Manual 2100-547H
Page
4 of 27
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
T
36
S 1 –
A
05
X
X
X
X
X
X
NOTE:
Vent options X, B and M are without exhaust capability. May require separate field-supplied barometric relief in building.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact
the last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method
to install the air cooled self-contained unit and the
electrical wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation
is made. See page 3 for information on codes and
standards.
Size of unit for a proposed installation should be based
on heat loss/gain calculation made according to methods
of Air Conditioning Contractors of America (ACCA). The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
KW
0Z
–
0KW
04
–
4KW
05
–
5KW
06
–
6KW
F8
–
8KW
S8
–
8KW
09
–
9KW
10
–
10KW
15
–
15KW
20
–
20KW
For 0 KW and circuit breakers (230/208 volt) or toggle disconnect (460V) applications, insert 0Z in the KW field of the model number.
Insert “D” for dehumidification with hot gas reheat. Reference latest revision of Form 7960-640 for complete details.
MODEL
NUMBER
CONTROL MODULES
(See Spec. Sheet S3447)
VOLTS & PHASE
A
–
230/208/60/1
B
–
230/208/60/3
C
–
460/60/3
REVISIONS
VENTILATION OPTIONS
X
–
Barometric Fresh Air Damper (Standard)
B
–
Blank-Off Plate
M
–
Motorized Fresh Air Damper –
No Exhaust
C
–
Commercial Ventilator
–
Mod. Spring Return w/Exhaust
V
–
Commercial Ventilator
–
Spring Return w/Exhaust
P
–
Commercial Ventilator
–
Power Return w/Exhaust
S
–
Economizer
–
Standard –
Enthalpy
W
–
Economizer
–
Equipment Bldg., Enthalpy
T
–
Economizer
–
Equipment Bldg., DB Temp
R
–
Energy Recovery Ventilator
–
Motorized with Exhaust
COLOR OPTIONS
X
–
Beige
1
–
White
4
–
Buckeye Gray
5
–
Desert Brown
8
–
Dark Bronze
A
–
Aluminum
S
–
Stainless Steel
COIL OPTIONS
X
–
Standard
1
–
Phenolic Coated Evaporator
2
–
Phenolic Coated Condenser
3
–
Phenolic Coated Evaporator
and Condenser
SUPPLY AIR OUTLET
X
–
Front (Standard)
S
–
Step Capacity
CAPACITY
30 – 2½ Ton
36 – 3 Ton
42 – 3½ Ton
48 – 4 Ton
60 – 5 Ton
FILTER OPTIONS
X
–
1" Fiberglass (MERV 2)
M
–
2" Pleated (MERV 11)
P
–
2" Pleated (MERV 8)
SPECIALTY PRODUCTS
(Non-Standard)
WARNING
Falling or tipping the unit could cause injury or death!
Use two (2) people or a machine to move the unit.