 71 WG481DA WG601DA 230 208 60 1 ...
Page 75: ...Manual 2100 376 Page 72 WG481DA WG601DA 230 208 60 1 ...
Page 76: ...Manual 2100 376 Page 73 WG481DB WG601DB 230 208 60 3 ...
Page 77: ...Manual 2100 376 Page 74 WG481DB WG601DB 230 208 60 3 ...
Page 78: ...Manual 2100 376 Page 75 WG481DC WG601DC 460 60 3 ...
Page 79: ...Manual 2100 376 Page 76 WG481DC WG601DC 460 60 3 ...