background image

Manual   2100-218
Page    5

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be checked
for external signs of shipping damage.  If damage is
found, the receiving party must contact the last carrier
immediately, preferably in writing, requesting inspection
by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The refrigerant system is completely assembled and
charged.  All internal wiring is complete.

The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.

These instructions explain the recommended method to
install the air cooled self-contained unit and the electrical
wiring connections to the unit.

These instructions and any instructions packaged with
any separate equipment required to make up the entire air
conditioning system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way.  Authorities having
jurisdiction should be consulted before the installation is
made.  See Page 1 for information on codes and
standards.

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA).  The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association for
the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No. 90A,
and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B.  Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

DUCT WORK

All duct work, supply and return, must be properly sized
for the design air flow requirement of the equipment.  Air
Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing.  All duct work or
portions thereof not in the conditioned space should be
properly insulated in order to both conserve energy and
prevent condensation or moisture damage.

Refer to Table 10 for maximum static pressure available
for duct design.

Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.  Use
insulation with a vapor barrier on the outside of the
insulation.  Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.

A 1/4 inch clearance to combustible material for the first
three feet of duct attached to the outlet air frame is
required.  See Wall Mounting Instructions and Figures 3
and 4 for further details.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.

Some installations may not require any return air duct.  A
metallic return air grille is required with installations not
requiring a return air duct.  The spacing between louvers
on the grille shall not be larger than 5/8 inch.

Any grille that meets with 5/8 inch louver criteria may be
used.  It is recommended that Bard Return Air Grille Kit
RG2 through RG5 or RFG2 through RFG5 be installed
when no return duct is used.  Contact distributor or
factory for ordering information.  If using a return air
filter grille, filters must be of sufficient size to allow a
maximum velocity of 400 fpm.

NOTE:  If no return air duct is used, applicable installation

codes may limit this cabinet to installation only in
a single story structure.

Summary of Contents for WA421

Page 1: ...MOUNTED PACKAGE AIR CONDITIONERS MODELS WA421 WA482 WA602 Manual 2100 218I Supersedes 2100 218H File Volume III Tab 16 Date 04 19 99 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead...

Page 2: ...Table 9 Maximum EXP Electric Heat Only 18 Table 10 Pressure Table 18 Table 11 Optional Accessories 19 Getting Other Information and Publications 1 Wall Mount General Information 2 Heat Pump Wall Moun...

Page 3: ...Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC...

Page 4: ...2 1 3 0 0 4 8 3 3 7 1 0 0 0 7 4 8 1 3 3 4 0 3 4 1 6 5 7 3 0 0 1 6 4 0 2 2 3 8 0 6 2 8 6 1 2 7 0 0 2 1 5 KW MODEL NUMBER CONTROL MODULES See Chart Below VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460...

Page 5: ...F G I J K L M N O P Q R S T A B C B 2 4 A W 8 4 A W 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4 9 6 2 9 6 4 3 3 4 2 3 7 3 3 8 8 2 4 8 8 3 2 0...

Page 6: ...A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N Z 0 C 0 0 C 1 2 4 A W 9 0 C 5 1 C 3 0 6 4 1 1 1 2 1 7 1 6 2 5 1 0 2 0 3 4 1...

Page 7: ...l regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design air flow requirement of the equ...

Page 8: ...rvice This filter can be serviced from the outside by removing the service door A one inch washable filter and two inch pleated filter are also available as optional accessories The internal filter br...

Page 9: ...l If a combustible wall use a minimum of 30 1 2 x 10 1 2 dimensions for sizing However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required...

Page 10: ...Manual 2100 218 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS 416...

Page 11: ...ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causin...

Page 12: ...LL STRUCTURE FACTORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FINISHE...

Page 13: ...Manual 2100 218 Page 11 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS 550...

Page 14: ...See Start Up section for important information on three phase scroll compressor start ups Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 g...

Page 15: ...Manual 2100 218 Page 13 FIGURE 8 UNIT 24V TERMINAL BOARD MIS 1373...

Page 16: ...t it can be reconnected to low speed red wire for lower sound level See wiring diagram 50 HZ models must have fan wired on low speed These models are factory wired on low speed START UP IMPORTANT INST...

Page 17: ...set high pressure switch Turn thermostat off then on to reset the high pressure switch 3 Check all power fuses or circuit breakers to be sure they are the correct rating 4 Periodic cleaning of the out...

Page 18: ...phase line monitor to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct t...

Page 19: ...mum unit performance will occur with a refrigerant charge resulting in a suction line temperature 6 from compressor as shown in Table 6 TABLE 7 INDOOR BLOWER PERFORMANCE CFM 230V P S E H n I 2 0 2 8 4...

Page 20: ...eration on Page 14 TABLE 10 PRESSURE TABLE COOLING Air Temperature Entering Outdoor Coil F l e d o M r i A n r u t e R e r u t a r e p m e T e r u s s e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1...

Page 21: ...X X X X X X X X X X X 5 V R C 5 M F I E B 5 A V R E W B 5 C V R E W t s u a h x E h t i w r o t a l i t n e V l a i c r e m m o C t s u a h x E h t i w r e z i m o n o c E r o t a l i t n e V y r e v...

Reviews: