background image

Manual   2100-192
Page   14

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:

0.5 minute

(30 seconds) DOB = 123 second DOM

1.0 minute

(60 seconds) DOB = 126 second DOM

2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed. Pressure tables can be found later in the
manual covering all models. It is imperative to match
the correct pressure table to the unit by model number.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a 

soft lockout

 and stay in soft lockout

until the high pressure switch closes and the delay on
break time has expired.   If the high pressure switch
opens again in this same operating cycle the unit will go
into 

manual lockout

 condition and the alarm relay circuit

will energize.   Recycling the wall thermostat resets the
manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.   Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever compressor is locked out due to HPC
or LPC sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut
out and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

Summary of Contents for WA301

Page 1: ...CKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Manual No 2100 192M Supersedes 2100 192L File Volume III Tab 16 Date 05 13 02 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just...

Page 2: ...General 5 Duct Work 5 Filters 5 Fresh Air Intake 6 Condensate Drain 6 Installation Instructions Wall Mounting Information 7 Mounting the Unit 7 Top Outlet Only 7 Wiring Main Power 7 Wiring Low Voltag...

Page 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washing...

Page 4: ...e latest revision Article 310 for power conductor sizing CAUTION When more than one field power conductor circuit is run through one conduit the conductors must be derated Pay special attention to not...

Page 5: ...odels only TABLE 2 DIMENSIONS OF BASIC UNIT NOMINAL l e d o M h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 0 3 A W 6 3 A W 0 0 2 8 3 5 2 1 7 1 3...

Page 6: ...M A H U T B S P M A H U T B S P M A H U T B 0 5 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 0 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 0 0 1 6 1 4 0 3 1 4...

Page 7: ...rement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated...

Page 8: ...drainage FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is equipped with the fresh air damper assembly the assembly is shipped already attache...

Page 9: ...nch diameter flat washers on the lag bolts 7 Secure rain flashing to wall and caulk across entire length of top See Figure 3 8 For additional mounting rigidity the return air and supply air frames or...

Page 10: ...lor coded thermostat cable is recommended The connection points are shown in Figure 10 TABLE 5 THERMOSTAT WIRE SIZE r e m r o f s n a r T A V A L F e r i W e g u a G m u m i x a M e c n a t s i D t e...

Page 11: ...it showing 1 4 inch clearance to combustible surfaces FIGURE 4 ELECTRIC HEAT CLEARANCE MIS 277 WARNING WARNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combus...

Page 12: ...Page 10 FIGURE 5 WALL MOUNTING INSTRUCTIONS MIS 549 FIGURE 6 WALL MOUNTING INSTRUCTIONS MIS 548 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR...

Page 13: ...Manual 2100 192 Page 11 MIS 550 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Page 14: ...Manual 2100 192 Page 12 FIGURE 8 LOW VOLTAGE WIRING MIS 1373C...

Page 15: ...elay On a call for heating circuit R W1 make at the thermostat pulling in heat contact for the strip heat and blower operation On a call for second stage heat R W2 makes bringing on second heat contac...

Page 16: ...mmediately The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired If the high pressure switch opens again...

Page 17: ...ng in a suction line temperature 6 inches from compressor as shown in Table 8 The suction line temperatures in Table 8 are based upon 80 F dry bulb 67 F wet bulb 50 percent R H temperature and rated a...

Page 18: ...e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1 0 2 1 5 2 1 1 0 3 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 4 7 8 1 2 7 7 2 3 2 9 7 7 4 2 1 8 2 6 2 2 8 7 7 2 4 8 2 9 2 5 8 6 0 3...

Page 19: ...e t a l P f f O k n a l B X X X X X X 3 D A F B r e p m a D r i A h s e r F c i r t e m o r a B X X X X X X 3 D A F M r e p m a D r i A h s e r F d e z i r o t o M X X X X X X 3 V R C t s u a h x E h...

Reviews: