Bard PH1224 Installation Instructions Manual Download Page 16

Manual 2100-344
Page

14

FAN BLADE SETTINGS

Shown in Figure 12 are the correct fan blade setting
dimensions for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan
and/or motor area will require that the dimensions in
Figure 12 be checked and blade adjusted in or out on the
motor shaft accordingly.

SOLID STATE HEAT PUMP CONTROL
TROUBLESHOOTING PROCEDURE

1. Turn on AC power supply to indoor and outdoor units.

2. Turn thermostat blower switch to fan on.  The indoor

blower should start.  (If it doesn’t, troubleshoot indoor
unit and correct problem.)

3. Turn thermostat blower switch to Auto position.  Indoor

blower should stop.

4. Set system switch to heat or cool.  Adjust thermostat to

call for heat or cool.  The indoor blower, compressor,
and outdoor fan should start.

NOTE:  If there is no power to 24 volt transformer, the

compressor and outdoor fan motor will not start
for 5 minutes.  This is because of the compressor
short cycle protection.

TABLE  10

The above suction line temperatures are based upon 80° F
dry bulb/67° F wet bulb (50% RH) temperature and rated
airflow across the evaporator during cooling cycle.

l

e

d

o

M

d

e

t

a

R

w

o

l

f

r

i

A

F

e

e

r

g

e

D

5

9

D

O

e

r

u

t

a

r

e

p

m

e

T

F

e

e

r

g

e

D

2

8

D

O

e

r

u

t

a

r

e

p

m

e

T

4

2

2

1

H

P

0

3

2

1

H

P

6

3

2

1

H

P

0

0

8

0

0

0

1

0

0

1

1

6

5

-

6

5

6

5

-

6

5

2

5

-

0

5

2

6

-

1

6

0

6

-

8

5

4

5

-

2

5

SERVICE AND TROUBLESHOOTING

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all

times.  Also, not to needlessly close off supply and
return air registers.  This reduces air flow through the
system which shortens equipment service life as well as
increasing operating costs.

2. Switching to heating cycle at 75° F or higher outside

temperature may cause a nuisance trip of the manual
reset high pressure switch.

3. The heat pump wall thermostats perform multiple

functions.  Be sure that all function switches are
correctly set for the desired operating mode before
trying to diagnose any reported service problems.

4. Check all power fuses or circuit breakers to be sure that

they are the correct rating.

5. Periodic cleaning of the outdoor coil to permit full and

unrestricted airflow circulation is essential.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units
so that the system operating pressures can be observed.
Pressure tables can be found in Tables 11 and 12 in this
manual covering all models on both cooling and heating
cycles.  It is imperative to match the correct pressure table to
the unit by model number.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating
plate.  Optimum unit performance will occur with a
refrigerant charge resulting in a suction line temperature
(6” from compressor) as shown in Table 10.

FIGURE  12

FAN BLADE SETTING DIMENSIONS

MIS-1190

l

e

d

o

M

A

n

o

i

s

n

e

m

i

D

4

2

2

1

H

P

0

3

2

1

H

P

6

3

2

1

H

P

"

0

0

.

1

"

5

7

.

"

5

7

.

Summary of Contents for PH1224

Page 1: ...STRUCTIONS SINGLE PACKAGE HEAT PUMPS MODELS PH1224 PH1230 PH1236 Manual 2100 344 File Volume II Tab 11 Date 08 21 98 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned...

Page 2: ...Discharge Tube Brazing 17 Pressure Tables 18 Wiring Diagrams 19 21 Figures Figure 1 Prefabricated Rood Curb Specifications 4 Figure 2 Field Fabricated Curbing 4 Figure 3 Elevated Mounting Platforms 6...

Page 3: ...d Summer Air Conditioning and Equipment Selection Commercial Low Pressure ACCA Manual Q Low Velocity Duct System Design Load Calculation For Commercial ACCA Manual N Summer and Winter Air Conditioning...

Page 4: ...0 4 2 5 0 1 5 1 0 0 1 7 1 0 0 1 4 3 0 0 2 1 5 5 7 3 0 5 7 5 2 1 1 0 0 8 2 1 0 0 0 6 2 0 0 4 8 3 8 0 2 7 1 4 5 2 6 0 6 0 3 1 1 1 6 2 3 5 9 7 0 3 0 6 0 8 0 1 6 4 0 1 0 1 8 9 0 B B P 3 H E 5 1 B B P 3 H...

Page 5: ...uct work Flanges are provided for attaching the supply and return ducts These instructions explain the recommended method to install the air cooled self contained unit and the electrical wiring connec...

Page 6: ...ation Return Air Dimension C is length Supply Air Dimension C is length Return Air Dimension H is width Supply Sir Dimension J is width f o o R b r u C A B C D E F J H d o o H f o o R l e d o M g n i...

Page 7: ...mbustible materials necessary to dispose of the condensate from the outdoor coil on the heating cycle and this is virtually impossible with the unit installed inside the crawl space 3 SLAB MOUNTED AT...

Page 8: ...Manual 2100 344 Page 6 FIGURE 3 ELEVATED MOUNTING PLATFORMS MIS 1183 MIS 1185 FIGURE 4 AIRFLOW and SERVICE ACCESS CLEARANCES...

Page 9: ...Manual 2100 344 Page 7 FIGURE 5 ROOF TOP APPLICATION May also be required for ground level installations MIS 1176 FIGURE 6 SLAB MOUNTING AT GROUND LEVEL Above 32 F Outside Temperature MIS 1184...

Page 10: ...larger Do not operate unit without trap Unit must be level or slightly inclined toward drain With a trap installed on a unit located in an unconditioned area water in the trap may freeze It is recomme...

Page 11: ...e for connection with copper wire only These instructions must be adhered to Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wirin...

Page 12: ...a c i d n I y a l p s i D k c e h C s p m a L g n i t a c i d n I 4 3 0 3 0 4 8 0 8 4 9 F 1 f o t r a P t a t s o m r e h T p u k c a b y r e t t a B y a d 7 e l b a m m a r g o r p l a t i g i D t a...

Page 13: ...ing of the heating equipment to the structure Utilization of the Heating Application Data and the heat loss calculation of the building are useful in determining the correct set points TRANSFORMER TAP...

Page 14: ...etergent THREE PHASE SCROLL COMPRESSOR START UP INFORMATION Scroll compressors like several other types of compressors will only compress in one rotational direction Direction of rotation is not an is...

Page 15: ...Manual 2100 344 Page 13 FIGURE 11 HEAT PUMP CONTROL BOARD MIS 1191...

Page 16: ...2 5 0 5 2 6 1 6 0 6 8 5 4 5 2 5 SERVICE AND TROUBLESHOOTING SERVICE HINTS 1 Caution homeowner to maintain clean air filters at all times Also not to needlessly close off supply and return air register...

Page 17: ...v i t c e f e d r o t i c a p a c r o t o M g n i t a r r o t i c a p a c k c e h C d e t r o h s r o n e p o r o f k c e h C r o t i c a p a c r o t i c a p a c e c a l p e R l o r t n o c p m u p t...

Page 18: ...1 2 8 9 4 0 2 1 9 1 2 6 2 1 0 8 2 3 8 5 6 3 0 8 6 2 9 4 2 1 0 8 0 1 3 7 8 4 0 1 1 9 8 0 2 2 1 0 9 2 8 4 5 5 3 0 9 6 3 8 1 2 1 0 9 0 1 7 6 7 4 0 0 1 8 0 1 8 1 1 0 0 3 5 4 5 4 3 0 0 7 3 8 8 1 1 0 0 1 1...

Page 19: ...owly and uniformly until braze material softens and the tube can be pulled out of suction fitting See Figure 10 To connect Recommended brazing materials silfos with minimum 5 silver or silver braze ma...

Page 20: ...2 9 7 4 9 2 0 8 4 1 3 1 8 3 3 3 2 8 5 5 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 7 7 6 1 2 9 7 1 3 2 0 8 8 4 2 2 8 5 6 2 3 8 3 8 2 4 8 2 0 3 6 8 2 2 3 7 8 2 4 3 8 8 4 6 3 B D g e d...

Page 21: ...Manual 2100 344 Page 19 Wiring Diagram 4098 123 printed from CAD to get size needed...

Page 22: ...Manual 2100 344 Page 20 Wiring Diagram 4098 124 printed from CAD to get size needed...

Page 23: ...Manual 2100 344 Page 21 Wiring Diagram 4098 211 printed from CAD to get size needed...

Reviews: