background image

Manual 2100-526H
Page 

15 of 24

SERVICE HINTS

1.  Maintain clean air filters at all times. Also, do 

not  close off or block supply and return air 
registers. This reduces air flow through the system, 
which shortens equipment service life as well as 
increasing operating costs.

2.   Check all power fuses or circuit breakers to be sure 

they are the correct rating.

3.   Periodic cleaning of the outdoor coil to permit full 

and unrestricted airflow circulation is essential.

 

Frequency of coil cleaning will depend on duty 
cycle of equipment, type of use and installation 
site variables.  Telecommunication type 
installations in high traffic areas or in areas none 
too frequent to airborne debris, will require more 
frequent coil maintenance than those in areas not 
subject to those conditions.

SEQUENCE OF OPERATION

NON-ECONOMIZER
Stage 1 (Y1) cooling call activates Step 1 (partial 
capacity, 66%) of compressor capacity.
Stage 2 (Y2) cooling call activates Step 2 (full capacity, 
100%) of compressor capacity.

WITH ECONOMIZER
Stage 1 (Y1) cooling call goes to economizer controls 
for decision:
 -  If Enthalpy Control decides outdoor conditions 

are suitable for free cooling, the economizer will 
operate.

 

• If Stage 2 cooling call is issued during 

economizer operation, the economizer will 
close and the compressor will go straight to 
Step 2 full capacity operation.

 

- If Enthalpy Control decides outdoor conditions 

are not suitable for free cooling, the economizer 
will not operate (or close) and Step 1 of the 
compressor will operate.

 

• If Stage 2 cooling call is issued, the 

compressor will shift to Step 2 full cooling 
capacity operation.

COMPRESSOR CONTROL MODULE

The compressor control module is standard on the 
models covered by this manual.  The compressor 
control is an anti-short cycle/lockout timer with high 
and low pressure switch monitoring and alarm relay 
output.

A

djustable Delay On Make And Break Timer

On initial power up or anytime power is interrupted to 
the unit, the 

delay on make

 period begins, which will 

be 2 minutes plus 10% of the 

delay on break

 setting.  

When the delay on make is complete and the high 
pressure and low pressure switches are closed, the 
compressor contactor is energized.  Upon shutdown the 
delay or break timer starts and prevents restart until the 
delay on break and delay on make periods have expired.
During routine operation of the unit with no power 
interruptions, the compressor will operate on demand 
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor 
contactor will de-energize immediately.  The lockout 
timer will go into a 

soft lockout

 and stay in soft lockout 

until the high pressure switch closes and the delay on 
break time has expired.  If the high pressure switch 
opens again in this same operating cycle, the unit will 
go into 

manual lockout

 condition and the alarm relay 

circuit will energize.  Recycling the wall thermostat 
resets the manual lockout.

Low Pressure Switch, Bypass and Lockout Sequence

If the low pressure switch opens for more than 120 
seconds, the compressor contactor will de-energize 
and go into a soft lockout.  Regardless the state of the 
low pressure switch, the contactor will reenergize after 
the delay on make time delay has expired.  If the low 
pressure switch remains open, or opens again for longer 
than 120 seconds the unit will go into manual lockout 
condition and the alarm relay circuit will energize.  
Recycling the wall thermostat resets the manual 
lockout.

Optional Low Ambient Control

An optional low ambient control is available for both 
factory and field installed options.  The low ambient 
control is to be applied to the WA3S/WA4S/WA5S 
models when operation below 50°outdoor conditions 
are anticipated.  Without this device, the evaporating 
pressure would fall off, and the indoor coil would ice 
over.
The fan cycling control cycles the fan motor on, once 
the liquid refrigerant pressure reaches 350 psig, and 
off, once it has dropped to 225 psig.  It will continue to 
cycle between these parameters depending on outdoor 
temperatures and the load/stage of the system.
This cycling maintains a minimum liquid pressure 
affecting the minimum suction pressure.  This effect 
insures an evaporating temperature that is slightly 
above the point of ice formation on the evaporator.

Summary of Contents for THE WALL-MOUNT WA3S3-A

Page 1: ...NSTRUCTIONS WA3S3 A WA3S3 B WA3S3 C WA4S3 A WA4S3 B WA4S3 C WA5S3 A WA5S3 B WA5S3 C WL3S2 A WL3S2 B WL3S2 C WL4S2 A WL4S2 B WL4S2 C WL5S2 A WL5S2 B WL5S2 C Bard Manufacturing Company Inc Bryan Ohio 43...

Page 2: ...3 General 13 Topping Off System Charge 13 Safety Practices 13 Important Installer Note 14 Crankcase Heaters 14 High and Low Pressure Switch 14 Three Phase Scroll Compressor Start Up Information 14 Ser...

Page 3: ...d Manual N Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design for Winter Manual Q and Summer Air Conditioning For more information contact these publishers ACCA Air...

Page 4: ...in 480V units only VOLTS PHASE A 230 208 1 B 230 208 60 3 C 460 60 3 KW 0Z No KW w Circuit Breaker or Pull Disconnect 05 5 KW 06 6 KW 08 8 KW 09 9 KW 10 10 KW 15 15 KW 20 20 KW VENTILATION OPTIONS B...

Page 5: ...scale I A C K 2 13 H J 2 63 9 06 P M L O E 44 W 5 75 F G R S S S S S T D Return Air Opening MIS 2488 B Drain Inlet Air Air Outlet Front View Side View Cond 1 Back View Condenser Bracket Installation B...

Page 6: ...1 1 28 29 38 56 40 40 40 60 10 10 8 6 10 10 10 10 WA L4S C0Z C06 C09 C15 460 3 1 1 1 1 15 16 21 30 20 20 25 30 12 12 10 10 12 12 10 10 WA L5S A0Z A05 A08 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 1 or...

Page 7: ...ons thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage Refer to Table 10 for maximum static pressure availab...

Page 8: ...ting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance...

Page 9: ...nded that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of installation B 16 16 16 16 16 1 7 8 6 1 2 6 1 2 2 1 8 7 8 1 3 4 Typ 4 Typ 6 1...

Page 10: ...IR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRU...

Page 11: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 12: ...CE Part Number Predominate Features 8403 060 1120 445 3 stage Cool 3 stage Heat Programmable Non Programmable Electronic HP or Conventional Auto or Manual changeover 8403 058 TH5220D1151 2 stage Cool...

Page 13: ...rigerant composition during multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refriger...

Page 14: ...he Phase Monitor section later in this manual Verification of proper rotation must be made any time a compressor is change or rewired If improper rotation is corrected at this time there will be no ne...

Page 15: ...ng When the delay on make is complete and the high pressure and low pressure switches are closed the compressor contactor is energized Upon shutdown the delay or break timer starts and prevents restar...

Page 16: ...erve whether unit is operating in high cool or low cool when utilizing the charts This unit employs high flow Coremax valves instead of the typical Shrader type valves WARNING Do NOT use a Schrader va...

Page 17: ...another click as the solenoid returns to its original position 3 If clicks can t be heard shut off power and remove the control circuit molded plug from the compressor and measure the solenoid coil re...

Page 18: ...h this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shou...

Page 19: ...465 146 492 148 519 85 DB 72 WB Low Side High Side 137 216 139 237 140 258 141 279 142 300 143 321 146 346 148 370 151 395 153 419 155 447 157 474 158 502 160 529 LOW CAPAPACITY COOLING AIR TEMPERATU...

Page 20: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Page 21: ...g and press it into the socket until it latches A SLIGHT CLICK WILL BE HEARD WHEN PROPERLY INSERTED Finish installing the replacement control per one of the three following paragraphs 8a 8b or 8c 8a I...

Page 22: ...at Will occur automatically with a call for W1 signal from thermostat Will occur automatically with a call for W2 or Emergency Heat signal from thermostat TABLE 9 INDOOR BLOWER PERFORMANCE Model Rated...

Page 23: ...er Package X EHWA5S A15 Heater Package X EHWA5S A20 Heater Package X EHWA3S B06 Heater Package X EHWA5S B06 Heater Package X X EHWA5S B09 Heater Package X X X EHWA5S B15 Heater Package X X X EHWA5S C0...

Page 24: ...r Package X EHWA5S A15L Heater Package X EHWA5S A20L Heater Package X EHWA3S B06L Heater Package X EHWA5S B06L Heater Package X X EHWA5S B09L Heater Package X X X EHWA5S B15L Heater Package X X X EHWA...

Reviews: