Bard PH1224 Installation Instructions Manual Download Page 13

Manual 2100-344
Page

11

COMPRESSOR CUTOFF THERMOSTAT
WIRING  (15 KW ONLY)

FIGURE  9

UNIT 24V TERMINAL BOARD

MIS-1188

FIGURE  10

UNIT 24V TERMINAL BOARD

MIS-1189

TABLE 8

5 and 10 KW

l

e

d

o

M

W

K

s

t

l

o

V

e

s

a

h

P

4

2

2

1

H

P

0

1

,

5

,

0

0

3

2

1

0

3

2

1

H

P

0

1

,

5

,

0

0

3

2

1

6

3

2

1

H

P

0

1

,

5

,

0

0

3

2

1

TABLE 9

15 KW ONLY

l

e

d

o

M

W

K

s

t

l

o

V

e

s

a

h

P

0

3

2

1

H

P

5

1

0

3

2

1

6

3

2

1

H

P

5

1

0

3

2

1

COMPRESSOR  CUTOFF THERMOSTAT
WIRING  (5 and 10 KW)

COMPRESSOR CUTOFF THERMOSTAT
and OUTDOOR THERMOSTAT WIRING

Heat pump compressor operation at outdoor temperatures
below 0° F are neither desirable nor advantageous in terms
of efficiency.  Since most equipment at time of manufacture
is not designated for any specific destination of the county
and most of the equipment is installed in areas not
approaching the lower outdoor temperature range, the
compressor cutoffs are not factory installed.

Outdoor thermostats are available to hold off various banks
of electric heat until needed as determined by outdoor
temperature.  The set point of either type of thermostat is
variable with geographic region and sizing of the heating
equipment to the structure.  Utilization of the Heating
Application Data and the heat loss calculation of the
building are useful in determining the correct set points.

TRANSFORMER TAPS

230/208V, 1 phase and 3 phase equipment employ dual
primary voltage transformers.  All equipment leaves the
factory wired on 240V tap.  For 208V operation, reconnect
from 240V to 208V tap.  The acceptable operating voltage
range for the 240 and 208V taps are:

TAP

 RANGE

 240

253 – 216

 208

220 – 187

NOTE: The voltage should be measured at the field power

connection point in the unit and while the unit is
operating at full load (maximum amperage
operating condition).

THERMOSTAT INDICATOR LAMPS

The red lamp marked “EM. HT.” comes on and stays on
whenever the system switch is placed in Em. Ht. position.
The green lamp marked “Check” will come on if there is any
problem that prevents the compressor from running when it
is supposed to be.

EMERGENCY HEAT POSITION

The operator of the equipment must manually place the
system switch in this position.  This is done when there is a
known problem with the outdoor section, or when the green
“Check” lamp comes on indicating a problem.

REMOVE FACTORY
JUMPER Y-Y1

OUTDOOR THERMOSTAT
USED AS COMPRESSOR CUTOFF

REMOVE FACTORY
JUMPER Y-Y1

OUTDOOR THERMOSTAT
USED AS COMPRESSOR CUTOFF

Summary of Contents for PH1224

Page 1: ...STRUCTIONS SINGLE PACKAGE HEAT PUMPS MODELS PH1224 PH1230 PH1236 Manual 2100 344 File Volume II Tab 11 Date 08 21 98 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned...

Page 2: ...Discharge Tube Brazing 17 Pressure Tables 18 Wiring Diagrams 19 21 Figures Figure 1 Prefabricated Rood Curb Specifications 4 Figure 2 Field Fabricated Curbing 4 Figure 3 Elevated Mounting Platforms 6...

Page 3: ...d Summer Air Conditioning and Equipment Selection Commercial Low Pressure ACCA Manual Q Low Velocity Duct System Design Load Calculation For Commercial ACCA Manual N Summer and Winter Air Conditioning...

Page 4: ...0 4 2 5 0 1 5 1 0 0 1 7 1 0 0 1 4 3 0 0 2 1 5 5 7 3 0 5 7 5 2 1 1 0 0 8 2 1 0 0 0 6 2 0 0 4 8 3 8 0 2 7 1 4 5 2 6 0 6 0 3 1 1 1 6 2 3 5 9 7 0 3 0 6 0 8 0 1 6 4 0 1 0 1 8 9 0 B B P 3 H E 5 1 B B P 3 H...

Page 5: ...uct work Flanges are provided for attaching the supply and return ducts These instructions explain the recommended method to install the air cooled self contained unit and the electrical wiring connec...

Page 6: ...ation Return Air Dimension C is length Supply Air Dimension C is length Return Air Dimension H is width Supply Sir Dimension J is width f o o R b r u C A B C D E F J H d o o H f o o R l e d o M g n i...

Page 7: ...mbustible materials necessary to dispose of the condensate from the outdoor coil on the heating cycle and this is virtually impossible with the unit installed inside the crawl space 3 SLAB MOUNTED AT...

Page 8: ...Manual 2100 344 Page 6 FIGURE 3 ELEVATED MOUNTING PLATFORMS MIS 1183 MIS 1185 FIGURE 4 AIRFLOW and SERVICE ACCESS CLEARANCES...

Page 9: ...Manual 2100 344 Page 7 FIGURE 5 ROOF TOP APPLICATION May also be required for ground level installations MIS 1176 FIGURE 6 SLAB MOUNTING AT GROUND LEVEL Above 32 F Outside Temperature MIS 1184...

Page 10: ...larger Do not operate unit without trap Unit must be level or slightly inclined toward drain With a trap installed on a unit located in an unconditioned area water in the trap may freeze It is recomme...

Page 11: ...e for connection with copper wire only These instructions must be adhered to Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wirin...

Page 12: ...a c i d n I y a l p s i D k c e h C s p m a L g n i t a c i d n I 4 3 0 3 0 4 8 0 8 4 9 F 1 f o t r a P t a t s o m r e h T p u k c a b y r e t t a B y a d 7 e l b a m m a r g o r p l a t i g i D t a...

Page 13: ...ing of the heating equipment to the structure Utilization of the Heating Application Data and the heat loss calculation of the building are useful in determining the correct set points TRANSFORMER TAP...

Page 14: ...etergent THREE PHASE SCROLL COMPRESSOR START UP INFORMATION Scroll compressors like several other types of compressors will only compress in one rotational direction Direction of rotation is not an is...

Page 15: ...Manual 2100 344 Page 13 FIGURE 11 HEAT PUMP CONTROL BOARD MIS 1191...

Page 16: ...2 5 0 5 2 6 1 6 0 6 8 5 4 5 2 5 SERVICE AND TROUBLESHOOTING SERVICE HINTS 1 Caution homeowner to maintain clean air filters at all times Also not to needlessly close off supply and return air register...

Page 17: ...v i t c e f e d r o t i c a p a c r o t o M g n i t a r r o t i c a p a c k c e h C d e t r o h s r o n e p o r o f k c e h C r o t i c a p a c r o t i c a p a c e c a l p e R l o r t n o c p m u p t...

Page 18: ...1 2 8 9 4 0 2 1 9 1 2 6 2 1 0 8 2 3 8 5 6 3 0 8 6 2 9 4 2 1 0 8 0 1 3 7 8 4 0 1 1 9 8 0 2 2 1 0 9 2 8 4 5 5 3 0 9 6 3 8 1 2 1 0 9 0 1 7 6 7 4 0 0 1 8 0 1 8 1 1 0 0 3 5 4 5 4 3 0 0 7 3 8 8 1 1 0 0 1 1...

Page 19: ...owly and uniformly until braze material softens and the tube can be pulled out of suction fitting See Figure 10 To connect Recommended brazing materials silfos with minimum 5 silver or silver braze ma...

Page 20: ...2 9 7 4 9 2 0 8 4 1 3 1 8 3 3 3 2 8 5 5 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 7 7 6 1 2 9 7 1 3 2 0 8 8 4 2 2 8 5 6 2 3 8 3 8 2 4 8 2 0 3 6 8 2 2 3 7 8 2 4 3 8 8 4 6 3 B D g e d...

Page 21: ...Manual 2100 344 Page 19 Wiring Diagram 4098 123 printed from CAD to get size needed...

Page 22: ...Manual 2100 344 Page 20 Wiring Diagram 4098 124 printed from CAD to get size needed...

Page 23: ...Manual 2100 344 Page 21 Wiring Diagram 4098 211 printed from CAD to get size needed...

Reviews: