![Bard I36Z1-A Installation Instructions Manual Download Page 40](http://html1.mh-extra.com/html/bard/i36z1-a/i36z1-a_installation-instructions-manual_4095809040.webp)
Manual 2100-578E
Page
40 of 41
FAN blADE SETTING DIMENSIONS
The position of the fan blade should be flush with the
leaving face of the orifice plate. Check to make sure
the blades do not extend beyond the rear casing of the
unit. Spin the blade by hand to make sure it does not
hit the ring.
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity
of refrigerant listed on the serial plate. AHRI capacity
and efficiency ratings were determined by testing with
this refrigerant charge quantity. The following pres-
sure tables (Tables 10A & 10B and 11A & 11B) show
nominal pressures and temperatures for the units. Since
many installation specific situations can affect the pres
-
sure readings, this information should only be used by
certified technicians as a guide for evaluating proper
system performance. They shall not be used to adjust
charge. If charge is in doubt, reclaim, evacuate and
recharge the unit to the serial plate charge.
10
1
2 3
4
5
6
7
8
16
15
14
13
12
11
9
3
5
1 2
4
MIS-2839
FIGURE 21 — CONTROl CONNECTOR MOTOR HAlF
* Suggested mating connector
Housing — AMP 350809-1
Contact — AMP 350537-1
** WARNING — Applying 240VAC line input with
PIN 1 to PIN 2 jumper in place will permanently
damage unit!
POWER CONNECTOR
MOTOR HAlF
MODE of
OPERATION
OFF
Continuous
blower
(
ventilation
mode
)
Part load
Cooling
Full load
Cooling
Dehum.
Mode
(when
equipped)
Part
load
Heat
Pump
Full
load
Heat
Pump
Heat Pump
Full load w/
1st bank of
Elec. Heat
Heat Pump
Full load w/
1st & 2nd bank
of Elec. Heat
Emergency
Heat Mode
Thermostat
24 VAC
Inuput Signals
—
"G"
"G",
"Y1","Y2"
"G",
"Y1","Y2"
"D"
"G", "B",
"Y1"
"G", "B",
"Y1", "Y2"
"G", "Y1",
"Y2", "B",
"W1"
"G", "Y1",
"Y2", "B",
"W2", "W3"
"G",
"W2", "W3"
Pin #1
24 VAC "C" (Common) Signal, Always Energized
Pin #2
X
Pin #3
24 VAC "C" (Common) Signal, Always Energized
Pin #4
Not Used
Pin #5
Not Used
Pin #6
X
X
X
X
X
X
X
Pin #7
Not Used
Pin #8
Not Used
Pin #9
X
X
X
Pin #10
Not Used
Pin #11
Not Used
Pin #12
24 VAC Hot "R" Signal, Always Energized
Pin #13
X
X
Pin #14
X
X
X
X
X
Pin #15
X
X
X
X
X
X
X
X
X
Pin #16
Not Used
POWER CONNECTOR
PWb HEADER
AMP 1-350945-0
PIN
Description
1
Jumper Pin 1 to Pin 2 for 120VAC
Line Input Only **
2
3
Chassis Ground
4
AC Line
5
AC Line
TROUblESHOOTING ECM™ blOWER MOTORS
(Cont’d.)