CHECKING TEMPERATURE SENSOR 

OUTSIDE UNIT CIRCUIT

1.  Disconnect temperature sensor from board and 

from outdoor coil.

2.  Use an ohmmeter and measure the resistance of 

the sensor.  Also use ohmmeter to check for short 
or open.

3.  Check resistance reading to chart of resistance.  

Use sensor ambient temperature.  (Tolerance of 
part is ± 10%.)

4.  If sensor resistance reads very low, then sensor is 

shorted and will not allow proper operation of the 
heat pump control.

5.  If sensor is out of tolerance, shorted, open or reads 

very low ohms then it should be replaced.

Temperature (F) vs. Resistance (R) of Temperature Sensor

F

R

F

R

F

R

F

R

-25.0

196871

13.0

56985

53.0

19374

89.0

7507

-24.0

190099

14.0

55284

52.0

18867

90.0

7334

-23.0

183585

15.0

53640

53.0

18375

91.0

7165

-22.0

177318

16.0

52051

54.0

17989

92.0

7000

-21.0

171289

17.0

50514

55.0

17434

93.0

6840

-20.0

165487

18.0

49028

56.0

16984

94.0

6683

-19.0

159904

19.0

47590

57.0

16547

95.0

6531

-18.0

154529

20.0

46200

58.0

16122

96.0

6383

-17.0

149355

21.0

44855

59.0

15710

97.0

6239

-16.0

144374

22.0

43554

60.0

15310

98.0

6098

-15.0

139576

23.0

42295

61.0

14921

99.0

5961

-14.0

134956

24.0

41077

62.0

14544

100.0

5827

-13.0

130506

25.0

39898

63.0

14177

101.0

5697

-12.0

126219

26.0

38757

64.0

13820

102.0

5570

-11.0

122089

27.0

37652

65.0

13474

103.0

5446

-10.0

118108

28.0

36583

66.0

13137

104.0

5326

-9.0

114272

29.0

35548

67.0

12810

105.0

5208

-8.0

110575

30.0

34545

68.0

12492

106.0

5094

-7.0

107010

31.0

33574

69.0

12183

107.0

4982

-6.0

103574

32.0

32634

70.0

11883

108.0

4873

-5.0

100260

33.0

31723

71.0

11591

109.0

4767

-4.0

97064

34.0

30840

72.0

11307

110.0

4663

-3.0

93981

35.0

29986

73.0

11031

111.0

4562

-2.0

91008

36.0

29157

74.0

10762

112.0

4464

-1.0

88139

37.0

28355

75.0

10501

113.0

4367

0.0

85371

38.0

27577

76.0

10247

114.0

4274

1.0

82699

39.0

26823

77.0

10000

115.0

4182

2.0

80121

40.0

26092

78.0

9760

116.0

4093

3.0

77632

41.0

25383

79.0

9526

117.0

4006

4.0

75230

42.0

24696

80.0

9299

118.0

3921

5.0

72910

43.0

24030

81.0

9077

119.0

3838

6.0

70670

44.0

23384

82.0

8862

120.0

3757

7.0

68507

45.0

22758

83.0

8653

121.0

3678

8.0

66418

46.0

22150

84.0

8449

122.0

3601

9.0

64399

47.0

21561

85.0

8250

123.0

3526

10.0

62449

48.0

20989

86.0

8057

124.0

3452

11.0

60565

49.0

20435

87.0

7869

12.0

58745

50.0

19896

88.0

7686

Summary of Contents for T30S1-A

Page 1: ...B T36S1 C T42S1 A T42S1 B T42S1 C T48S1 A T48S1 B T48S1 C T60S1 A T60S1 B T60S1 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 547H Supersedes 2100 547G Date 8 16 17 T...

Page 2: ...ons T S Dehum 23 Table 7 Indoor Blower Performance 24 Table 8 Dehumidification Relay Logic Board 27 Getting Other Information and Publications 3 Wall Mount General Information 4 Wall Mount Model Nomen...

Page 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Page 4: ...ould be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National...

Page 5: ...through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum...

Page 6: ...ng upon wall construction Be sure to observe required clearance if combustible wall PLACEMENT 1 On side by side installations maintain a minimum of 20 clearance on right side to allow access to contro...

Page 7: ...ting location Remove the side grille to gain access to the compressor shipping brackets The brackets are located on the compressor double isolation base at the front and rear of the compressor The bra...

Page 8: ...ARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULK...

Page 9: ...Y AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF...

Page 10: ...rials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Page 11: ...ACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACT...

Page 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 13: ...of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing e...

Page 14: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Page 15: ...reverse operation for over 1 hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal...

Page 16: ...a special tool is required which can be obtained at www fastestinc com en SCCA07H See the replacement parts manual for replacement core part numbers DEFROST CYCLE The defrost cycle is controlled by t...

Page 17: ...ooling mode with outdoor fan off Pressure will rise fairly fast as there is likely no actual frost on the outdoor coil in this artificial test condition There is also a 5 minute compressor time delay...

Page 18: ...Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replac...

Page 19: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 3875...

Page 20: ...this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shoul...

Page 21: ...0 deg DB 67 deg WB Low SIde High Side 139 326 141 348 142 371 143 394 144 419 146 443 148 469 149 494 151 521 154 548 85 deg DB 72 deg WB Low SIde High Side 144 337 146 360 147 384 148 408 149 434 151...

Page 22: ...3 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1 C0Z C06 C09 C15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10 T60S1 A00 A0Z A05 A10 A15 A20 230 208 60 1 1 1 or 2 1 or 2...

Page 23: ...0 10 10 10 10 10 T48S1DB00 B0Z DB06 DB09 DB15 230 208 60 3 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1DC0Z DC06 DC09 DC15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10...

Page 24: ...own is with 2 thick disposable filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant Blower only CFM reduces during continuous fan mode Requires...

Page 25: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Chec...

Page 26: ...ite side of the connector plug and gently pulling the plug out of the connector socket in the control DO NOT PULL ON THE WIRES GRIP THE PLUG ONLY 6 The control module is now completely detached from t...

Page 27: ...ied X X X X X X X X Y Y1 B G 2nd Heating Unoccupied X X X X X X X Y Y1 B G O1 2nd Heating Occupied X X X X X X X X X Y Y1 B G O1 W3 2nd Heat Dehum Occupied X X X X X X X X X X X Y Y1 B G W3 2nd Heat D...

Reviews: