background image

Manual 2100-414C
Page

8

FIGURE  4

ELECTRIC HEAT CLEARANCE

SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL
MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO
COMBUSTIBLE SURFACES.

         WARNING

A minimum of 1/4 inch clearance must be maintained between the
supply air duct and combustible materials.  This is required for the
first 3 feet of ducting.

It is important to insure that the 1/4 inch minimum spacing is
maintained at all points.

Failure to do this could result in overheating the combustible
material and may result in a fire causing property damage, injury
or death.

MIS-277

Summary of Contents for SH611D

Page 1: ...ONS WALL MOUNTED PACKAGE HEAT PUMPS Model SH611D Manual 2100 414C Supersedes 2100 414B File Volume III Tab 17 Date 05 06 05 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as...

Page 2: ...wer Performance 21 Table 10 Maximum ESP of Operation 21 Table 11 Pressure Table Cooling 22 Table 12 Pressure Table Heating 22 Getting Other Information and Publications For More Information 1 Wall Mou...

Page 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Co...

Page 4: ...1 B 230 208 60 3 C 460 60 3 VENTILATIONOPTIONS X Barometric Fresh Air Damper Standard 1 B Blank off Plate M Motorized Fresh Air Damper 1 V Commercial Room Ventilator Motorized with Exhaust E Economize...

Page 5: ...h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q A B C B D 1 1 6 H S 2 4 4 1 2 2 8 7 4 9 8 7 9 8 7 9 2 8 7 5 1 8 7 9 2 8 7 3 4 9 1 8 5 1 4 0 3 6 1 1 1 2 4 7 3 4 3...

Page 6: ...should adhere to local codes DUCT WORK Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit All duct work supply and return must...

Page 7: ...grille filters must be of sufficient size to allow a maximum velocity of 400 fpm FILTERS A 1 inch throwaway filter is supplied with each unit The filter slides into position making it easy to service...

Page 8: ...ch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 3 and 4 for details WARNING Failur...

Page 9: ...Manual 2100 414C Page 7 FIGURE 3 MOUNTING INSTRUCTIONS...

Page 10: ...mum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum...

Page 11: ...Manual 2100 414C Page 9 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS MIS 548 SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 12: ...Manual 2100 414C Page 10 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS MIS 550 FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION...

Page 13: ...event unauthorized access to the disconnect To convert for the locking capability bend the tab locate in the bottom left hand corner of the disconnect opening under the disconnect access panel straigh...

Page 14: ...e and in Table 4 will work with this equipment The thermostat and subbase must be matched and the correct operation can be assured only by proper selection and application of these parts FIGURE 8 SHXX...

Page 15: ...MABLE THERMOSTAT FULL TIME DEHUMIDIFICATION IMPORTANT NOTE Only the thermostat and subbase combinations as shown in Table 4 will work with this equipment The thermostat and subbase must be matched and...

Page 16: ...or of the equipment must manually place the system switch in this position This is done when there is a known problem with the unit or when the red flashing LED comes on indicating a problem FIGURE 10...

Page 17: ...low pressure trip by the electronic heat pump control This is a 24 VAC output W2 terminal is second stage heat if equipped O1 terminal is the ventilation input This terminal energizes any factory inst...

Page 18: ...rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on th...

Page 19: ...e energized by manual fan switch on subbase for constant air circulation Refer to Figure 14 HEATING SEQUENCE On a call for heating the compressor and reversing valve of the unit are energized to provi...

Page 20: ...g for time to elapse Use a small screwdriver or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to t...

Page 21: ...i s a h p r e w o P t c e r r o c e s a h p n o D E L d e r r o f k c e h C y l n o s t i n u e s a h p 3 r o t i n o m t i n u e h t o t s d a e l r e w o p o w t h c t i w S r o t o m r o o d t u o...

Page 22: ...66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0 44...

Page 23: ...s n e m i D D 1 1 6 H S 5 7 1 TABLE 7 REFRIGERANTCHARGE l e d o M d e t a R w o l f r i A D O 5 9 e r u t a r e p m e T D O 2 8 e r u t a r e p m e T D 1 1 6 H S 0 5 3 1 1 5 8 4 3 5 0 5 Rated CFM and...

Page 24: ...S h g i H 9 6 1 8 1 0 7 7 0 2 2 7 9 2 2 3 7 7 4 2 5 7 1 6 2 6 7 2 7 2 6 7 8 7 2 7 7 1 8 2 8 7 0 8 2 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 7 7 8 1 2 7 4 1 2 5 7 7 3 2 6 7 6 5 2 8...

Page 25: ...Manual 2100 414C Page 23 FIGURE 14 BARD HEAT PUMP COOLING MODE CIRCUIT DIAGRAM FIGURE 15 BARD HEAT PUMP DEHUMIDIFICATION MODE CIRCUIT DIAGRAM...

Reviews: