Manual 2100-642
Page
17 of 82
FIGURE 1.10
Adjusting the VAC Transformer
It is very important that the transformer is wired for the correct 575V voltage
2. Confirm correct wires are connected: For 575V, the gray (575) and black (common) transformer wires must be used.
Shelter supply breaker in ON position Bard
system breaker in OFF position
575V Three Phase Voltage Range:
546VAC – 632VAC
1. Verify incoming AC voltage: Multimeter set to VAC
+
575VAC
Gray and black wires
must be used