background image

Manual 2100-414C
Page

18

DEFROST CYCLE

The defrost cycle is controlled by temperature and time

on the solid state heat pump control.  See Figure 12.

When the outdoor temperature is in the lower 40° F

temperature range or colder, the outdoor coil

temperature is 32° F or below.  This coil temperature is

sensed by the coil temperature sensor mounted near the

bottom of the outdoor coil.  Once coil temperature

reaches 30° F or below, the coil temperature sensor

sends a signal to the control logic of the heat pump

control and the defrost timer will start.

After 60 minutes at 30° F or below, the heat pump

control will place the system in the defrost mode.

During the defrost mode, the refrigerant cycle switches

back to the cooling cycle, the outdoor motor stops,

electric heaters are energized, and hot gas passing

through the outdoor coil melts any accumulated frost.

When the temperature rises to approximately 57° F, the

coil temperature sensor will send a signal to the heat

pump control which will return the system to heating

operations automatically.

If some abnormal or temporary condition such as a high

wind causes the heat pump to have a prolonged defrost

cycle, the heat pump control will restore the system to

heating operation automatically after 10 minutes.

The heat pump defrost control board has an option of

30, 60 or 90 minutes setting.  All models are shipped

from the factory on the 60-minute pin.  If special

circumstances require a change to another time, remove

the wire from the 60-minute terminal and reconnect to

the desired terminal.  The manufacturer's

recommendation is for 60-minute defrost cycles.  Refer

to Figure 12.

FIGURE  12

DEFROST CONTROL BOARD

MIS-1174

There is a cycle speed up jumper on the control.  This

can be used to reduce the time between defrost cycle

operation without waiting for time to elapse.

Use a small screwdriver or other metallic object, or

another 1/4 inch QC, to short between the 

SPEEDUP

terminals to accelerate the HPC timer and initiate

defrost.

Be careful not to touch any other terminals with the

instrument used to short the 

SPEEDUP

 terminals.  It

may take up to 10 seconds with the 

SPEEDUP

terminals shorted for  the speedup to be completed and

the defrost cycle to start.

As soon as the defrost cycle kicks in remove the

shorting instrument from the SPEEDUP terminals.

Otherwise the timing will remain accelerated and run

through the 1-minute minimum defrost length sequence

in a matter of seconds and will automatically terminate

the defrost sequence.

There is an initiate defrost jumper (sen jump) on the

control that can be used at any outdoor ambient during

the heating cycle to simulate a  0° coil temperature.

This can be used to check defrost operation of the unit

without waiting for the outdoor ambient to fall into the

defrost region.

By placing a jumper across the 

SEN JMP

 terminals (a

1/4 inch QC terminal works best) the defrost sensor

mounted on the outdoor coil is shunted out and will

activate the timing circuit.  This permits the defrost

cycle to be checked out in warmer weather conditions

without the outdoor temperature having to fall into the

defrost region.

In order to terminate the defrost test the 

SEN JMP

jumper must be removed.  If left in place too long the
compressor could stop due to the high pressure control

opening because of  high

pressure condition created

by operating in the cooling

mode with outdoor fan off.

Pressure will rise fairly fast

as there is likely no actual

frost on the outdoor coil in

this artificial test condition.

There is also a 5 minute

compressor time delay

function built into the HPC.

This is to protect the

compressor from short cycling

conditions.  In some instances

it is helpful to the service

technician to override or speed

up this timing period, and

shorting out the 

SPEEDUP

terminals for a few seconds

can do this.

Summary of Contents for SH611D

Page 1: ...ONS WALL MOUNTED PACKAGE HEAT PUMPS Model SH611D Manual 2100 414C Supersedes 2100 414B File Volume III Tab 17 Date 05 06 05 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as...

Page 2: ...wer Performance 21 Table 10 Maximum ESP of Operation 21 Table 11 Pressure Table Cooling 22 Table 12 Pressure Table Heating 22 Getting Other Information and Publications For More Information 1 Wall Mou...

Page 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Co...

Page 4: ...1 B 230 208 60 3 C 460 60 3 VENTILATIONOPTIONS X Barometric Fresh Air Damper Standard 1 B Blank off Plate M Motorized Fresh Air Damper 1 V Commercial Room Ventilator Motorized with Exhaust E Economize...

Page 5: ...h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q A B C B D 1 1 6 H S 2 4 4 1 2 2 8 7 4 9 8 7 9 8 7 9 2 8 7 5 1 8 7 9 2 8 7 3 4 9 1 8 5 1 4 0 3 6 1 1 1 2 4 7 3 4 3...

Page 6: ...should adhere to local codes DUCT WORK Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit All duct work supply and return must...

Page 7: ...grille filters must be of sufficient size to allow a maximum velocity of 400 fpm FILTERS A 1 inch throwaway filter is supplied with each unit The filter slides into position making it easy to service...

Page 8: ...ch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 3 and 4 for details WARNING Failur...

Page 9: ...Manual 2100 414C Page 7 FIGURE 3 MOUNTING INSTRUCTIONS...

Page 10: ...mum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum...

Page 11: ...Manual 2100 414C Page 9 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS MIS 548 SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 12: ...Manual 2100 414C Page 10 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS MIS 550 FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION...

Page 13: ...event unauthorized access to the disconnect To convert for the locking capability bend the tab locate in the bottom left hand corner of the disconnect opening under the disconnect access panel straigh...

Page 14: ...e and in Table 4 will work with this equipment The thermostat and subbase must be matched and the correct operation can be assured only by proper selection and application of these parts FIGURE 8 SHXX...

Page 15: ...MABLE THERMOSTAT FULL TIME DEHUMIDIFICATION IMPORTANT NOTE Only the thermostat and subbase combinations as shown in Table 4 will work with this equipment The thermostat and subbase must be matched and...

Page 16: ...or of the equipment must manually place the system switch in this position This is done when there is a known problem with the unit or when the red flashing LED comes on indicating a problem FIGURE 10...

Page 17: ...low pressure trip by the electronic heat pump control This is a 24 VAC output W2 terminal is second stage heat if equipped O1 terminal is the ventilation input This terminal energizes any factory inst...

Page 18: ...rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on th...

Page 19: ...e energized by manual fan switch on subbase for constant air circulation Refer to Figure 14 HEATING SEQUENCE On a call for heating the compressor and reversing valve of the unit are energized to provi...

Page 20: ...g for time to elapse Use a small screwdriver or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to t...

Page 21: ...i s a h p r e w o P t c e r r o c e s a h p n o D E L d e r r o f k c e h C y l n o s t i n u e s a h p 3 r o t i n o m t i n u e h t o t s d a e l r e w o p o w t h c t i w S r o t o m r o o d t u o...

Page 22: ...66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0 44...

Page 23: ...s n e m i D D 1 1 6 H S 5 7 1 TABLE 7 REFRIGERANTCHARGE l e d o M d e t a R w o l f r i A D O 5 9 e r u t a r e p m e T D O 2 8 e r u t a r e p m e T D 1 1 6 H S 0 5 3 1 1 5 8 4 3 5 0 5 Rated CFM and...

Page 24: ...S h g i H 9 6 1 8 1 0 7 7 0 2 2 7 9 2 2 3 7 7 4 2 5 7 1 6 2 6 7 2 7 2 6 7 8 7 2 7 7 1 8 2 8 7 0 8 2 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 7 7 8 1 2 7 4 1 2 5 7 7 3 2 6 7 6 5 2 8...

Page 25: ...Manual 2100 414C Page 23 FIGURE 14 BARD HEAT PUMP COOLING MODE CIRCUIT DIAGRAM FIGURE 15 BARD HEAT PUMP DEHUMIDIFICATION MODE CIRCUIT DIAGRAM...

Reviews: