background image

Manual  2100-192
Page   13

IMPORTANT INSTALLER NOTE

For improved start-up performance, wash the indoor
coil with a dishwasher detergent.

CRANKCASE HEATERS

All units are provided with some form of compressor
crankcase heat.

All single and three phase models have an insertion
well-type heater located in the lower section of the
compressor housing.  This is a self-regulating type
heater that draws only enough power to maintain the
compressor at a safe temperature.

Some form of crankcase heat is essential to prevent
liquid refrigerant from migrating to the compressor,
causing oil pump out on compressor start up and
possible valve failure due to compressing a liquid.

The decal in Figure 9 is affixed to all outdoor units
detailing start up procedure.  This is very important.
Please read carefully.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all

times. Also, not to needlessly close off supply and
return air registers. This reduces air flow through the
system, which shortens equipment service life as well
as increasing operating costs.

2. Check all power fuses or circuit breakers to be sure

they are the correct rating.

3. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

Cooling—Circuit R-Y makes at thermostat pulling in
compressor contactor, starting the compressor and
outdoor motor. The G (indoor motor) circuit is
automatically completed on any call for cooling
operation or can be energized by manual fan switch on
subbase for constant air circulation. On all 230 volt
units there is a one minute off delay on the blower
motor.  460 volt models do not have an off delay. On a
call for heating, circuit R-W1 make at the thermostat
pulling in heat contact for the strip heat and blower
operation. On a call for second stage heat, R-W2 makes
bringing on second heat contactor, if so equipped.

START UP

FIGURE 9

START UP LABEL

COMPRESSOR CONTROL MODULE

The compressor control module is optional on the
models covered by this manual.  The compressor control
is an anti-short cycle/lockout timer with high and low
pressure switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to
the unit  the 

delay on make

 period begins which will be

2 minutes plus 10% of the 

delay on break

 setting.  When

the delay on make is complete and the high pressure
switch (and low pressure switch if employed) is closed,
the compressor contactor is energized.  Upon shutdown
the delay or break timer starts and prevents restart until
the delay on break and delay on make periods have
expired.

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

IMPORTANT

These procedures must be followed
at initial start up and at any time
power has been removed for 12
hours or longer.

To prevent compressor damage which may
result from the presence of liquid refrigerant in
the compressor crankcase:

1.  Make certain the room thermostat is in the
"off" position (the compressor is not to operate).

2.  Apply  power by closing the system
disconnect switch.  This energizes the
compressor heater which evaporates the liquid
refrigerant in the crankcase.

3.  Allow 4 hours or 60 minutes per poind of
refrigerant in the system as noted on the unit
rating plate, whichever is greater.

4.  After properly elapsed time, the thermostat
may be set to operate the compressor.

5.  Except as required for safety while servicing,

do not open system disconnect switch

.

           

 7961-061

Summary of Contents for WA301

Page 1: ...CKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Manual No 2100 192M Supersedes 2100 192L File Volume III Tab 16 Date 05 13 02 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just...

Page 2: ...General 5 Duct Work 5 Filters 5 Fresh Air Intake 6 Condensate Drain 6 Installation Instructions Wall Mounting Information 7 Mounting the Unit 7 Top Outlet Only 7 Wiring Main Power 7 Wiring Low Voltag...

Page 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washing...

Page 4: ...e latest revision Article 310 for power conductor sizing CAUTION When more than one field power conductor circuit is run through one conduit the conductors must be derated Pay special attention to not...

Page 5: ...odels only TABLE 2 DIMENSIONS OF BASIC UNIT NOMINAL l e d o M h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 0 3 A W 6 3 A W 0 0 2 8 3 5 2 1 7 1 3...

Page 6: ...M A H U T B S P M A H U T B S P M A H U T B 0 5 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 0 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 0 0 1 6 1 4 0 3 1 4...

Page 7: ...rement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated...

Page 8: ...drainage FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is equipped with the fresh air damper assembly the assembly is shipped already attache...

Page 9: ...nch diameter flat washers on the lag bolts 7 Secure rain flashing to wall and caulk across entire length of top See Figure 3 8 For additional mounting rigidity the return air and supply air frames or...

Page 10: ...lor coded thermostat cable is recommended The connection points are shown in Figure 10 TABLE 5 THERMOSTAT WIRE SIZE r e m r o f s n a r T A V A L F e r i W e g u a G m u m i x a M e c n a t s i D t e...

Page 11: ...it showing 1 4 inch clearance to combustible surfaces FIGURE 4 ELECTRIC HEAT CLEARANCE MIS 277 WARNING WARNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combus...

Page 12: ...Page 10 FIGURE 5 WALL MOUNTING INSTRUCTIONS MIS 549 FIGURE 6 WALL MOUNTING INSTRUCTIONS MIS 548 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR...

Page 13: ...Manual 2100 192 Page 11 MIS 550 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Page 14: ...Manual 2100 192 Page 12 FIGURE 8 LOW VOLTAGE WIRING MIS 1373C...

Page 15: ...elay On a call for heating circuit R W1 make at the thermostat pulling in heat contact for the strip heat and blower operation On a call for second stage heat R W2 makes bringing on second heat contac...

Page 16: ...mmediately The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired If the high pressure switch opens again...

Page 17: ...ng in a suction line temperature 6 inches from compressor as shown in Table 8 The suction line temperatures in Table 8 are based upon 80 F dry bulb 67 F wet bulb 50 percent R H temperature and rated a...

Page 18: ...e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1 0 2 1 5 2 1 1 0 3 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 4 7 8 1 2 7 7 2 3 2 9 7 7 4 2 1 8 2 6 2 2 8 7 7 2 4 8 2 9 2 5 8 6 0 3...

Page 19: ...e t a l P f f O k n a l B X X X X X X 3 D A F B r e p m a D r i A h s e r F c i r t e m o r a B X X X X X X 3 D A F M r e p m a D r i A h s e r F d e z i r o t o M X X X X X X 3 V R C t s u a h x E h...

Reviews: