background image

Manual 2100628 

Page 

13 of 24

HUMIDITY CONTROL OPTION

When two units are controlled and connected with 
the MV4001K-B, they can be adapted to perform 
dehumidification with the addition of a simple humidity 
controller that closes-on-rise, and is connected to 
terminals "H1" and "H2" on the main controller board 
(see Figure 8 on page 15).  Recommended is Bard Part 
# 8403-038 (H600A 1014).  

NOTE:  Both HVAC units 

must be equipped with electric resistance heat for this 

sequence to work properly. 

  1. Temperature control always has priority over 

dehumidification.  If there is any stage of cooling 
demand active, the dehumidification sequence is 
locked out.

  2. If all stages of cooling are satisfied, and relative 

humidity is above the set point of the humidity 
controller.

 

a.  The Green "Dehumid Operation Light" will come 

on, and the lag unit compresser and blower will 
operate until the set point of humidty controller 
is satisfied (or cancelled by a call for cooling).

 

b.  If the space temperature drops to 19.4°C, the 

electric heater of the lead unit will cycle to help 
maintain building temperature.  It will cycle off 
at 20.6°C.

 

c.  If the space temperature drops to 17.8°C, 

the "Stage 2 Heating Light" will come on, 
and the lag unit compressor operation for 
dehumidification mode will terminate until the 
building temperature rises above18.3°C from 
the 1st Stage heat and building load.  The 
Green "Dehumidification Light" will stay on 
during this sequence, and when 2nd Stage 
Heating light is "OFF", the compressor is "ON".  
The electric resistance heater in the lag unit is 
locked out in dehumidification mode.

Lag Unit outputs G, Y1, and Y2 are all switched 
one during dumidification sequence.  This is true 
for both alternating and non-alternating controller 
configurations. 

Summary of Contents for K36A2-A

Page 1: ...6A2 A K36A2 N K42A2 A K42A2 N K48A2 A K48A2 N INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 628 Supersedes NEW Date 12 1 14 K60A2 A K60A2 N K36...

Page 2: ...able 8 Indoor Blower Performance 24 Table 9 Maximum ESP Electric Heat Only 24 Table 10 Electric Heat 24 Getting Other Information and Publications 3 Wall Mount General Information 4 Wall Mount Model N...

Page 3: ...er and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...e entire air conditioning system should be carefully read before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instru...

Page 5: ...s Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return...

Page 6: ...which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is provided for ease of installation but is not required 2 The unit itself is su...

Page 7: ...BLE PANEL ACCESS HEATER ELECTRICAL ENTRANCE HIGH VOLTAGE ENTRANCE ELECTRIC HEAT ACCESS PANEL DISCONNECT C BREAKER BUILT IN RAIN HOOD 4 PITCH J K H C I A 2 13 D 3 4 I D DRAIN HOSE Mounting Brackets Loc...

Page 8: ...4 1 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM T...

Page 9: ...mbustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheat...

Page 10: ...TURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH...

Page 11: ...ALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 12: ...on page 23 for Electrical Specifications WIRING LOW VOLTAGE WIRING All 230 208V 1 phase equipment has dual primary voltage transformers All equipment leaves the factory wired on 240V tap For 208V oper...

Page 13: ...mid Operation Light will come on and the lag unit compresser and blower will operate until the set point of humidty controller is satisfied or cancelled by a call for cooling b If the space temperatur...

Page 14: ...Manual 2100 628 Page 14 of 24 FIGURE 7 THERMOSTAT CONNECTIONS...

Page 15: ...TDOWN NC CONTACTS OPEN ON ALARM Rt REMOVE JUMPER FOR COMP DISABLE FEATURE 2 REMOVE JUMPER WHEN CONNECTING GEN CONTACT 3 REMOVE JUMPER WHEN CONNECTING FIRE SHUTDOWN CONTACT 1 NC CONTACTS OPEN ON ALARM...

Page 16: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Page 17: ...run in reverse rotation for an extended period of time the compressor s internal protector will trip All three phase compressors are wired identically internally As a result once the correct phasing i...

Page 18: ...m relay circuit will energize Recycling the wall thermostat resets the manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120 seconds the com...

Page 19: ...e unit to the serial plate charge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove screws holding...

Page 20: ...URE 10 MOTOR HIGH VOLTAGE CONNECTIONS FIGURE 10 NOTE Bard Models PA13242 PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2...

Page 21: ...e common and the appropriate motor terminal 1 5 G input is typically on terminal 1 but refer to wiring diagram a If the low voltage communication is not present check the demand from the thermostat Al...

Page 22: ...ser Fan Operation page 17 Model Return Air Temperature C Pressure 35 37 39 41 43 45 47 49 51 53 55 K36 2 27 DB 19 WB Low Side High Side 143 145 147 148 150 152 154 156 158 160 162 368 388 408 429 449...

Page 23: ...gle Circuit Minimum Circuit Ampacity Maximum External Fuse or Ckt Brkr Field Power Wire Size Ground Wire K36L2 A0Z 208 230 60 1 1 A05 1 K36L2 N0Z 400 60 3 1 8 2 10 14 14 N05 1 9 8 15 14 14 K42L2 A0Z 2...

Page 24: ...Amps BTUH 5 20 8 17 065 18 1 12 800 6 9 0 21 330 TABLE 7 RECOMMENDED AIRFLOW Model Nominal Rated CFM Nominal Rated ESP Recommended Airflow Range K36A K36L 1100 15 930 1350 K42A K42L 1300 20 1485 1070...

Reviews: