background image

Manual 2100-547H 

Page 

4 of 27

WALL MOUNT GENERAL INFORMATION

HEAT PUMP WALL MOUNT MODEL NOMENCLATURE

 

T  

36  

 S   1  – 

05 

X

NOTE:

  Vent options X, B and M are without exhaust capability.  May require separate field-supplied barometric relief in building.

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be 
checked for external signs of shipping damage.  If 
damage is found, the receiving party must contact 
the last carrier immediately, preferably in writing, 
requesting inspection by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed 
by trained, experienced service and installation 
technicians.

The refrigerant system is completely assembled and 
charged.  All internal wiring is complete.

The unit is designed for use with or without duct work.  
Flanges are provided for attaching the supply and return 
ducts.

These instructions explain the recommended method 
to install the air cooled self-contained unit and the 
electrical wiring connections to the unit.

These instructions and any instructions packaged with 
any separate equipment required to make up the entire 
air conditioning system should be carefully read before 
beginning the installation.  Note particularly “Starting 
Procedure” and any tags and/or labels attached to the 
equipment.

While these instructions are intended as a general 
recommended guide, they do not supersede any national 
and/or local codes in any way.  Authorities having 
jurisdiction should be consulted before the installation 
is made.  See page 3 for information on codes and 
standards.

Size of unit for a proposed installation should be based 
on heat loss/gain calculation made according to methods 
of Air Conditioning Contractors of America (ACCA).  The 
air duct should be installed in accordance with the 
Standards of the National Fire Protection Association 
for the Installation of Air Conditioning and Ventilating 
Systems of Other Than Residence Type, NFPA No. 
90A, and Residence Type Warm Air Heating and Air 

KW

 

  

0Z

 

 

0KW

04

 

 

4KW

05

 

 

5KW 

06

 

 

6KW

F8

 

 

8KW

S8

 

 

8KW 

09

 

 

9KW 

10

 

 

10KW

15

 

 

15KW

20

 

 

20KW

  For 0 KW and circuit breakers (230/208 volt) or toggle disconnect (460V) applications, insert 0Z in the KW field of the model number. 

  Insert “D” for dehumidification with hot gas reheat.  Reference latest revision of Form 7960-640 for complete details.

MODEL 

NUMBER

CONTROL MODULES

(See Spec. Sheet S3447)

VOLTS & PHASE

A

 

 

230/208/60/1

B

 

 

230/208/60/3

C

 

 

460/60/3

REVISIONS

VENTILATION OPTIONS

X

 

 

Barometric Fresh Air Damper (Standard)

B

 

 

Blank-Off Plate

M

 

 

Motorized Fresh Air Damper –

 

No Exhaust

C

 

 

Commercial Ventilator

 

 

Mod. Spring Return w/Exhaust

V

 

 

Commercial Ventilator

 

 

Spring Return w/Exhaust

P

 

 

Commercial Ventilator

 

 

Power Return w/Exhaust

S

 

 

Economizer

 

 

Standard –

 

Enthalpy

W

 

 

Economizer

 

 

Equipment Bldg., Enthalpy

T

 

 

Economizer

 

 

Equipment Bldg., DB Temp

R

 

 

Energy Recovery Ventilator

 

 

Motorized with Exhaust

COLOR OPTIONS

X

 

 

Beige

1

 

 

White

4

 

 

Buckeye Gray

5

 

 

Desert Brown

8

 

 

Dark Bronze

A

 

 

Aluminum

S

 

 

Stainless Steel

COIL OPTIONS

X

 

 

Standard

1

 

 

Phenolic Coated Evaporator

2

 

 

Phenolic Coated Condenser

3

 

 

Phenolic Coated Evaporator  

 

and Condenser

SUPPLY AIR OUTLET

X

 

 

Front (Standard)

 

Step Capacity

CAPACITY  

30 – 2½ Ton 
36 – 3 Ton 
42 – 3½ Ton 
48 – 4 Ton
60 – 5 Ton

FILTER OPTIONS 

X

 

 

1" Fiberglass (MERV 2)

M

 

 

2" Pleated (MERV 11)

P

 

 

2" Pleated (MERV 8)

SPECIALTY PRODUCTS 

(Non-Standard)

         WARNING

Falling or tipping the unit could cause injury or death!  

Use two (2) people or a machine to move the unit.

Summary of Contents for T30S1-A

Page 1: ...B T36S1 C T42S1 A T42S1 B T42S1 C T48S1 A T48S1 B T48S1 C T60S1 A T60S1 B T60S1 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 547H Supersedes 2100 547G Date 8 16 17 T...

Page 2: ...ons T S Dehum 23 Table 7 Indoor Blower Performance 24 Table 8 Dehumidification Relay Logic Board 27 Getting Other Information and Publications 3 Wall Mount General Information 4 Wall Mount Model Nomen...

Page 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Page 4: ...ould be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National...

Page 5: ...through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum...

Page 6: ...ng upon wall construction Be sure to observe required clearance if combustible wall PLACEMENT 1 On side by side installations maintain a minimum of 20 clearance on right side to allow access to contro...

Page 7: ...ting location Remove the side grille to gain access to the compressor shipping brackets The brackets are located on the compressor double isolation base at the front and rear of the compressor The bra...

Page 8: ...ARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULK...

Page 9: ...Y AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF...

Page 10: ...rials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Page 11: ...ACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACT...

Page 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 13: ...of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing e...

Page 14: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Page 15: ...reverse operation for over 1 hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal...

Page 16: ...a special tool is required which can be obtained at www fastestinc com en SCCA07H See the replacement parts manual for replacement core part numbers DEFROST CYCLE The defrost cycle is controlled by t...

Page 17: ...ooling mode with outdoor fan off Pressure will rise fairly fast as there is likely no actual frost on the outdoor coil in this artificial test condition There is also a 5 minute compressor time delay...

Page 18: ...Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replac...

Page 19: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 3875...

Page 20: ...this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shoul...

Page 21: ...0 deg DB 67 deg WB Low SIde High Side 139 326 141 348 142 371 143 394 144 419 146 443 148 469 149 494 151 521 154 548 85 deg DB 72 deg WB Low SIde High Side 144 337 146 360 147 384 148 408 149 434 151...

Page 22: ...3 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1 C0Z C06 C09 C15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10 T60S1 A00 A0Z A05 A10 A15 A20 230 208 60 1 1 1 or 2 1 or 2...

Page 23: ...0 10 10 10 10 10 T48S1DB00 B0Z DB06 DB09 DB15 230 208 60 3 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1DC0Z DC06 DC09 DC15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10...

Page 24: ...own is with 2 thick disposable filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant Blower only CFM reduces during continuous fan mode Requires...

Page 25: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Chec...

Page 26: ...ite side of the connector plug and gently pulling the plug out of the connector socket in the control DO NOT PULL ON THE WIRES GRIP THE PLUG ONLY 6 The control module is now completely detached from t...

Page 27: ...ied X X X X X X X X Y Y1 B G 2nd Heating Unoccupied X X X X X X X Y Y1 B G O1 2nd Heating Occupied X X X X X X X X X Y Y1 B G O1 W3 2nd Heat Dehum Occupied X X X X X X X X X X X Y Y1 B G W3 2nd Heat D...

Reviews: