Manual 2100-737A
Page
22 of 25
TABLE 3A
Cooling Pressures
Low side pressure ± 4 PSIG
High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge
should be removed, system evacuated and recharged to serial plate charge weight.
NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check condenser fan wiring. See
“Condenser Fan Operation”.
Air Temperature Entering Outdoor Coil °F
TABLE 4
Electrical Specifications
TABLE 3B
Heating Pressures (All Temperatures °F)
Model
Return Air
Temperature
Pressure
75
80
85
90
95
100
105
110
115
120
125
T60H
75º DB
62º WB
Low Side
High Side
124
331
126
353
128
377
130
401
132
427
134
453
135
481
137
509
139
539
140
570
142
602
80º DB
67º WB
Low Side
High Side
133
340
135
363
137
387
139
412
141
438
143
465
145
493
147
523
148
553
150
585
152
617
85º DB
72º WB
Low Side
High Side
137
352
139
375
142
400
144
426
146
453
148
481
150
510
152
541
154
572
156
605
157
639
Model
Return Air
Temperature
Pressure
0
5
10
15
20
25
30
35
40
45
50
55
60
65
T60H
70º
Low Side
High Side
36
281
41
287
47
294
53
301
60
309
66
317
73
326
81
335
88
345
96
355
104
366
113
377
122
389
131
401
Models
Rated Volts,
HZ and
Phase
No. of
Field
Power
Circuits
Single Circuit
Multiple Circuit
Min.
Circuit
Ampacity
Max.
External
Fuse or
Circuit
Breaker
Field
Power
Wire
Size
Ground
WIre
Size
Minimum
Circuit
Ampacity
Maximum
Circuit Exterior
Fuse or Circuit
Breaker
Field Power
Wire Size
Ground
WIre Size
Ckt.
A
Ckt.
B
Ckt.
C
Ckt.
A
Ckt.
B
Ckt.
C
Ckt.
A
Ckt.
B
Ckt.
C
Ckt.
A
Ckt.
B
Ckt.
C
T60H2-A00, A0Z
-A05
-A10
-A15
-A20
230/208-60-1
1
1 or 2
1 or 2
1 or 2
1 or 3
43
69
95
95
113
60
80
100
100
125
8
4
3
3
2
10
8
8
8
6
43
43
43
43
26
52
52
52
52
50
50
50
50
30
60
60
60
60
8
8
8
8
10
6
6
6
6
10
10
10
10
10
10
10
10
10
T60H2-B00, B0Z
-B09
-B15
-B18
230/208-60-3
1
1
1
2
34
59
59
N/A
40
60
60
N/A
8
6
6
N/A
10
10
10
N/A
59
28
60
30
6
10
10
10
T60H2-C0Z
-C06
-C15
-C18
460-60-3
1
1
1
1
18
32
32
34
25
35
35
35
12
10
10
8
12
10
10
10
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical Code (latest version),
Article 310 for power conductor sizing.
Caution:
When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310
regarding Ampacity Adjustment Factors when more than three (3) conductors are in a raceway.
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
Maximum KW that can operate with the heat pump on is 10KW. Full heat available during Emergency Heat Mode.
Maximum KW that can operate with the heat pump on is 9KW. Full heat available during Emergency Heat Mode.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance
with the National Electrical Code and all local codes.