Manual 2100-376
Page 16
12. VENT RESIZING INSTRUCTIONS
When an existing furnace is removed from a venting
system servicing other appliances, the venting system is
likely to be too large to properly vent the remaining
attached appliances.
The following steps shall be followed with each of the
appliances remaining connected to the common venting
system, placed in operation one at a time while the
other appliances remaining connected to the common
venting system are not in operation.
1. Seal any unused openings in the venting system;
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
code, ANSI Z223.1 or the CAN/CGA B149
Installation Codes and these instructions. Determine
that there is no blockage or restriction, leakage,
corrosion and other deficiencies which could cause
an unsafe condition;
3. In so far as is practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system are
located and other spaces of the building. Turn on
clothes dryers and any appliances not connected to
the venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they will
operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers;
4. Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance shall operate continuously;
5. Test for draft hood equipped appliance spillage at
the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or
candle;
6. After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-
burning appliances to their previous conditions of
use;
7. If improper venting is observed during any of the
above tests, the venting system must be corrected.
13. FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in
the service panel.
If the unit is equipped with a fresh air damper
assembly, the assembly is shipped already attached to
the unit. The damper blade is locked in the closed
position. To allow the damper to operate, the
maximum and minimum blade position stops must be
installed. See Figure 9.
All capacity, efficiency and cost of operation
information as required for Department of Energy
“Energyguide” Fact Sheets is based upon the fresh air
blank-off plate in place and is recommended for
maximum energy efficiency.
The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.
One of several other ventilation options may be
installed. Refer to model number and/or supplemental
installation instructions.
14. CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the
top of the unit down to the unit base. There are
openings in the unit base for the drain hose to pass
through. In the event the drain hose is connected to a
drain system of some type, it must be an open or vented
type system to assure proper drainage.
FIGURE 9
FRESH AIR DAMPER
BLADE IS
LOCKED CLOSED
FOR SHIPPING
MIS-938
Summary of Contents for WG241D
Page 13: ...Manual 2100 376 Page 10 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60 MIS 1472 ...
Page 16: ...Manual 2100 376 Page 13 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS MIS 1474 ...
Page 22: ...Manual 2100 376 Page 19 FIGURE 11 LOW VOLTAGE WIRING MIS 1748 ...
Page 23: ...Manual 2100 376 Page 20 FIGURE 11A LOW VOLTAGE WIRING ...
Page 24: ...Manual 2100 376 Page 21 FIGURE 12 GAS PIPE CONNECTION MIS 1683 ...
Page 34: ...Manual 2100 376 Page 31 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL ...
Page 56: ...Manual 2100 376 Page 53 WG241DA 230 208 60 1 ...
Page 57: ...Manual 2100 376 Page 54 WG241DA 230 208 60 1 ...
Page 58: ...Manual 2100 376 Page 55 WG241DB 230 208 60 3 ...
Page 59: ...Manual 2100 376 Page 56 WG241DB 230 208 60 3 ...
Page 60: ...Manual 2100 376 Page 57 WG241DC 460 60 3 ...
Page 61: ...Manual 2100 376 Page 58 WG241DC 460 60 3 ...
Page 62: ...Manual 2100 376 Page 59 WG301DA WG361DA 230 208 60 1 ...
Page 63: ...Manual 2100 376 Page 60 WG301DA WG361DA 230 208 60 1 ...
Page 64: ...Manual 2100 376 Page 61 WG301DB WG361DB 230 208 60 3 ...
Page 65: ...Manual 2100 376 Page 62 WG301DB WG361DB 230 208 60 3 ...
Page 66: ...Manual 2100 376 Page 63 WG301DC WG361DC 460 60 3 ...
Page 67: ...Manual 2100 376 Page 64 WG301DC WG361DC 460 60 3 ...
Page 68: ...Manual 2100 376 Page 65 WG422DA 230 208 60 1 ...
Page 69: ...Manual 2100 376 Page 66 WG422DA 230 208 60 1 ...
Page 70: ...Manual 2100 376 Page 67 WG422DB 230 208 60 3 ...
Page 71: ...Manual 2100 376 Page 68 WG422DB 230 208 60 3 ...
Page 72: ...Manual 2100 376 Page 69 WG422DC 460 60 3 ...
Page 73: ...Manual 2100 376 Page 70 WG422DC 460 60 3 ...
Page 74: ...Manual 2100 376 Page 71 WG481DA WG601DA 230 208 60 1 ...
Page 75: ...Manual 2100 376 Page 72 WG481DA WG601DA 230 208 60 1 ...
Page 76: ...Manual 2100 376 Page 73 WG481DB WG601DB 230 208 60 3 ...
Page 77: ...Manual 2100 376 Page 74 WG481DB WG601DB 230 208 60 3 ...
Page 78: ...Manual 2100 376 Page 75 WG481DC WG601DC 460 60 3 ...
Page 79: ...Manual 2100 376 Page 76 WG481DC WG601DC 460 60 3 ...