Manual 2100-752B
Page
34 of 49
10
1
2 3
4
5
6
7
8
16
15
14
13
12
11
9
3
5
1 2
4
MIS-2839
FIGURE 28
Control Connector Motor Half
* Suggested mating connector
Housing — AMP 350809-1
Contact — AMP 350537-1
**
WARNING
–
Applying 240VAC line input with
PIN 1 to PIN 2 jumper in place will permanently
damage unit!
Power Connector Motor Half
Mode of
Operation
OFF
Continuous
Blower
(Ventilation
Mode)
Part Load
Cooling
("Y1-Y2"
Jumper
Removed)
Full Load
Cooling
Dehum.
Mode
Heat 1st
Bank of Elec.
Heat
Heat 1st &
2nd Bank of
Elec. Heat
Thermostat
24 VAC
Input
Signals
—
"G"
"G", "Y1"
"G",
"Y1","Y2"
"D"
"G", "B/W1"
"G", "B/W1",
"W2"
Pin #1
24 VAC "C" (Common) Signal, Always Energized
Pin #2
Not Used
Pin #3
24 VAC "C" (Common) Signal, Always Energized
Pin #4
Not Used
Pin #5
Not Used
Pin #6
X
X
X
Pin #7
Not Used
Pin #8
Not Used
Pin #9
X
X
Pin #10
X
X
X
X
X
Pin #11
Not Used
Pin #12
24 VAC Hot "R" Signal, Always Energized
Pin #13
X
X
Pin #14
X
Pin #15
X
X
X
X
X
Pin #16
Not Used
Power Connector
PWB Header
AMP 1-350945-0
PIN
Description
1
Jumper Pin 1 to Pin 2 for
120VAC Line Input Only **
2
3
Chassis Ground
4
AC Line
5
AC Line
TABLE 6
Troubleshooting ECM
TM
Indoor Blower Motors