Manual 2100-376
Page 8
7.
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air
openings must be cut through the wall as
detailed in Figure 4.
2. On wood-frame walls, the wall construction
must be strong and rigid enough to carry the
weight of the unit without transmitting any unit
vibration.
3. Concrete block walls must be thoroughly
inspected to insure that they are capable of
carrying the weight of the installed unit.
8.
MOUNTING THE UNIT
1. These units are secured by wall mounting
brackets which secure the unit to the outside
wall surface at both sides. A bottom mounting
bracket is provided for ease of installation but
is not required.
2. The WG42, WG48 and WG60 models are
suitable for 0 inch clearance on the installation
mounting wall and to the top. For all models the
supply air duct flange and the first 3 feet of
supply air duct require a minimum of 1 inch
clearance to combustible material. The WG24,
WG30 and WG36 models are suitable for 0 inch
clearance on the installation mounting wall, but
require 1 inch clearance to the top if combustible
material overhang projects above the unit. See
Figure 3 and 3A. If a combustible wall, use a
minimum of Figure 1 “A” dimension plus 2
inches and “B” dimension plus 2 inches. See
Figures 4 and 5 for details.
3. Locate and mark lag bolt locations and bottom
mounting bracket location.
4. Mount bottom mounting bracket.
5. Hook top rain flashing under back bend of top.
Top rain flashing is shipped secured to the right
side of the back.
6. Position unit in opening and secure with 5/16
lag bolts; use 7/8 inch diameter flat washers on
the lag bolts. Use lag bolts long enough to
support the unit’s weight when mounted to the
structure. This length may be dependant on the
type of construction.
7. Secure rain flashing to wall and caulk across
entire length of top. See Figure 3.
8. On side by side installations, maintain a
minimum of 20 inches clearance on right side
to allow access to control panel and burner
compartment, and to allow proper airflow to the
outdoor coil. Additional clearance may be
required to meet local or national codes.
WARNING
Failure to provide the one inch clearance
between the supply duct and a combustible
surface for the first three feet of duct can result
in fire causing damage, injury or death.
CAUTION
If the bottom bracket is used, be certain the
bracket is secured to the outside wall surface
in a way sufficient to support the entire weight
of the unit during installation until side
mounting brackets are secured.
Summary of Contents for WG241D
Page 13: ...Manual 2100 376 Page 10 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60 MIS 1472 ...
Page 16: ...Manual 2100 376 Page 13 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS MIS 1474 ...
Page 22: ...Manual 2100 376 Page 19 FIGURE 11 LOW VOLTAGE WIRING MIS 1748 ...
Page 23: ...Manual 2100 376 Page 20 FIGURE 11A LOW VOLTAGE WIRING ...
Page 24: ...Manual 2100 376 Page 21 FIGURE 12 GAS PIPE CONNECTION MIS 1683 ...
Page 34: ...Manual 2100 376 Page 31 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL ...
Page 56: ...Manual 2100 376 Page 53 WG241DA 230 208 60 1 ...
Page 57: ...Manual 2100 376 Page 54 WG241DA 230 208 60 1 ...
Page 58: ...Manual 2100 376 Page 55 WG241DB 230 208 60 3 ...
Page 59: ...Manual 2100 376 Page 56 WG241DB 230 208 60 3 ...
Page 60: ...Manual 2100 376 Page 57 WG241DC 460 60 3 ...
Page 61: ...Manual 2100 376 Page 58 WG241DC 460 60 3 ...
Page 62: ...Manual 2100 376 Page 59 WG301DA WG361DA 230 208 60 1 ...
Page 63: ...Manual 2100 376 Page 60 WG301DA WG361DA 230 208 60 1 ...
Page 64: ...Manual 2100 376 Page 61 WG301DB WG361DB 230 208 60 3 ...
Page 65: ...Manual 2100 376 Page 62 WG301DB WG361DB 230 208 60 3 ...
Page 66: ...Manual 2100 376 Page 63 WG301DC WG361DC 460 60 3 ...
Page 67: ...Manual 2100 376 Page 64 WG301DC WG361DC 460 60 3 ...
Page 68: ...Manual 2100 376 Page 65 WG422DA 230 208 60 1 ...
Page 69: ...Manual 2100 376 Page 66 WG422DA 230 208 60 1 ...
Page 70: ...Manual 2100 376 Page 67 WG422DB 230 208 60 3 ...
Page 71: ...Manual 2100 376 Page 68 WG422DB 230 208 60 3 ...
Page 72: ...Manual 2100 376 Page 69 WG422DC 460 60 3 ...
Page 73: ...Manual 2100 376 Page 70 WG422DC 460 60 3 ...
Page 74: ...Manual 2100 376 Page 71 WG481DA WG601DA 230 208 60 1 ...
Page 75: ...Manual 2100 376 Page 72 WG481DA WG601DA 230 208 60 1 ...
Page 76: ...Manual 2100 376 Page 73 WG481DB WG601DB 230 208 60 3 ...
Page 77: ...Manual 2100 376 Page 74 WG481DB WG601DB 230 208 60 3 ...
Page 78: ...Manual 2100 376 Page 75 WG481DC WG601DC 460 60 3 ...
Page 79: ...Manual 2100 376 Page 76 WG481DC WG601DC 460 60 3 ...