background image

Manual 2100-737A 

Page 

16 of 25

IMPORTANT INSTALLER NOTE

For improved start up performance wash the indoor coil 
with a dish washing detergent.

HIGH AND LOW PRESSURE SWITCH

All T**S wall mounted air conditioner series models 
are supplied with a remote reset for the high and low 
pressure switch.  If tripped, this pressure switch may 
be reset by turning the thermostat off then back on 
again.

THREE PHASE SCROLL COMPRESSOR 

START UP INFORMATION

Scroll compressors, like several other types of 
compressors, will only compress in one rotational 
direction.  Direction of rotation is not an issue with 
single phase compressors since they will always start 
and run in the proper direction.

However, three phase compressors will rotate in either 
direction depending upon phasing of the power.  
Since there is a 50-50 chance of connecting power 
in such a way as to cause rotation in the reverse 
direction, verification of proper rotation must be made.  
Verification of proper rotation direction is made by 
observing that suction pressure drops and discharge 
pressure rises when the compressor is energized.  
Reverse rotation also results in an elevated sound level 
over that with correct rotation, as well as substantially 
reduced current draw compared to tabulated values.

Verification of 

proper rotation

 must be made at the 

time the equipment is put into service.  If improper 
rotation is corrected at this time, there will be no 
negative impact on the durability of the compressor. 
However, reverse operation for over 1 hour may have a 
negative impact on the bearing due to oil pump out.

NOTE:

  If compressor is allowed to run in reverse 

rotation for an extended period of time, the 

compressor’s internal protector will trip.

All three phase ZP compressors are wired identically 
internally.  As a result, once the correct phasing 
is determined for a specific system or installation, 
connecting properly phased power leads to the same 
Fusite terminal should maintain proper rotation 
direction.

The direction of rotation of the compressor may be 
changed by reversing any two line connections to the 
unit.

PHASE MONITOR

All units with three phase scroll compressors are 
equipped with a three phase line monitor to prevent 
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two 
LEDs.  If the Y signal is present at the phase monitor 
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and 
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply 
leads to the unit.  

Do not reverse any of the unit factory 

wires as damage may occur.

SERVICE HINTS

1.  Caution owner/operator to maintain clean air filters 

at all times and to not needlessly close off supply 
and return air registers.  This reduces airflow 
through the system, which shortens equipment 
service life as well as increasing operating costs.

2.  Check all power fuses or circuit breakers to be sure 

they are the correct rating.

3.  Periodic cleaning of the outdoor coil to permit full 

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

Cooling

Circuit R-Y makes at thermostat pulling in compressor 
contactor, starting the compressor and outdoor motor.  
The G (indoor motor) circuit is automatically completed 
on any call for cooling operation or can be energized 
by manual fan switch on subbase for constant air 
circulation.

Heating

A 24V solenoid coil on reversing valve controls heating 
cycle operation.  Two thermostat options, one allowing 
“Auto” changeover from cycle to cycle and the other 
constantly energizing solenoid coil during heating 
season and thus eliminating pressure equalization 
noise except during defrost, are to be used.  On “Auto” 
option a circuit is completed from R-B and  R-Y on 
each heating “on” cycle, energizing reversing valve 
solenoid and pulling in compressor contactor starting 
compressor and outdoor motor.  R-G also make starting 
indoor blower motor.  Heat pump heating cycle now in 
operation.  The second option has no “Auto” changeover 
position, but instead energizes the reversing valve 
solenoid constantly whenever the system switch on 
subbase is placed in “Heat” position, the “B” terminal 
being constantly energized from R.  A thermostat 
demand for Stage 1 heat completes R-Y circuit, pulling 
in compressor contactor starting compressor and outdoor 
motor.  R-G also make starting indoor blower motor.

Summary of Contents for T60H2-A

Page 1: ...unted Packaged Heat Pump Models INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 737A Supersedes 2100 737 Date 5 14 21 T60H2 A T60H2 B T60H2 C Page 1 of 25 ...

Page 2: ...ations 3 Wall Mount General Information 4 Heat Pump Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Fresh Air Intake 5 Condensate Drain 5 Installation Instructions 6 Wall Mounting Information 6 Mounting the Unit 6 Placement 6 Clearances Required 6 Minimum Clearances 6 Wiring Main Power 12 Wiring Low Voltage Wiring 12 Optional Outdoor Thermostat Applications 13 Opt...

Page 3: ...Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Telephone ...

Page 4: ...d installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Condi...

Page 5: ...r factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable installation codes may limit this cabinet to installation only in a single story structure FILTERS A 1 throwaway filter is standard with each unit The filter slides into position making it easy to service This...

Page 6: ...lashing to wall and caulk across entire length of top See Figure 3 8 For additional mounting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance if combustible wall PLACEMENT 1 On side by side installations maintain a minimum of 20 clearance on right side t...

Page 7: ...2 13 A Cond Air Inlet Electrical Entrances Optional Side Wall Mounting Brackets Built In Location Shipping Return Air Opening Supply Air Opening Top Rain Flashing Bottom Installation Bracket Back View M L O E R S S S S S T 44 N Q P B FIGURE 2 Unit Dimensions All dimensions are in inches Dimensional drawings are not to scale Model Width Depth Height Supply Return A B C B E F G I J K L M N O P Q R S...

Page 8: ...9 3 4 32 12 5 1 2 2 29 OPENING 1 Return Opening IT IS RECOMMENDED THAT A BEAD OF SUPPLY AIR NOTES TOP FLASHING AT TIME OF INSTALLATION RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND THE SIDE MOUNTING FLANGES AND UNDER MIS 416 F TOP WALL FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED WALL STRUCTURE FROM COMBUSTABLE 1 4 CLEARANCE ON ALL MATERIALS HEATER ACCESS PANEL FOAM AIR SEAL Right Side View Wall O...

Page 9: ...rials This is required for the first 3ʹ of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 CLEARANCE TO COMBUSTIBLE SURFACES ...

Page 10: ...AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRUCTURAL STEEL ATTACH TO TOP 1 000 CLEARANCE 1 000 CLEARANCE PLATE OF WALL C SEE UNIT DIMENSIONS FIGURE 2 OPENING RETURN DUCT 2 x 6 ATTACH TO BOTTOM OVER FRAME...

Page 11: ... WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE WALL INSTALLATION DUCTED SUPPLY GRILLE OUTSIDE SPACE FALSE WALL RETURN AIR GRILLE OUTSIDE OR BELOW CEILING RAFTERS AS SHOWN FINISHED CEILING SURFACE RAIN FLASHING RAIN FLASHING RETURN AT UNIT NO DUC...

Page 12: ...at is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab located in the bottom le...

Page 13: ...the correct set points NOTE The additional LAB low ambient bypass relay is required to prevent heater operation during low temperature cooling operation OPTIONAL COMPRESSOR CUTOFF THERMOSTAT See Figures 8 9 Heat pump compressor operation at outdoor temperatures below 0 F are neither desirable nor advantageous in term of efficiency An outdoor thermostat can be applied to take the mechanical heating...

Page 14: ...tat This is done to maximize efficiency by utilizing the heat pump to bring the conditioned space temperature up rather than cycling on the electric heat due a second stage call for heat from the thermostat on start up coming off a night set back condition or someone increasing the thermostat set point NOTE Some programmable thermostats do have a built in time delay for pulling in second stage hea...

Page 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrigerant it must come out of ...

Page 16: ...MONITOR All units with three phase scroll compressors are equipped with a three phase line monitor to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light If phases are reversed the red fault LED will be lit and compressor operation is inhibited If a f...

Page 17: ...temperature sensor will send a signal to the heat pump control which will return the system to heating operations automatically If some abnormal or temporary condition such as a high wind causes the heat pump to have a prolonged defrost cycle the heat pump control will restore the system to heating operation automatically after 8 minutes The heat pump defrost control board has an option of 30 60 o...

Page 18: ... as there is likely no actual frost on the outdoor coil in this artificial test condition There is also a 5 minute compressor time delay function built into the HPC This is to protect the compressor from short cycling conditions The board s LED will have a fast blink rate when in the compressor time delay In some instances it is helpful to the service technician to override or speed up this timing...

Page 19: ... Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not go into defrost heating only Temperature sensor or heat pump control defective Disconnect temperature sensor from board and jumper across SPEEDUP terminals and SEN JMP t...

Page 20: ...9 16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0 13820 102 0 5570 11 0 122089 27 0 37652 65 0 13474 103 0 5446 10 0 118108 28 0 36583 66 0 13137 104 0 5326 9 0 114272 29 0 35548 67 0 12810 105 0 5208 8 0 110575 30 0 34545 68 0 12492 106 0 50...

Page 21: ...by testing with this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance They shall not be used to adjust charge If charge is in doubt reclaim evacuate and recharge t...

Page 22: ...ize Minimum Circuit Ampacity Maximum Circuit Exterior Fuse or Circuit Breaker Field Power Wire Size Ground WIre Size Ckt A Ckt B Ckt C Ckt A Ckt B Ckt C Ckt A Ckt B Ckt C Ckt A Ckt B Ckt C T60H2 A00 A0Z A05 A10 A15 A20 230 208 60 1 1 1 or 2 1 or 2 1 or 2 1 or 3 43 69 95 95 113 60 80 100 100 125 8 4 3 3 2 10 8 8 8 6 43 43 43 43 26 52 52 52 52 50 50 50 50 30 60 60 60 60 8 8 8 8 10 6 6 6 6 10 10 10 1...

Page 23: ...ble filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant Blower only CFM reduces during continuous fan mode Requires wiring modification consult Wiring Diagram and unplug and leave disconnected the insulated male female connector connecting together the Gray Orange wires located near the 24V terminal block enclosure CFM output on Cooling or E...

Page 24: ...f it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop filter Check correct duct restrictions Symptom Cause Procedure Noisy blower or cabinet Check for loose blower housing panels etc High static creating high blower speed ...

Page 25: ...site side of the connector plug and gently pulling the plug out of the connector socket in the control DO NOT PULL ON THE WIRES GRIP THE PLUG ONLY 6 The control module is now completely detached from the motor Verify with a standard ohmmeter that the resistance from each motor lead in the motor plug just removed to the motor shell is 100K ohms Refer to Figure 25 Measure to unpainted motor end plat...

Reviews: