Manual 2100-365
Page 3
1.
IMPORTANT
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians. All duct work or portions thereof not in
the conditioned space should be properly insulated in
order to both conserve energy and prevent
condensation or moisture damage.
2. APPLICATION
This is a fan-assisted forced air gas furnace with
electric air conditioning for outdoor installation. A fan-
assisted furnace is equipped with an integral
mechanical means to draw products of combustion
through the combustion chamber and heat exchanger.
The furnace installation must conform with local
building codes and ordinances or, in their absence,
with the National Fuel Gas Code ANSI Z223.1 or
CAN/CGA-B149.1, latest edition, and the National
Electrical Code ANSI/NFPA-7 or CSA C22.1, latest
edition. It is the personal responsibility and obligation
of the purchaser to contact a qualified installer to
assure that installation is adequate and is in
conformance with governing codes and ordinances.
3.
DUCT WORK
The unit is designed for use with or without duct work.
See Warning on Page 7. Flanges are provided for
attaching the supply and return ducts. These
instructions explain the recommended method to install
the air cooled self-contained electric air conditioning
and gas heating unit and the electrical wiring
connections and gas piping to the unit. The refrigerant
system is completely assembled and charged. All
internal wiring is complete.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
heating/cooling system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
All duct work, supply and return, must be properly
sized for the design air flow requirement of the
equipment. Air Conditioning Contractors of America
(ACCA) is an excellent guide to proper sizing.
Refer to Table 9 for maximum static pressure available
for duct design.
AIR CONDITIONING MODULE OPTIONS
STD =
Standard equipment.
j
CCM Compressor control module has adjustable 30 second to 5 minute delay-on-break
timer. On initial power up, or any time the power is interrupted, the delay-on-make
will be 2 minutes plus 10% of the delay-on-break setting. There is no delay-on-
make during routine operation of the unit. The module also provides the lockout
feature (with 1 retry) for high and/or low pressure controls, and a 2 minute timed
bypass for low pressure control.
k
HPC High pressure control is auto reset. Always used with compressor control module
(CCM) which is included. See note
j
.
l
LPC Low pressure control is auto reset. Always used with compressor control module
(CCM) which is included. See note
j
.
m
LAC Low ambient control permits cooling operation down to 0°F.
1
M
C
C
2
C
P
H
3
C
P
L
4
C
A
L
d
e
ll
a
t
s
n
I
y
r
o
t
c
a
F
e
d
o
C
d
e
ll
a
t
s
n
I
d
l
e
i
F
t
r
a
P
D
T
S
D
T
S
%
G
6
1
-
A
M
C
D
T
S
D
T
S
%
%
H
8
1
-
A
M
C
D
T
S
D
T
S
%
I
6
-
A
M
C
CAUTION
During the initial firing of the burners there will probably be some amount of smoke issued to the
circulating air stream as the result of residual oil burning off of the heat exchanger tubes. This oil
is required during the forming process of the stainless steel heat exchanger tubes to facilitate the
bending. OSHA or the National Toxicology Program does not list the oil as a carcinogen. In vapor
form this may be irretating to the eyes or could cause headaches. This is a one time occurrence,
and ventilation of the space may be required depending upon the space being conditioned.
Summary of Contents for WG241
Page 12: ...Manual 2100 365 Page 9 FIGURE 2 MOUNTING INSTRUCTIONS FOR WG24 WG30 AND WG36 MIS 1681...
Page 13: ...Manual 2100 365 Page 10 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60 MIS 1472...
Page 16: ...Manual 2100 365 Page 13 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS MIS 1474...
Page 22: ...Manual 2100 365 Page 19 FIGURE 11 LOW VOLTAGE WIRING MIS 1719...
Page 23: ...Manual 2100 365 Page 20 FIGURE 12 GAS PIPE CONNECTION MIS 1683...
Page 33: ...Manual 2100 365 Page 30 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL...
Page 50: ...Manual 2100 365 Page 47 WG241 A 230 208 60 1...
Page 51: ...Manual 2100 365 Page 48 WG241 A 230 208 60 1...
Page 52: ...Manual 2100 365 Page 49 WG241 B 230 208 60 3...
Page 53: ...Manual 2100 365 Page 50 WG241 B 230 208 60 3...
Page 54: ...Manual 2100 365 Page 51 WG241 C 460 60 3...
Page 55: ...Manual 2100 365 Page 52 WG241 C 460 60 3...
Page 56: ...Manual 2100 365 Page 53 WG301 A WG361 A 230 208 60 1...
Page 57: ...Manual 2100 365 Page 54 WG301 A WG361 A 230 208 60 1...
Page 58: ...Manual 2100 365 Page 55 WG301 B WG361 B 230 208 60 3...
Page 59: ...Manual 2100 365 Page 56 WG301 B WG361 B 230 208 60 3...
Page 60: ...Manual 2100 365 Page 57 WG301 C WG361 C 460 60 3...
Page 61: ...Manual 2100 365 Page 58 WG301 C WG361 C 460 60 3...
Page 62: ...Manual 2100 365 Page 59 WG422 A 230 208 60 1...
Page 63: ...Manual 2100 365 Page 60 WG422 A 230 208 60 1...
Page 64: ...Manual 2100 365 Page 61 WG422 B 230 208 60 3...
Page 65: ...Manual 2100 365 Page 62 WG422 B 230 208 60 3...
Page 66: ...Manual 2100 365 Page 63 WG422 C 460 60 3...
Page 67: ...Manual 2100 365 Page 64 WG422 C 460 60 3...
Page 68: ...Manual 2100 365 Page 65 WG481 A WG601 A 230 208 60 1...
Page 69: ...Manual 2100 365 Page 66 WG481 A WG601 A 230 208 60 1...
Page 70: ...Manual 2100 365 Page 67 WG481 B WG601 B 230 208 60 3...
Page 71: ...Manual 2100 365 Page 68 WG481 B WG601 B 230 208 60 3...
Page 72: ...Manual 2100 365 Page 69 WG481 C WG601 C 460 60 3...
Page 73: ...Manual 2100 365 Page 70 WG481 C WG601 C 460 60 3...