Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor 
blower motor, take the following steps:
1.  The correct replacement module must be used.  The controls 

are factory programmed for specific operating modes.  
Even though they look alike, different modules may have 
completely different functionality.  

Using the wrong control 

module voids all product warranties and may produce 

unexpected results.

2.  Begin by removing AC power from the furnace or air handler 

being serviced.  

Do not work on the motor with AC power 

applied.

  

To avoid electric shock from the motor’s capacitors, 

disconnect power and wait at least 5 minutes before opening 
motor.

3.  It is usually not necessary to remove the motor from the 

blower assembly.  However, it is recommended that the 
whole blower assembly, with the motor, be removed from the 
furnace/air handler.  (Follow the manufacturer’s procedures).  
Unplug the two cable connectors to the motor.  There are 
latches on each connector.  

Do not pull on the wires. 

 

The 

plugs remove easily when properly released.

4.  Locate the two standard ¼" hex head bolts at the rear of the 

control housing (at the back end of the control opposite the 
shaft end).  

Refer to Figure 10.  

Remove these two bolts from 

the motor and control assembly while holding the motor in a 
way that will prevent the motor or control from falling when 
the bolts are removed.  If an ECM2.0 control is being replaced 
(recognized by an aluminum casting rather that a deep-drawn 
black steel can housing the electronics), remove only the hex-
head bolts.  

Do not remove the torx-head screws.

5.  The control module is now free of mechanical attachment 

to the motor endshield but is still connected by a plug and 
three wires inside the control.  Carefully rotate the control to 
gain access to the plug at the control end of the wires.  With 
thumb and forefinger, reach the latch holding the plug to 
the control and release it by squeezing the latch tab and the 
opposite side of the connector plug and gently pulling the 
plug out of the connector socket in the control.  

Do not pull 

on the wires.  Grip the plug only.

6.  The control module is now completely detached from the 

motor.  Verify with a standard ohmmeter that the resistance 
from each motor lead (in the motor plug just removed) to the 
motor shell is >100K ohms.  

Refer to Figure 11.  

(Measure 

to unpainted motor end plate.)  If any motor lead fails this 
test, do not proceed to install the control module.  

The 

motor is defective and must be replaced.

  Installing the new 

control module will cause it to fail also.

7.  Verify that the replacement control is correct for your 

application.  Refer to the manufacturer's authorized 
replacement list.  

Using the wrong control will result in 

improper or no blower operation.

  Orient the control module 

so that the 3-wire motor plug can be inserted into the socket 
in the control.  Carefully insert the plug and press it into 
the socket until it latches.  

A slight click will be heard when 

properly inserted.

  

8.  Finish installing the replacement control per one of the three 

following paragraphs, 8a, 8b or 8c.

 8a.

 

If replacing an ECM 2.0 control

 (control in cast 

aluminum can with air vents on the back of the can) 

with an ECM 2.3 control

 (control containing black 

potting for water protection in black deep-drawn steel 
case with no vents in the bottom of the can), locate 
the two through-bolts and plastic tab that are packed 
with the replacement control.  Insert the plastic tab 
into the slot at the perimeter of the open end of the 
can so that the pin is located on the inside of the 
perimeter of the can.  Rotate the can so that the tab 
inserts into the tab locator hole in the endshield of the 

Manual

2100-522B

Page

36 of 38

TROUBLESHOOTING  GE  ECM

 MOTORS CONT’D.

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove

Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              

Use the shorter 

bolts and 

alignment pin 

supplied when 

replacing an 

ECM 2.0 

control.

Figure 3

ECM 

2.3/2.5

Power Connector

(5-pin)

Control Connector

(16-pin)

Hex-head Screws

Motor Connector

(3-pin)

Motor Connector

(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats

Over Ramp

From Motor

Circuit

Board

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower

motor you need to take the following steps:

1. You MUST have the correct replacement module.  The controls are

factory programmed for specific operating modes.  Even though they look

alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT

WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the furnace or air handler being

serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER

APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect

power and wait at least 5 minutes before opening motor.

3. It is usually not necessary to remove the motor from the blower

assembly.  However, it is recommended that the whole blower assembly,

with the motor, be removed from the furnace/air handler.  (Follow the

manufacturer’s procedures).  Unplug the two cable connectors to the motor.

There are latches on each connector.  

DO NOT PULL ON THE WIRES.

The plugs remove easily when properly released.

4. Locate  the  two  standard  ¼"  hex  head  bolts  at  the  rear  of  the  control

housing  (at  the  back  end  of  the  control  opposite  the  shaft  end).   

Refer  to

Figure  24.   

Remove  these  two  bolts  from  the  motor  and  control  assembly

while  holding  the  motor  in  a  way  that  will  prevent  the  motor  or  control

from  falling  when  the  bolts  are  removed.    If  an  ECM2.0  control  is  being

replaced  (recognized  by  an  aluminum  casting  rather  that  a  deep-drawn

black  steel  can  housing  the  electronics),  remove  only  the  hex-head  bolts.

DO  NOT  REMOVE  THE  TORX-HEAD  SCREWS.

5. The  control  module  is  now  free  of  mechanical  attachment  to  the

motor  endshield  but  is  still  connected  by  a  plug  and  three  wires  inside

the  control.    Carefully  rotate  the  control  to  gain  access  to  the  plug  at

the  control  end  of  the  wires.    With  thumb  and  forefinger,  reach  the

latch  holding  the  plug  to  the  control  and  release  it  by  squeezing  the

latch  tab  and  the  opposite  side  of  the  connector  plug  and  gently  pulling

the  plug  out  of  the  connector  socket  in  the  control.   

DO  NOT  PULL

ON  THE  WIRES.    GRIP  THE  PLUG  ONLY.

6. The  control  module  is  now  completely  detached  from  the  motor.

Verify  with  a  standard  ohmmeter  that  the  resistance  from  each  motor

lead  (in  the  motor  plug  just  removed)  to  the  motor  shell  is  >100K  ohms.

Refer to Figure 25.  

(Measure to unpainted motor end plate.)  If any

motor  lead  fails  this  test,  do  not  proceed  to  install  the  control  module.

THE  MOTOR  IS  DEFECTIVE  AND  MUST  BE  REPLACED.

Installing  the  new  control  module  will  cause  it  to  fail  also.

7. Verify  that  the  replacement  control  is  correct  for  your

application.    Refer  to  the  manufacturer's  authorized  replacement  list.

USING  THE  WRONG  CONTROL  WILL  RESULT  IN

IMPROPER  OR  NO  BLOWER  OPERATION.

    Orient  the  control

module  so  that  the  3-wire  motor  plug  can  be  inserted  into  the  socket  in

the  control.    Carefully  insert  the  plug  and  press  it  into  the  socket  until

it  latches.   

A  SLIGHT  CLICK  WILL  BE  HEARD  WHEN

PROPERLY  INSERTED.

    Finish  installing  the  replacement  control  per

one  of  the  three  following  paragraphs,  8a,  8b  or  8c.

8a. 

IF  REPLACING  AN  ECM  2.0  CONTROL

  (control  in  cast

aluminum  can  with  air  vents  on  the  back  of  the  can) 

WITH  AN  ECM

2.3  CONTROL

  (control  containing  black  potting  for  water  protection  in

black  deep-drawn  steel  case  with  no  vents  in  the  bottom  of  the  can),

locate  the  two  through-bolts  and  plastic  tab  that  are  packed  with  the

replacement  control.    Insert  the  plastic  tab  into  the  slot  at  the  perimeter

of the open end of the can so that the pin is located on the inside of the

perimeter of the can.  Rotate the can so that the tab inserts into the tab

locater  hole  in  the  endshield  of  the  motor.    Using  the  two  through-bolts

provided  with  the  replacement  control,  reattach  the  can  to  the  motor.

THE  TWO  THROUGH-BOLTS  PROVIDED  WITH  THE

REPLACEMENT  ECM  2.3  CONTROL  ARE  SHORTER  THAN

THE  BOLTS  ORIGINALLY  REMOVED  FROM  THE  ECM  2.0

CONTROL  AND  MUST  BE  USED  IF  SECURE  ATTACHMENT

OF  THE  CONTROL  TO  THE  MOTOR  IS  TO  BE  ACHIEVED.

DO  NOT  OVERTIGHTEN  THE  BOLTS.

8b. 

IF  REPLACING  AN  ECM  2.3  CONTROL

 

WITH  AN  ECM  2.3

CONTROL

,  the  plastic  tab  and  shorter  through-bolts  are  not  needed.    The

control  can  be  oriented  in  two  positions  180°  apart.   

MAKE  SURE  THE

ORIENTATION  YOU  SELECT  FOR  REPLACING  THE

CONTROL  ASSURES  THE  CONTROL'S  CABLE  CONNECTORS

WILL  BE  LOCATED  DOWNWARD  IN  THE  APPLICATION  SO

THAT  WATER  CANNOT  RUN  DOWN  THE  CABLES  AND  INTO

THE  CONTROL.

    Simply  orient  the  new  control  to  the  motor's  endshield,

insert bolts, and tighten.  

DO  NOT  OVERTIGHTEN  THE  BOLTS.

8c. 

IF  REPLACING  AN  ECM  2.0  CONTROL  WITH  AN  ECM  2.0

CONTROL 

(It  is  recommended  that  ECM  2.3  controls  be  used  for  all

replacements), 

the  new  control  must  be  attached  to  the  motor  using

through  bolts  identical  to  those  removed  with  the  original  control.   

DO

NOT  OVERTIGHTEN  THE  BOLTS.

9. Reinstall  the  blower/motor  assembly  into  the  HVAC  equipment.

Follow  the  manufacturer's  suggested  procedures.

10.  Plug  the  16-pin  control  plug  into  the  motor.    The  plug  is  keyed.

Make  sure  the  connector  is  properly  seated  and  latched.

11.  Plug  the  5-pin  power  connector  into  the  motor.    Even  though  the

plug  is  keyed, 

OBSERVE  THE  PROPER  ORIENTATION.    DO  NOT

FORCE  THE  CONNECTOR.

    It  plugs  in  very  easily  when  properly

oriented.   

REVERSING  THIS  PLUG  WILL  CAUSE  IMMEDIATE

FAILURE  OF  THE  CONTROL  MODULE.

12.  Final  installation  check.    Make  sure  the  motor  is  installed  as  follows:

a. Unit  is  as  far  INTO  the  blower  housing  as  possible.

b. Belly  bands  are  not  on  the  control  module  or  covering  vent  holes.

c. Motor  connectors  should  be  oriented  between  the  4  o’clock  and  8

o’clock  positions  when  the  blower  is  positioned  in  its  final

location  and  orientation.

d. Add  a  drip  loop  to  the  cables  so  that  water  cannot  enter  the  motor

by  draining  down  the  cables.   

Refer  to  Figure  26.

The  installation  is  now  complete.    Reapply  the  AC  power  to  the  HVAC

equipment  and  verify  that  the  new  motor  control  module  is  working

properly.    Follow  the  manufacturer's  procedures  for  disposition  of  the  old

control  module.

Figure 25

Figure 24

Figure 26

Figure 11

Figure 10

Figure 12

motor.  Using the two through-bolts provided with the 
replacement control, reattach the can to the motor.

  

The two through-bolts provided with the replacement 

ECM 2.3 control are shorter than the bolts originally 

removed from the ECM 2.0 control and must be used if 

secure attachment of the control to the motor is to be 

achieved.

  

Do not overtighten the bolts.

 

 8b. 

If replacing an ECM 2.3 control with an ECM 2.3 

control,

 the plastic tab and shorter through-bolts 

are not needed.  The control can be oriented in two 
positions 180° apart.  

Make sure the orientation you 

select for replacing the control assures the control's 

cable connectors will be located downward in the 

application so that water cannot run down the cables 

and into the control.

  Simply orient the new control to 

the motor's endshield, insert bolts, and tighten.  

Do not 

overtighten the bolts.

 

8c. 

If replacing an ECM 2.0 control with an ECM 2.0 

control

 

(It is recommended that ECM 2.3 controls be 

used for all replacements), 

the new control must be 

attached to the motor using through bolts identical 
to those removed with the original control.  

Do not 

overtighten the bolts.

9.  Reinstall the blower/motor assembly into the HVAC 

equipment.  Follow the manufacturer's suggested 
procedures.

10.  Plug the 16-pin control plug into the motor.  The plug is 

keyed.  Make sure the connector is properly seated and 
latched.

11. Plug the 5-pin power connector into the motor.  Even though 

the plug is keyed, 

observe the proper orientation.  do not 

force the connector.

  It plugs in very easily when properly 

oriented.  

Reversing this plug will cause immediate failure of 

the control module.

12. Final installation check.  Make sure the motor is installed as 

follows:

 

a.  Unit is as far INTO the blower housing as possible.

 

b.  Belly bands are not on the control module or covering 

vent holes.

 

c.  Motor connectors should be oriented between the 4 

o’clock and 8 o’clock positions when the blower is 
positioned in its final location and orientation.

 

d.  Add a drip loop to the cables so that water cannot enter 

the motor by draining down the cables.  

Refer to Figure 

12.

The installation is now complete.  Reapply the AC power to the 
HVAC equipment and verify that the new motor control module 
is working properly.  Follow the manufacturer's procedures for 
disposition of the old control module.

Summary of Contents for T30S1-A

Page 1: ...B T36S1 C T42S1 A T42S1 B T42S1 C T48S1 A T48S1 B T48S1 C T60S1 A T60S1 B T60S1 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 547H Supersedes 2100 547G Date 8 16 17 T...

Page 2: ...ons T S Dehum 23 Table 7 Indoor Blower Performance 24 Table 8 Dehumidification Relay Logic Board 27 Getting Other Information and Publications 3 Wall Mount General Information 4 Wall Mount Model Nomen...

Page 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Page 4: ...ould be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National...

Page 5: ...through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum...

Page 6: ...ng upon wall construction Be sure to observe required clearance if combustible wall PLACEMENT 1 On side by side installations maintain a minimum of 20 clearance on right side to allow access to contro...

Page 7: ...ting location Remove the side grille to gain access to the compressor shipping brackets The brackets are located on the compressor double isolation base at the front and rear of the compressor The bra...

Page 8: ...ARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULK...

Page 9: ...Y AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF...

Page 10: ...rials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Page 11: ...ACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACT...

Page 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 13: ...of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing e...

Page 14: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Page 15: ...reverse operation for over 1 hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal...

Page 16: ...a special tool is required which can be obtained at www fastestinc com en SCCA07H See the replacement parts manual for replacement core part numbers DEFROST CYCLE The defrost cycle is controlled by t...

Page 17: ...ooling mode with outdoor fan off Pressure will rise fairly fast as there is likely no actual frost on the outdoor coil in this artificial test condition There is also a 5 minute compressor time delay...

Page 18: ...Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replac...

Page 19: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 3875...

Page 20: ...this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shoul...

Page 21: ...0 deg DB 67 deg WB Low SIde High Side 139 326 141 348 142 371 143 394 144 419 146 443 148 469 149 494 151 521 154 548 85 deg DB 72 deg WB Low SIde High Side 144 337 146 360 147 384 148 408 149 434 151...

Page 22: ...3 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1 C0Z C06 C09 C15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10 T60S1 A00 A0Z A05 A10 A15 A20 230 208 60 1 1 1 or 2 1 or 2...

Page 23: ...0 10 10 10 10 10 T48S1DB00 B0Z DB06 DB09 DB15 230 208 60 3 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1DC0Z DC06 DC09 DC15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10...

Page 24: ...own is with 2 thick disposable filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant Blower only CFM reduces during continuous fan mode Requires...

Page 25: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Chec...

Page 26: ...ite side of the connector plug and gently pulling the plug out of the connector socket in the control DO NOT PULL ON THE WIRES GRIP THE PLUG ONLY 6 The control module is now completely detached from t...

Page 27: ...ied X X X X X X X X Y Y1 B G 2nd Heating Unoccupied X X X X X X X Y Y1 B G O1 2nd Heating Occupied X X X X X X X X X Y Y1 B G O1 W3 2nd Heat Dehum Occupied X X X X X X X X X X X Y Y1 B G W3 2nd Heat D...

Reviews: