Manual 2100-541D
Page 24 of 28
TABLE 6A
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical Code (latest version), Article 310 for power conductor sizing.
Caution:
When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment
Factors when more than three (3) conductors are in a raceway.
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
Maximum KW that can operate with the heat pump on is 4KW. Full heat available during Emergency Heat Mode.
Maximum KW that can operate with the heat pump on is 10KW. Full heat available during Emergency Heat Mode.
Maximum KW that can operate with the heat pump on is 9KW. Full heat available during Emergency Heat Mode.
Maximum KW that can operate with the heat pump on is 8KW. Full heat available during Emergency Heat Mode.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance w/the Nat'l. Electrical Code & all local codes.
Electrical Specifications — T**H Series
MODEL
Rated Volts,
HZ & Phase
No.
Field
Power
Circuits
Single Circuit
Multiple Circuit
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Ckt. Brkr.
Field
Power
Wire
Size
Ground
Wire
Minimum
Circuit
Ampacity
Maximum
External Fuse or
Ckt. Breaker
Field Power Wire
Size
Ground
Wire Size
Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C
T24H1-A00, A0Z
-A04
-AS8
-AF8
230/208-60-1
1
1
1
1 or 2
24
45
48
65
35
50
50
70
8
8
8
6
10
10
10
8
24
42
35
45
8
8
10
10
T24H1-B00, B0Z
-B06
-B09
230/208-60-3
1
1
1
16
34
42
20
35
45
12
8
8
12
10
10
T24H1-C0Z
-C06
-C09
460-60-3
1
1
1
9
18
23
15
20
25
14
12
10
14
12
10
T30H1-A00, A0Z
-A04
-AS8
-AF8
230/208-60-1
1
1
1
1 or 2
24
45
48
66
35
50
50
70
8
8
8
4
10
10
10
8
24
42
35
45
8
8
10
10
T30H1-B00, B0Z
-B06
-B09
230/208-60-3
1
1
1
18
36
45
25
40
45
10
8
8
10
10
10
T30H1-C0Z
-C06
-C09
460-60-3
1
1
1
10
19
24
15
20
25
14
12
10
14
12
10
T36H1-A00, A0Z
-A05
-A08
-A10
-A15
230/208-60-1
1
1
1 or 2
1 or 2
1 or 2
29
55
70
81
85
40
60
70
90
90
8
6
4
4
4
10
10
8
8
8
29
29
33
42
52
52
40
40
40
45
60
60
8
8
8
8
6
6
10
10
10
10
10
10
T36H1-B00, B0Z
-B06
-B09
-B15
230/208-60-3
1
1
1
1
21
39
48
52
30
45
50
60
10
8
6
6
10
10
10
10
T36H1-C0Z
-C06
-C09
-C15
460-60-3
1
1
1
1
12
21
26
27
15
25
30
30
14
10
10
10
14
10
10
10
T42H1-A00, A0Z
-A05
-A08
-A10
-A15
230/208-60-1
1
1
1 or 2
1 or 2
1 or 2
31
57
73
83
86
40
60
80
90
90
8
6
4
4
3
10
10
8
8
8
31
31
34
42
52
52
40
40
40
45
60
60
8
8
8
8
6
6
10
10
10
10
10
10
T42H1-B00, B0Z
-B06
-B09
-B15
230/208-60-3
1
1
1
1
26
44
53
53
35
50
60
60
8
8
6
6
10
10
10
10
T42H1-C0Z
-C06
-C09
-C15
460-60-3
1
1
1
1
13
22
26
27
15
25
30
30
12
10
10
10
12
10
10
10
T48H1-A00, A0Z
-A05
-A08
-A10
-A15
230/208-60-1
1
1 or 2
1 or 2
1 or 2
1 or 2
37
63
79
89
89
50
70
90
100
100
8
6
4
3
3
10
8
8
8
8
37
37
37
37
26
42
52
52
50
50
50
50
30
50
60
60
8
8
8
8
10
8
6
6
10
10
10
10
10
10
10
10
T48H1-B00, B0Z
-B06
-B09
-B15
230/208-60-3
1
1
1
1
27
45
54
55
40
50
60
60
8
8
6
6
10
10
10
10
T48H1-C0Z
-C06
-C09
-C15
460-60-3
1
1
1
1
15
24
28
29
20
25
30
30
12
10
10
10
12
10
10
10
T60H1-A00, A0Z
-A05
-A10
-A15
-A20
230/208-60-1
1
1 or 2
1 or 2
1 or 2
1 or 3
44
70
96
96
113
60
80
100
100
125
8
4
3
3
2
10
8
8
8
6
44
44
44
44
26
52
52
52
26
50
50
50
50
30
60
60
60
30
8
8
8
8
10
6
6
6
10
10
10
10
10
10
10
10
10
10
T60H1-B00, B0Z
-B06
-B09
-B15
-B18
230/208-60-3
1
1
1
1
2
31
49
58
58
N/A
45
60
60
60
N/A
8
8
6
6
N/A
10
10
10
10
N/A
58
28
60
30
6
10
10
10
T60H1-C0Z
-C06
-C09
-C15
-C18
460-60-3
1
1
1
1
1
16
25
29
29
34
20
30
30
30
35
12
10
10
10
8
12
10
10
10
10