PHASE MONITOR

All units with three phase scroll compressors are 
equipped with a 3-phase line monitor to prevent 
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two 
LEDs.  If the Y signal is present at the phase monitor 
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and 
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply 
leads to the unit.  Do not reverse any of the unit factory 
wires as damage may occur.

MOTOR START DEVICE

Single Phase (-A) model compressor circuits are 
equipped with a 25 ohm PTCR (Positive Temperature 
Coefficient Resistor) motor starting device as standard 
equipment.

The PTCR is wired in parallel with the run capacitor.  
When voltage is applied, and device is cool, its low 
resistance permits a large current to flow in the 
auxiliary windings - increasing the motors available 
starting torque.  The device then rapidly heats up, 
and the current levels drop to a few milliamperes.  
The PTCR then becomes self-regulating, passing just 
enough current to maintain its temperature to remain 
in the high resistance state.  Once the voltage source is 
removed, the device then cools down and the resistance 
drops, and is then ready for the next compressor start 
cycle.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on 
all units so that the system operating pressures can be 
observed.  Pressure tables can be found later in the 
manual covering all models.  It is imperative to match 
the correct pressure table to the unit by model number.

Be careful to observe whether unit is operating in high 
cool or low cool when utilizing the charts.

This unit employs high-flow Coremax valves instead of 
the typical Shrader type valves.

WARNING! Do NOT use a Schrader valve core removal 

tool with these valves. Use of such a tool could result in 

eye injuries or refrigerant burns!

To change a Coremax valve without first removing the 
refrigerant, a special tool is required which can be 
obtained at www.fastestinc.com/en/SCCA07H.  See the 
replacement parts manual for replacement core part 
numbers.

Alarm Relay Output

Alarm terminal is output connection for applications 
where alarm relay is employed.  This terminal is 
powered whenever compressor is locked out due to HPC 
or LPC sequences as described.

NOTE: Both high and low pressure switch controls  

  are inherently automatic reset devices.  The  

  high pressure switch and low pressure  

  switch cut out and cut in settings are fixed by 

  specific air conditioner or heat pump unit  

  model.  The lockout features, both soft and  

  manual, are a function of the Compressor  

  Control Module. 

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break Timer

The potentiometer is used to select Delay on Break time 
from 30 seconds to 5 minutes.  Delay on Make (DOM) 
timing on power-up and after power interruptions is 
equal to 2 minutes plus 10% of Delay on Break (DOB) 
setting:

0.5 minute (30 seconds) DOB = 123  second DOM
1.0 minute (60 seconds) DOB = 126   second DOM 
2.0 minute (120 seconds) DOB = 132  second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144  second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power 
interruptions the compressor will operate on demand 
with no delay.

T

ypical Settings for Dual Unit Installation:

Unit 1: DOB set at 2 minutes, and DOM is 132 
seconds

Unit 2: DOB set at 4 minutes, and DOM is 144 
seconds

Summary of Contents for THE WALL-MOUNT WA3S3-A

Page 1: ...NSTRUCTIONS WA3S3 A WA3S3 B WA3S3 C WA4S3 A WA4S3 B WA4S3 C WA5S3 A WA5S3 B WA5S3 C WL3S2 A WL3S2 B WL3S2 C WL4S2 A WL4S2 B WL4S2 C WL5S2 A WL5S2 B WL5S2 C Bard Manufacturing Company Inc Bryan Ohio 43...

Page 2: ...3 General 13 Topping Off System Charge 13 Safety Practices 13 Important Installer Note 14 Crankcase Heaters 14 High and Low Pressure Switch 14 Three Phase Scroll Compressor Start Up Information 14 Ser...

Page 3: ...d Manual N Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design for Winter Manual Q and Summer Air Conditioning For more information contact these publishers ACCA Air...

Page 4: ...in 480V units only VOLTS PHASE A 230 208 1 B 230 208 60 3 C 460 60 3 KW 0Z No KW w Circuit Breaker or Pull Disconnect 05 5 KW 06 6 KW 08 8 KW 09 9 KW 10 10 KW 15 15 KW 20 20 KW VENTILATION OPTIONS B...

Page 5: ...scale I A C K 2 13 H J 2 63 9 06 P M L O E 44 W 5 75 F G R S S S S S T D Return Air Opening MIS 2488 B Drain Inlet Air Air Outlet Front View Side View Cond 1 Back View Condenser Bracket Installation B...

Page 6: ...1 1 28 29 38 56 40 40 40 60 10 10 8 6 10 10 10 10 WA L4S C0Z C06 C09 C15 460 3 1 1 1 1 15 16 21 30 20 20 25 30 12 12 10 10 12 12 10 10 WA L5S A0Z A05 A08 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 1 or...

Page 7: ...ons thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage Refer to Table 10 for maximum static pressure availab...

Page 8: ...ting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance...

Page 9: ...nded that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of installation B 16 16 16 16 16 1 7 8 6 1 2 6 1 2 2 1 8 7 8 1 3 4 Typ 4 Typ 6 1...

Page 10: ...IR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRU...

Page 11: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 12: ...CE Part Number Predominate Features 8403 060 1120 445 3 stage Cool 3 stage Heat Programmable Non Programmable Electronic HP or Conventional Auto or Manual changeover 8403 058 TH5220D1151 2 stage Cool...

Page 13: ...rigerant composition during multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refriger...

Page 14: ...he Phase Monitor section later in this manual Verification of proper rotation must be made any time a compressor is change or rewired If improper rotation is corrected at this time there will be no ne...

Page 15: ...ng When the delay on make is complete and the high pressure and low pressure switches are closed the compressor contactor is energized Upon shutdown the delay or break timer starts and prevents restar...

Page 16: ...erve whether unit is operating in high cool or low cool when utilizing the charts This unit employs high flow Coremax valves instead of the typical Shrader type valves WARNING Do NOT use a Schrader va...

Page 17: ...another click as the solenoid returns to its original position 3 If clicks can t be heard shut off power and remove the control circuit molded plug from the compressor and measure the solenoid coil re...

Page 18: ...h this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shou...

Page 19: ...465 146 492 148 519 85 DB 72 WB Low Side High Side 137 216 139 237 140 258 141 279 142 300 143 321 146 346 148 370 151 395 153 419 155 447 157 474 158 502 160 529 LOW CAPAPACITY COOLING AIR TEMPERATU...

Page 20: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Page 21: ...g and press it into the socket until it latches A SLIGHT CLICK WILL BE HEARD WHEN PROPERLY INSERTED Finish installing the replacement control per one of the three following paragraphs 8a 8b or 8c 8a I...

Page 22: ...at Will occur automatically with a call for W1 signal from thermostat Will occur automatically with a call for W2 or Emergency Heat signal from thermostat TABLE 9 INDOOR BLOWER PERFORMANCE Model Rated...

Page 23: ...er Package X EHWA5S A15 Heater Package X EHWA5S A20 Heater Package X EHWA3S B06 Heater Package X EHWA5S B06 Heater Package X X EHWA5S B09 Heater Package X X X EHWA5S B15 Heater Package X X X EHWA5S C0...

Page 24: ...r Package X EHWA5S A15L Heater Package X EHWA5S A20L Heater Package X EHWA3S B06L Heater Package X EHWA5S B06L Heater Package X X EHWA5S B09L Heater Package X X X EHWA5S B15L Heater Package X X X EHWA...

Reviews: