Manual 2100-647
Page
17 of 28
Adjustments
Adjustable Delay-on-Make and Delay-on-Break Timer
The potentiometer is used to select delay-on-break time
from 30 seconds to 5 minutes. Delay-on-make (DOM)
timing on power up and after power interruptions is
equal to 2 minutes plus 10% of delay-on-break (DOB)
setting:
0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM
During routine operation of the unit with no power
interruptions, the compressor will operate on demand
with no delay.
Terminal
Description
Use
Series "2"
Reference
1
Compressor on Output Signal from Jade to MV
Economizer Only
"A"
2
24VAC HOT
from Terminal 2 Connected to Unit Transformer
24V HOT
"R"
3
24VAC COMMON
from Unit Transformer to MV
24V COMMON
"C"
4
Unit Compressor Operation
Cooling Operation
"Y"
5
Close Damper Input (Close Blade 100%)
Economizer Only
"F"
6
Electric Heat On Operation, Stage 1 and 2
Heating Operation
"W1"
7
1st Stage Cooling Input, 1st Stage Cooling Signal to Jade
Economizer Only
"Y1"
8
2nd Stage Cooling Input, 2nd Stage Cooling Signal to Jade
Economizer Only
"Y2"
9
Blower Operation (Indoor Blower On)
Blower Operation
"G"
10
Filter Switch Normally Closed Dry Contacts
Alarm Signal
"4"
11
Filter Switch Normally Closed Dry Contacts
Alarm Signal
"5"
12
Blade Switch Delay Relay Normally Closed Dry Contacts
Economizer Only
"8"
13
Blade Switch Delay Relay Normally Closed Dry Contacts
Economizer Only
"9"
14
Occupied Signal Input, Econ Emergency Open (Open Blade 100%)
Economizer Only
"E"
15
Econ Open Output (
6V HOT, 24V HOT
after Blade Open 100% and delay)
Economizer Only
"10"
16
Alarm Relay Common Dry Contact
Comp Alarm Signal
"3"
17
Alarm Relay Normally Open Dry Contact
Comp Alarm Signal
"2"
18
Alarm Relay Normally Closed Dry Contact
Comp Alarm Signal
"1"
19
24VAC HOT
to Terminal 2 from Unit Transformer Through Smoke Alarm Jumper
Wire*
24V HOT
"RT"
20
2nd Stage Heating On Operated Through Jumper to Terminal 6
Heating Operation,
2nd Stage
"W2'
21
Blade Switch Terminal
24V HOT
When Blade is Open, Sends Signal from Switch
to Delay Relay
Economizer Only
"7"
TABLE 1
Sequence of Operation
* Replace jumper wire with smoke alarm connections to interrupt 24VAC unit power if smoke alarm is used in shelter. Jumper can also
be removed to break 24VAC power to unit.
Typical Settings for Dual Unit Installation:
Unit 1: DOB set at 2 minutes and DOM is 132 seconds
Unit 2: DOB set at 4 minutes and DOM is 144 seconds
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on
all units so that the system operating pressures can
be observed. A pressure table can be found on page
19 covering all models. It is imperative to match the
correct pressure table to the unit by model number.