Bard PH1224 Installation Instructions Manual Download Page 14

Manual 2100-344
Page

12

START UP AND OPERATION

the reversing valve solenoid constantly whenever the system
switch on subbase is placed in “Heat” position, the “B”
terminal being constantly energized from R.  A thermostat
demand for heat completes R-Y circuit, pulling in
compressor contactor starting compressor and outdoor
motor.  R-G also make starting indoor blower motor.

DEFROST CYCLE

The defrost cycle is controlled by temperature and time on
the solid state heat pump control.

When the outdoor temperature is in the lower 40° F
temperature range or colder, the outdoor coil temperature is
32°F or below.  This temperature is sensed by the coil
sensor mounted near the bottom of the outdoor coil.  Once
the coil temperature reaches 32°F or below, the coil sensor
sends a signal to the control logic of the heat pump control
and defrost timer will start.

After 60 (90 or 30) minutes at 32°F or below, the heat pump
control will place the system in the defrost mode.

During the defrost mode, the refrigerant cycle switches back
to the cooling cycle, the outdoor motor stops, electric heaters
are energized, and hot gas passing through the outdoor coil
melts any accumulated frost.  When the temperature rises to
approximately 57° F, the coil sensor will send a signal to the
heat pump control which will return the system to heating
operations automatically.

If some abnormal or temporary condition such as a high
wind causes the heat pump to have a prolonged defrost
cycle, the heat pump control will restore the system to
heating operation automatically after 10 minutes.

There are three settings on the heat pump control -- 30
minutes, 60 minutes, and 90 minutes.  Most models are
shipped wired on the 60 minutes setting for greatest
operating economy.  If special circumstances require a
change to another time, remove wire connected to terminal
60 and reconnect to desired terminal.  (See Figure 11.)

There is a cycle speed up jumper on the control.  This can be
used to reduce the time between defrost cycle operation
without waiting for time to elapse.

There is an initial defrost (sen jmp) jumper on the control
that can be used at any outdoor ambient during the heating
cycle to simulate a 0° coil temperature.  This can be used to
check defrost operation of the unit without waiting for the
outdoor ambient to fall into the defrost region.

START UP NOTES

For improved start up performance, wash the indoor coil
with dishwasher detergent

THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION

Scroll compressors, like several other types of compressors,
will only compress in one rotational direction.  Direction of
rotation is not an issue with single phase compressors since
they will always start and run in the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since there
is a 50-50 chance of connecting power in such a way as to
cause rotation in the reverse direction, verification of proper
rotation must be made.   Verification of proper rotation
direction is made by observing that suction pressure drops
and discharge pressure rises when the compressor is
energized.  Reverse rotation also results in an elevated
sound level over that with correct rotation, as well as,
substantially reduced current draw compared to tabulated
values.

Verification of proper rotation must be made at the time
the equipment is put into service.
  If improper rotation is
corrected at this time there will be no negative impact on the
durability of the compressor.  However, reverse operation for
over one hour may have a negative impact on the bearing
due to oil pump out.

NOTE: If compressor is allowed to run in reverse

rotation for several minutes the compressor’s
internal protector will trip.

All three phase ZR*3 compressors are wired identically
internally.  As a result, once the correct phasing is
determined for a specific system or installation, connecting
properly phased power leads to the same Fusite terminals
should maintain proper rotation direction.

The direction of rotation of the motor may be changed by
reversing any two line connections to the unit.

SEQUENCE OF OPERATION

COOLING

  –  Circuit R-Y makes at thermostat pulling in

compressor contactor starting the compressor and outdoor
motor.  The G (indoor motor) circuit is automatically
completed on any call for cooling operation, or can be
energized by manual fan switch on subbase for constant air
circulation.

HEATING

  –  A 24V solenoid coil on reversing valve

controls heating cycle operation.  Two thermostat options,
one allowing “AUTO” changeover from cycle to cycle and
the other constantly energizing solenoid coil during heating
season and thus eliminating pressure equalization noise
except during defrost, are to be used.  On “AUTO” option, a
circuit is completed from R-W1 and R-Y on each heating
“On” cycle energizing reversing valve solenoid and pulling
in compressor contactor starting compressor and outdoor
motor. R-G also make starting indoor blower motor.  Heat
pump heating cycle now in operation.  The second energizes

Summary of Contents for PH1224

Page 1: ...STRUCTIONS SINGLE PACKAGE HEAT PUMPS MODELS PH1224 PH1230 PH1236 Manual 2100 344 File Volume II Tab 11 Date 08 21 98 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned...

Page 2: ...Discharge Tube Brazing 17 Pressure Tables 18 Wiring Diagrams 19 21 Figures Figure 1 Prefabricated Rood Curb Specifications 4 Figure 2 Field Fabricated Curbing 4 Figure 3 Elevated Mounting Platforms 6...

Page 3: ...d Summer Air Conditioning and Equipment Selection Commercial Low Pressure ACCA Manual Q Low Velocity Duct System Design Load Calculation For Commercial ACCA Manual N Summer and Winter Air Conditioning...

Page 4: ...0 4 2 5 0 1 5 1 0 0 1 7 1 0 0 1 4 3 0 0 2 1 5 5 7 3 0 5 7 5 2 1 1 0 0 8 2 1 0 0 0 6 2 0 0 4 8 3 8 0 2 7 1 4 5 2 6 0 6 0 3 1 1 1 6 2 3 5 9 7 0 3 0 6 0 8 0 1 6 4 0 1 0 1 8 9 0 B B P 3 H E 5 1 B B P 3 H...

Page 5: ...uct work Flanges are provided for attaching the supply and return ducts These instructions explain the recommended method to install the air cooled self contained unit and the electrical wiring connec...

Page 6: ...ation Return Air Dimension C is length Supply Air Dimension C is length Return Air Dimension H is width Supply Sir Dimension J is width f o o R b r u C A B C D E F J H d o o H f o o R l e d o M g n i...

Page 7: ...mbustible materials necessary to dispose of the condensate from the outdoor coil on the heating cycle and this is virtually impossible with the unit installed inside the crawl space 3 SLAB MOUNTED AT...

Page 8: ...Manual 2100 344 Page 6 FIGURE 3 ELEVATED MOUNTING PLATFORMS MIS 1183 MIS 1185 FIGURE 4 AIRFLOW and SERVICE ACCESS CLEARANCES...

Page 9: ...Manual 2100 344 Page 7 FIGURE 5 ROOF TOP APPLICATION May also be required for ground level installations MIS 1176 FIGURE 6 SLAB MOUNTING AT GROUND LEVEL Above 32 F Outside Temperature MIS 1184...

Page 10: ...larger Do not operate unit without trap Unit must be level or slightly inclined toward drain With a trap installed on a unit located in an unconditioned area water in the trap may freeze It is recomme...

Page 11: ...e for connection with copper wire only These instructions must be adhered to Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wirin...

Page 12: ...a c i d n I y a l p s i D k c e h C s p m a L g n i t a c i d n I 4 3 0 3 0 4 8 0 8 4 9 F 1 f o t r a P t a t s o m r e h T p u k c a b y r e t t a B y a d 7 e l b a m m a r g o r p l a t i g i D t a...

Page 13: ...ing of the heating equipment to the structure Utilization of the Heating Application Data and the heat loss calculation of the building are useful in determining the correct set points TRANSFORMER TAP...

Page 14: ...etergent THREE PHASE SCROLL COMPRESSOR START UP INFORMATION Scroll compressors like several other types of compressors will only compress in one rotational direction Direction of rotation is not an is...

Page 15: ...Manual 2100 344 Page 13 FIGURE 11 HEAT PUMP CONTROL BOARD MIS 1191...

Page 16: ...2 5 0 5 2 6 1 6 0 6 8 5 4 5 2 5 SERVICE AND TROUBLESHOOTING SERVICE HINTS 1 Caution homeowner to maintain clean air filters at all times Also not to needlessly close off supply and return air register...

Page 17: ...v i t c e f e d r o t i c a p a c r o t o M g n i t a r r o t i c a p a c k c e h C d e t r o h s r o n e p o r o f k c e h C r o t i c a p a c r o t i c a p a c e c a l p e R l o r t n o c p m u p t...

Page 18: ...1 2 8 9 4 0 2 1 9 1 2 6 2 1 0 8 2 3 8 5 6 3 0 8 6 2 9 4 2 1 0 8 0 1 3 7 8 4 0 1 1 9 8 0 2 2 1 0 9 2 8 4 5 5 3 0 9 6 3 8 1 2 1 0 9 0 1 7 6 7 4 0 0 1 8 0 1 8 1 1 0 0 3 5 4 5 4 3 0 0 7 3 8 8 1 1 0 0 1 1...

Page 19: ...owly and uniformly until braze material softens and the tube can be pulled out of suction fitting See Figure 10 To connect Recommended brazing materials silfos with minimum 5 silver or silver braze ma...

Page 20: ...2 9 7 4 9 2 0 8 4 1 3 1 8 3 3 3 2 8 5 5 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 7 7 6 1 2 9 7 1 3 2 0 8 8 4 2 2 8 5 6 2 3 8 3 8 2 4 8 2 0 3 6 8 2 2 3 7 8 2 4 3 8 8 4 6 3 B D g e d...

Page 21: ...Manual 2100 344 Page 19 Wiring Diagram 4098 123 printed from CAD to get size needed...

Page 22: ...Manual 2100 344 Page 20 Wiring Diagram 4098 124 printed from CAD to get size needed...

Page 23: ...Manual 2100 344 Page 21 Wiring Diagram 4098 211 printed from CAD to get size needed...

Reviews: