IMPORTANT INSTALLER NOTE

For improved start up performance wash the indoor coil 
with a dish washing detergent.

HIGH PRESSURE SWITCH

All K**A/K**L wall mounted air conditioner series 
models are supplied with a remote reset for the high 
and low pressure switch.  If tripped, this pressure 
switch may be reset by turning the thermostat off then 
back on again.

THREE PHASE SCROLL COMPRESSOR 

START UP INFORMATION

Scroll compressors, like several other types of 
compressors, will only compress in one rotational 
direction.  Direction of rotation is not an issue with 
single phase compressors since they will always start 
and run in the proper direction.

However, three phase compressors will rotate in either 
direction depending upon phasing of the power.  
Since there is a 50-50 chance of connecting power 
in such a way as to cause rotation in the reverse 
direction, verification of proper rotation must be made.  
Verification of proper rotation direction is made by 
observing that suction pressure drops and discharge 
pressure rises when the compressor is energized.  
Reverse rotation also results in an elevated sound level 
over that with correct rotation, as well as substantially 
reduced current draw compared to tabulated values.

Verification of 

proper rotation

 must be made at the 

time the equipment is put into service.  If improper 
rotation is corrected at this time, there will be no 
negative impact on the durability of the compressor. 
However, reverse operation for over one hour may have 
a negative impact on the bearing due to oil pump out.

NOTE:  If compressor is allowed to run in reverse 

rotation for an extended period of time, the 

compressor’s internal protector will trip.

All three phase compressors are wired identically 
internally.  As a result, once the correct phasing 
is determined for a specific system or installation, 
connecting properly phased power leads to the same 
Fusite terminal should maintain proper rotation 
direction.

The direction of rotation of the compressor may be 
changed by reversing any two line connections to the 
unit.

PHASE MONITOR

All units with three phase scroll compressors are 
equipped with a 3 phase line monitor to prevent 
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two 
LEDs.  If the Y signal is present at the phase monitor 
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and 
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply 
leads to the unit.  

Do not reverse any of the unit factory 

wires as damage may occur.

CONDENSER FAN OPERATION

NOTE:

  All models covered by this manual are 

equipped with a low ambient control (LAC); 

on start up, the condenser fan motor will have 

delayed start until system refrigerant operating 

pressure builds up.  After starting, the fan 

motor may or may not cycle depending upon 

ambient conditions.  This is normal operation.

SERVICE HINTS

1.  Caution owner/operator to maintain clean air 

filters at all times.  Also, not to needlessly close 
off supply and return air registers.  This reduces 
airflow through the system, which shortens 
equipment service life as well as increasing 
operating costs.

2.  Check all power fuses or circuit breakers to be sure 

they are the correct rating.

3.  Periodic cleaning of the outdoor coil to permit full 

and unrestricted airflow circulation is essential.

Summary of Contents for K36A2-A

Page 1: ...6A2 A K36A2 N K42A2 A K42A2 N K48A2 A K48A2 N INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 628 Supersedes NEW Date 12 1 14 K60A2 A K60A2 N K36...

Page 2: ...able 8 Indoor Blower Performance 24 Table 9 Maximum ESP Electric Heat Only 24 Table 10 Electric Heat 24 Getting Other Information and Publications 3 Wall Mount General Information 4 Wall Mount Model N...

Page 3: ...er and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...e entire air conditioning system should be carefully read before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instru...

Page 5: ...s Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return...

Page 6: ...which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is provided for ease of installation but is not required 2 The unit itself is su...

Page 7: ...BLE PANEL ACCESS HEATER ELECTRICAL ENTRANCE HIGH VOLTAGE ENTRANCE ELECTRIC HEAT ACCESS PANEL DISCONNECT C BREAKER BUILT IN RAIN HOOD 4 PITCH J K H C I A 2 13 D 3 4 I D DRAIN HOSE Mounting Brackets Loc...

Page 8: ...4 1 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM T...

Page 9: ...mbustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheat...

Page 10: ...TURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH...

Page 11: ...ALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 12: ...on page 23 for Electrical Specifications WIRING LOW VOLTAGE WIRING All 230 208V 1 phase equipment has dual primary voltage transformers All equipment leaves the factory wired on 240V tap For 208V oper...

Page 13: ...mid Operation Light will come on and the lag unit compresser and blower will operate until the set point of humidty controller is satisfied or cancelled by a call for cooling b If the space temperatur...

Page 14: ...Manual 2100 628 Page 14 of 24 FIGURE 7 THERMOSTAT CONNECTIONS...

Page 15: ...TDOWN NC CONTACTS OPEN ON ALARM Rt REMOVE JUMPER FOR COMP DISABLE FEATURE 2 REMOVE JUMPER WHEN CONNECTING GEN CONTACT 3 REMOVE JUMPER WHEN CONNECTING FIRE SHUTDOWN CONTACT 1 NC CONTACTS OPEN ON ALARM...

Page 16: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Page 17: ...run in reverse rotation for an extended period of time the compressor s internal protector will trip All three phase compressors are wired identically internally As a result once the correct phasing i...

Page 18: ...m relay circuit will energize Recycling the wall thermostat resets the manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120 seconds the com...

Page 19: ...e unit to the serial plate charge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove screws holding...

Page 20: ...URE 10 MOTOR HIGH VOLTAGE CONNECTIONS FIGURE 10 NOTE Bard Models PA13242 PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2...

Page 21: ...e common and the appropriate motor terminal 1 5 G input is typically on terminal 1 but refer to wiring diagram a If the low voltage communication is not present check the demand from the thermostat Al...

Page 22: ...ser Fan Operation page 17 Model Return Air Temperature C Pressure 35 37 39 41 43 45 47 49 51 53 55 K36 2 27 DB 19 WB Low Side High Side 143 145 147 148 150 152 154 156 158 160 162 368 388 408 429 449...

Page 23: ...gle Circuit Minimum Circuit Ampacity Maximum External Fuse or Ckt Brkr Field Power Wire Size Ground Wire K36L2 A0Z 208 230 60 1 1 A05 1 K36L2 N0Z 400 60 3 1 8 2 10 14 14 N05 1 9 8 15 14 14 K42L2 A0Z 2...

Page 24: ...Amps BTUH 5 20 8 17 065 18 1 12 800 6 9 0 21 330 TABLE 7 RECOMMENDED AIRFLOW Model Nominal Rated CFM Nominal Rated ESP Recommended Airflow Range K36A K36L 1100 15 930 1350 K42A K42L 1300 20 1485 1070...