background image

Manual 2100-526H
Page 

14 of 24

IMPORTANT INSTALLER NOTE

For improved start-up performance, wash the indoor 
coil with a dishwasher detergent.

CRANKCASE HEATERS

All units covered in this manual are provided with 
compressor crankcase heat.  

This crankcase heater is a band type heater located 
around the bottom of the compressor.  This heater is 
controlled by the crankcase heater relay.  The heater is 
only energized when the compressor is not running.

Crankcase heat is essential to prevent liquid refrigerant 
from migrating to the compressor, preventing oil pump 
out on compressor start-up and possible bearing or 
scroll vane failure due to compressing a liquid.

The decal in Figure 7 is affixed to all model units 
detailing start-up procedure.  This is very important.  

Please read carefully

.

HIGH AND LOW PRESSURE SWITCH

All models covered by this manual are supplied with 
a remote reset high pressure switch and low pressure 
switch.  If tripped, this pressure switch may be reset by 
turning the thermostat off then back on again.

NOTE:

  Defective pressure switches can be replaced 

without reclaiming system charge as they are screwed 

onto the service port rather than brazed onto the 

system.

THREE PHASE SCROLL COMPRESSOR 

START UP INFORMATION

Scroll compressors, like several other types of 
compressors, will only compress in one rotational 
direction.  Direction of rotation is not an issue with 
single phase compressors since they will always start 
and run in the proper direction.

However, three phase compressors will rotate in either 
direction depending upon phasing of the power.  Since 
there is a 50-50 chance of connecting power in such 
a way as to cause rotation in the reverse direction, 
verification of proper rotation must be made. All three 
phase units incorporate a phase monitor to ensure 
proper field wiring.  See the “Phase Monitor” section 
later in this manual.  

Verification of 

proper rotation

 must be made any time a 

compressor is change or rewired.  If improper rotation is 
corrected at this time there will be no negative impact 
on the durability of the compressor. However, reverse 
operation for over one hour may have a negative impact 
on the bearing due to oil pump out.

NOTE: 

If compressor is allowed to run in reverse 

rotation for several minutes, the compressor’s 

internal protector will trip.

All three phase ZPS compressors are wired identically 
internally.  As a result, once the correct phasing 
is determined for a specific system or installation, 
connecting properly phased power leads to the same 
Fusite terminal should maintain proper rotation 
direction.

Verification of proper rotation direction is made by 
observing that suction pressure drops and discharge 
pressure rises when the compressor is energized.  
Reverse rotation also results in an elevated sound level 
over that with correct rotations, as well as, substantially 
reduced current draw compared to tabulated values.

The direction of rotation of the compressor may be 
changed by reversing any two line connections to the 
unit.

See “Phase Monitor”, page 16.

IMPORTANT

These procedures must be followed at 
initial start-up and at any time power has 
been removed for 12 hours or longer.
To prevent compressor damage which 
may result from the presence of liquid 
refrigerant in the compressor crankcase.
1.  Make certain the room thermostat is in 
  the “off” position (the compressor is 
  not to operate).
2.  Apply power by closing the system  
  disconnect switch.  This energizes the 
  compressor heater which evaporates  
  the liquid refrigerant in the crankcase.
3.  Allow 4 hours or 60 minutes per pound  
  of refrigerant in the system as noted  
  on the unit rating plate, whichever is  
 greater.
4.  After properly elapsed time, the 
  thermostat may be set to operate the  
 compressor.
5.  Except as required for safety while  
  servicing  –  

Do not open system  

  disconnect switch

.

 

 

 

 

               7961-061

FIGURE 7

START-UP LABEL

Summary of Contents for THE WALL-MOUNT WA3S3-A

Page 1: ...NSTRUCTIONS WA3S3 A WA3S3 B WA3S3 C WA4S3 A WA4S3 B WA4S3 C WA5S3 A WA5S3 B WA5S3 C WL3S2 A WL3S2 B WL3S2 C WL4S2 A WL4S2 B WL4S2 C WL5S2 A WL5S2 B WL5S2 C Bard Manufacturing Company Inc Bryan Ohio 43...

Page 2: ...3 General 13 Topping Off System Charge 13 Safety Practices 13 Important Installer Note 14 Crankcase Heaters 14 High and Low Pressure Switch 14 Three Phase Scroll Compressor Start Up Information 14 Ser...

Page 3: ...d Manual N Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design for Winter Manual Q and Summer Air Conditioning For more information contact these publishers ACCA Air...

Page 4: ...in 480V units only VOLTS PHASE A 230 208 1 B 230 208 60 3 C 460 60 3 KW 0Z No KW w Circuit Breaker or Pull Disconnect 05 5 KW 06 6 KW 08 8 KW 09 9 KW 10 10 KW 15 15 KW 20 20 KW VENTILATION OPTIONS B...

Page 5: ...scale I A C K 2 13 H J 2 63 9 06 P M L O E 44 W 5 75 F G R S S S S S T D Return Air Opening MIS 2488 B Drain Inlet Air Air Outlet Front View Side View Cond 1 Back View Condenser Bracket Installation B...

Page 6: ...1 1 28 29 38 56 40 40 40 60 10 10 8 6 10 10 10 10 WA L4S C0Z C06 C09 C15 460 3 1 1 1 1 15 16 21 30 20 20 25 30 12 12 10 10 12 12 10 10 WA L5S A0Z A05 A08 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 1 or...

Page 7: ...ons thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage Refer to Table 10 for maximum static pressure availab...

Page 8: ...ting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance...

Page 9: ...nded that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of installation B 16 16 16 16 16 1 7 8 6 1 2 6 1 2 2 1 8 7 8 1 3 4 Typ 4 Typ 6 1...

Page 10: ...IR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRU...

Page 11: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 12: ...CE Part Number Predominate Features 8403 060 1120 445 3 stage Cool 3 stage Heat Programmable Non Programmable Electronic HP or Conventional Auto or Manual changeover 8403 058 TH5220D1151 2 stage Cool...

Page 13: ...rigerant composition during multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refriger...

Page 14: ...he Phase Monitor section later in this manual Verification of proper rotation must be made any time a compressor is change or rewired If improper rotation is corrected at this time there will be no ne...

Page 15: ...ng When the delay on make is complete and the high pressure and low pressure switches are closed the compressor contactor is energized Upon shutdown the delay or break timer starts and prevents restar...

Page 16: ...erve whether unit is operating in high cool or low cool when utilizing the charts This unit employs high flow Coremax valves instead of the typical Shrader type valves WARNING Do NOT use a Schrader va...

Page 17: ...another click as the solenoid returns to its original position 3 If clicks can t be heard shut off power and remove the control circuit molded plug from the compressor and measure the solenoid coil re...

Page 18: ...h this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shou...

Page 19: ...465 146 492 148 519 85 DB 72 WB Low Side High Side 137 216 139 237 140 258 141 279 142 300 143 321 146 346 148 370 151 395 153 419 155 447 157 474 158 502 160 529 LOW CAPAPACITY COOLING AIR TEMPERATU...

Page 20: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Page 21: ...g and press it into the socket until it latches A SLIGHT CLICK WILL BE HEARD WHEN PROPERLY INSERTED Finish installing the replacement control per one of the three following paragraphs 8a 8b or 8c 8a I...

Page 22: ...at Will occur automatically with a call for W1 signal from thermostat Will occur automatically with a call for W2 or Emergency Heat signal from thermostat TABLE 9 INDOOR BLOWER PERFORMANCE Model Rated...

Page 23: ...er Package X EHWA5S A15 Heater Package X EHWA5S A20 Heater Package X EHWA3S B06 Heater Package X EHWA5S B06 Heater Package X X EHWA5S B09 Heater Package X X X EHWA5S B15 Heater Package X X X EHWA5S C0...

Page 24: ...r Package X EHWA5S A15L Heater Package X EHWA5S A20L Heater Package X EHWA3S B06L Heater Package X EHWA5S B06L Heater Package X X EHWA5S B09L Heater Package X X X EHWA5S B15L Heater Package X X X EHWA...

Reviews: