Manual 2100-541D
Page
25 of 28
Electrical Specifications — T**H Series Dehumidification
TABLE 6B
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical Code (latest version), Article 310 for power conductor sizing.
Caution:
When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment
Factors when more than three (3) conductors are in a raceway.
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
Maximum KW that can operate with the heat pump on is 4KW. Full heat available during Emergency Heat Mode.
Maximum KW that can operate with the heat pump on is 10KW. Full heat available during Emergency Heat Mode.
Maximum KW that can operate with the heat pump on is 9KW. Full heat available during Emergency Heat Mode.
Maximum KW that can operate with the heat pump on is 8KW. Full heat available during Emergency Heat Mode.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance w/the Nat'l. Electrical Code & all local codes.
MODEL
Rated Volts,
HZ & Phase
No.
Field
Power
Circuits
Single Circuit
Multiple Circuit
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Ckt. Brkr.
Field
Power
Wire
Size
Ground
Wire
Minimum
Circuit
Ampacity
Maximum
External Fuse or
Ckt. Breaker
Field Power Wire
Size
Ground
Wire Size
Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C
T24H1DA00, DA0Z
DA04
DAS8
DAF8
230/208-60-1
1
1
1
1 or 2
24
45
48
65
35
50
50
70
8
8
8
6
10
10
10
8
24
42
35
45
8
8
10
10
T24H1DB00, DB0Z
DB06
DB09
230/208-60-3
1
1
1
16
34
42
20
35
45
12
8
8
12
10
10
T24H1DC0Z
DC06
DC09
460-60-3
1
1
1
9
18
23
15
20
25
14
12
10
14
12
10
T30H1DA00, DA0Z
DA04
DAS8
DAF8
230/208-60-1
1
1
1
1 or 2
24
45
48
66
35
50
50
70
8
8
8
4
10
10
10
8
24
42
35
45
8
8
10
10
T30H1DB00, DB0Z
DB06
DB09
230/208-60-3
1
1
1
18
36
45
25
40
45
10
8
8
10
10
10
T30H1DC0Z
DC06
DC09
460-60-3
1
1
1
10
19
24
15
20
25
14
12
10
14
12
10
T36H1DA00, DA0Z
DA05
DA08
DA10
DA15
230/208-60-1
1
1
1 or 2
1 or 2
1 or 2
29
55
70
81
85
40
60
70
90
90
8
6
4
4
4
10
10
8
8
8
29
29
33
42
52
52
40
40
40
45
60
60
8
8
8
8
6
6
10
10
10
10
10
10
T36H1DB00, DB0Z
DB06
DB09
DB15
230/208-60-3
1
1
1
1
21
39
48
52
30
45
50
60
10
8
6
6
10
10
10
10
T36H1DC0Z
DC06
DC09
DC15
460-60-3
1
1
1
1
12
21
26
27
15
25
30
30
14
10
10
10
14
10
10
10
T42H1DA00, DA0Z
DA05
DA08
DA10
DA15
230/208-60-1
1
1
1 or 2
1 or 2
1 or 2
31
57
73
83
86
40
60
80
90
90
8
6
4
4
3
10
10
8
8
8
31
31
34
42
52
52
40
40
40
45
60
60
8
8
8
8
6
6
10
10
10
10
10
10
T42H1DB00, DB0Z
DB06
DB09
DB15
230/208-60-3
1
1
1
1
26
44
53
53
35
50
60
60
8
8
6
6
10
10
10
10
T42H1DC0Z
DC06
DC09
DC15
460-60-3
1
1
1
1
13
22
26
27
15
25
30
30
12
10
10
10
12
10
10
10
T48H1DA00, DA0Z
DA05
DA08
DA10
DA15
230/208-60-1
1
1 or 2
1 or 2
1 or 2
1 or 2
37
63
79
89
89
50
70
90
100
100
8
6
4
3
3
10
8
8
8
8
37
37
37
37
26
42
52
52
50
50
50
50
30
50
60
60
8
8
8
8
10
8
6
6
10
10
10
10
10
10
10
10
T48H1DB00, DB0Z
DB06
DB09
DB15
230/208-60-3
1
1
1
1
27
45
54
55
40
50
60
60
8
8
6
6
10
10
10
10
T48H1DC0Z
DC06
DC09
DC15
460-60-3
1
1
1
1
15
24
28
29
20
25
30
30
12
10
10
10
12
10
10
10
T60H1DA00, DA0Z
DA05
DA10
DA15
DA20
230/208-60-1
1
1 or 2
1 or 2
1 or 2
1 or 3
44
70
96
96
113
60
80
100
100
125
8
4
3
3
2
10
8
8
8
6
44
44
44
44
26
52
52
52
26
50
50
50
50
30
60
60
60
30
8
8
8
8
10
6
6
6
10
10
10
10
10
10
10
10
10
10
T60H1DB00, DB0Z
DB06
DB09
DB15
DB18
230/208-60-3
1
1
1
1
2
31
49
58
58
N/A
45
60
60
60
N/A
8
8
6
6
N/A
10
10
10
10
N/A
58
28
60
30
6
10
10
10
T60H1DC0Z
DC06
DC09
DC15
DC18
460-60-3
1
1
1
1
1
16
25
29
29
34
20
30
30
30
35
12
10
10
10
8
12
10
10
10
10