SUCTION AND DISCHARGE TUBE
BRAZING

Compliant Scroll compressors have copper plated steel
suction and discharge tubes.  These tubes are far more
rugged and less prone to leaks than copper tubes used on
other compressors.  Due to different thermal properties of
steel and copper, brazing procedures may have to be
changed from those commonly used.

To disconnect:  heat joint Areas 2 and 3 slowly and
uniformly until braze material softens and the tube can
be pulled out of suction fitting.  (See Figure 10.)

To connect:

Recommended brazing materials:  silfos with
minimum 5% silver or silver braze material with
flux.

Reinsert tube into fitting.

Heat tube uniformly in Area 1 moving slowly to
Area 2.  When joint reaches brazing temperature,
apply brazing material.  (See Figure 10.)

Heat joint uniformly around the circumference to
flow braze material completely around the joint.

Slowly move torch into Area 3 to draw braze
material into joint.  (See Figure 10.)

Do not overheat joint.

MIS-1179

FIGURE  13

BRAZING DIAGRAM

Summary of Contents for PH1224

Page 1: ...STRUCTIONS SINGLE PACKAGE HEAT PUMPS MODELS PH1224 PH1230 PH1236 Manual 2100 344 File Volume II Tab 11 Date 08 21 98 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned...

Page 2: ...Discharge Tube Brazing 17 Pressure Tables 18 Wiring Diagrams 19 21 Figures Figure 1 Prefabricated Rood Curb Specifications 4 Figure 2 Field Fabricated Curbing 4 Figure 3 Elevated Mounting Platforms 6...

Page 3: ...d Summer Air Conditioning and Equipment Selection Commercial Low Pressure ACCA Manual Q Low Velocity Duct System Design Load Calculation For Commercial ACCA Manual N Summer and Winter Air Conditioning...

Page 4: ...0 4 2 5 0 1 5 1 0 0 1 7 1 0 0 1 4 3 0 0 2 1 5 5 7 3 0 5 7 5 2 1 1 0 0 8 2 1 0 0 0 6 2 0 0 4 8 3 8 0 2 7 1 4 5 2 6 0 6 0 3 1 1 1 6 2 3 5 9 7 0 3 0 6 0 8 0 1 6 4 0 1 0 1 8 9 0 B B P 3 H E 5 1 B B P 3 H...

Page 5: ...uct work Flanges are provided for attaching the supply and return ducts These instructions explain the recommended method to install the air cooled self contained unit and the electrical wiring connec...

Page 6: ...ation Return Air Dimension C is length Supply Air Dimension C is length Return Air Dimension H is width Supply Sir Dimension J is width f o o R b r u C A B C D E F J H d o o H f o o R l e d o M g n i...

Page 7: ...mbustible materials necessary to dispose of the condensate from the outdoor coil on the heating cycle and this is virtually impossible with the unit installed inside the crawl space 3 SLAB MOUNTED AT...

Page 8: ...Manual 2100 344 Page 6 FIGURE 3 ELEVATED MOUNTING PLATFORMS MIS 1183 MIS 1185 FIGURE 4 AIRFLOW and SERVICE ACCESS CLEARANCES...

Page 9: ...Manual 2100 344 Page 7 FIGURE 5 ROOF TOP APPLICATION May also be required for ground level installations MIS 1176 FIGURE 6 SLAB MOUNTING AT GROUND LEVEL Above 32 F Outside Temperature MIS 1184...

Page 10: ...larger Do not operate unit without trap Unit must be level or slightly inclined toward drain With a trap installed on a unit located in an unconditioned area water in the trap may freeze It is recomme...

Page 11: ...e for connection with copper wire only These instructions must be adhered to Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wirin...

Page 12: ...a c i d n I y a l p s i D k c e h C s p m a L g n i t a c i d n I 4 3 0 3 0 4 8 0 8 4 9 F 1 f o t r a P t a t s o m r e h T p u k c a b y r e t t a B y a d 7 e l b a m m a r g o r p l a t i g i D t a...

Page 13: ...ing of the heating equipment to the structure Utilization of the Heating Application Data and the heat loss calculation of the building are useful in determining the correct set points TRANSFORMER TAP...

Page 14: ...etergent THREE PHASE SCROLL COMPRESSOR START UP INFORMATION Scroll compressors like several other types of compressors will only compress in one rotational direction Direction of rotation is not an is...

Page 15: ...Manual 2100 344 Page 13 FIGURE 11 HEAT PUMP CONTROL BOARD MIS 1191...

Page 16: ...2 5 0 5 2 6 1 6 0 6 8 5 4 5 2 5 SERVICE AND TROUBLESHOOTING SERVICE HINTS 1 Caution homeowner to maintain clean air filters at all times Also not to needlessly close off supply and return air register...

Page 17: ...v i t c e f e d r o t i c a p a c r o t o M g n i t a r r o t i c a p a c k c e h C d e t r o h s r o n e p o r o f k c e h C r o t i c a p a c r o t i c a p a c e c a l p e R l o r t n o c p m u p t...

Page 18: ...1 2 8 9 4 0 2 1 9 1 2 6 2 1 0 8 2 3 8 5 6 3 0 8 6 2 9 4 2 1 0 8 0 1 3 7 8 4 0 1 1 9 8 0 2 2 1 0 9 2 8 4 5 5 3 0 9 6 3 8 1 2 1 0 9 0 1 7 6 7 4 0 0 1 8 0 1 8 1 1 0 0 3 5 4 5 4 3 0 0 7 3 8 8 1 1 0 0 1 1...

Page 19: ...owly and uniformly until braze material softens and the tube can be pulled out of suction fitting See Figure 10 To connect Recommended brazing materials silfos with minimum 5 silver or silver braze ma...

Page 20: ...2 9 7 4 9 2 0 8 4 1 3 1 8 3 3 3 2 8 5 5 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 7 7 6 1 2 9 7 1 3 2 0 8 8 4 2 2 8 5 6 2 3 8 3 8 2 4 8 2 0 3 6 8 2 2 3 7 8 2 4 3 8 8 4 6 3 B D g e d...

Page 21: ...Manual 2100 344 Page 19 Wiring Diagram 4098 123 printed from CAD to get size needed...

Page 22: ...Manual 2100 344 Page 20 Wiring Diagram 4098 124 printed from CAD to get size needed...

Page 23: ...Manual 2100 344 Page 21 Wiring Diagram 4098 211 printed from CAD to get size needed...

Reviews: