FAN BLADE SETTING DIMENSIONS
The position of the fan blade should be flush with the
leaving face of the orifice plate. Check to make sure
the blades do not extend beyond the rear casing of the
unit. Spin the blade by hand to make sure it does not
hit the ring.
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity
of refrigerant listed on the serial plate. AHRI capacity
and efficiency ratings were determined by testing with
this refrigerant charge quantity. The following pressure
tables show nominal pressures and temperatures for
the units. Since many installation specific situations
can affect the pressure readings, this information
should only be used by certified technicians as a guide
for evaluating proper system performance. They shall
not be used to adjust charge. If charge is in doubt,
reclaim, evacuate and recharge the unit to the serial
plate charge.
10
1
2 3
4
5
6
7
8
16
15
14
13
12
11
9
3
5
1 2
4
MIS-2839
FIGURE 40
Control Connector Motor Half
* Suggested mating connector
Housing — AMP 350809-1
Contact — AMP 350537-1
**
WARNING
–
Applying 240VAC line input with
PIN 1 to PIN 2 jumper in place will permanently
damage unit!
Power Connector Motor Half
MODE of
OPERATION
OFF
Continuous
Blower
(Ventilation
Mode)
Part Load
Cooling
Full Load
Cooling
Dehum.
Mode
(when
equipped)
Part
Load
Heat
Pump
Full
Load Heat
Pump
Heat Pump
Full Load w/
1st Bank of
Elec. Heat
Heat Pump Full
Load w/ 1st &
2nd Bank of
Elec. Heat
Emergency
Heat Mode
Thermostat
24 VAC
Inuput Signals
—
"G"
"G",
"Y1","Y2"
"G",
"Y1","Y2"
"D"
"G", "B",
"Y1"
"G", "B",
"Y1", "Y2"
"G", "Y1",
"Y2", "B",
"W1"
"G", "Y1", "Y2",
"B", "W2",
"W3"
"G",
"W2", "W3"
Pin #1
24 VAC "C" (Common) Signal, Always Energized
Pin #2
X
Pin #3
24 VAC "C" (Common) Signal, Always Energized
Pin #4
Not Used
Pin #5
Not Used
Pin #6
X
X
X
X
X
X
X
Pin #7
Not Used
Pin #8
Not Used
Pin #9
X
X
X
Pin #10
Not Used
Pin #11
Not Used
Pin #12
24 VAC Hot "R" Signal, Always Energized
Pin #13
X
X
Pin #14
X
X
X
X
X
Pin #15
X
X
X
X
X
X
X
X
X
Pin #16
Not Used
POWER CONNECTOR
PWB HEADER
AMP 1-350945-0
PIN
Description
1
Jumper Pin 1 to Pin 2 for 120VAC
Line Input Only **
2
3
Chassis Ground
4
AC Line
5
AC Line
Troubleshooting ECM
TM
Indoor Blower Motors