background image

Manual 2100-647

Page 

19 of 28

TABLE 3 

Cooling Pressure

Air Temperature Entering Outdoor Coil °F

Low side pressure ± 4 PSIG                                                         
High side pressure ± 10 PSIG

Tables are based upon rated CFM (airflow) across the evaporator coil.  If there is any doubt as to correct operating 
charge being in the system, the charge should be removed, system evacuated and recharged to serial plate charge 
weight.

NOTE:

  Pressure table based on high speed condenser fan operation.  If condensing pressures appear elevated,  

check condenser fan wiring.  See “Condenser Fan Operation”.

Model

Return Air Temp 

(DB/WB)

Pressure

75

80

85

90

95

100

105

110

115

120

125

H24A/L

75/62

Low Side

High Side

123
314

124
334

126
355

128
377

129
401

131
425

133
451

135
479

137
507

139
536

141
567

80/67

Low Side

High Side

132
322

133
343

135
364

137
387

138
411

140
436

142
463

144
491

146
520

149
550

151
582

85/72

Low Side

High Side

137
333

138
355

140
377

142
401

143
425

145
451

147
479

149
508

151
538

154
569

156
602

H36A/L

75/62

Low Side

High Side

117
323

120
346

122
370

124
394

127
419

129
446

131
473

134
500

136
528

137
558

138
587

80/67

Low Side

High Side

125
331

128
355

130
379

133
404

136
430

138
457

140
485

143
513

145
542

147
572

148
602

85/72

Low Side

High Side

129
343

132
367

135
392

138
418

141
445

143
473

145
502

148
531

150
561

152
592

153
623

H42A/L

75/62

Low Side

High Side

123
323

125
346

128
371

130
395

132
421

135
447

137
474

138
501

140
528

142
558

144
587

80/67

Low Side

High Side

132
331

134
355

137
380

139
405

141
432

144
458

146
486

148
514

150
542

152
572

154
602

85/72

Low Side

High Side

137
343

139
367

142
393

144
419

146
447

149
474

151
503

153
532

155
561

157
592

159
623

H48A/L

75/62

Low Side

High Side

120
330

122
353

125
377

127
402

130
428

132
454

134
482

136
510

137
540

139
570

141
601

80/67

Low Side

High Side

128
338

131
362

134
387

136
412

139
439

141
466

143
494

145
523

147
554

149
585

151
616

85/72

Low Side

High Side

132
350

136
375

139
401

141
426

144
454

146
482

148
511

150
541

152
573

154
605

156
638

H60A/L

75/62

Low Side

High Side

127
344

129
362

131
380

134
401

136
421

137
444

140
467

142
492

145
518

148
545

151
573

80/67

Low Side

High Side

136
353

138
371

140
390

143
411

145
432

147
455

150
479

152
505

155
531

158
559

161
588

85/72

Low Side

High Side

141
365

143
384

145
404

148
425

150
447

152
471

155
496

157
523

160
550

164
579

167
609

Summary of Contents for H24AA-A

Page 1: ...IR CONDITIONER Models INSTALLATION INSTRUCTIONS H24AA A H36AA A H42AA A H48AA A H60AA A H24LA A H36LA A H42LA A H48LA A H60LA A Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual...

Page 2: ...ssories 22 Table 10 Vent and Control Options 22 Table 11 Unit Low Voltage Terminal Connection Chart MV Series Controller 23 Table 12 Unit Low Voltage Terminal Connection Chart MC Series Controller 24...

Page 3: ...mmer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contracto...

Page 4: ...hould be consulted before the installation is made See Page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to...

Page 5: ...be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return air grille is required with in...

Page 6: ...olts 7 Secure rain flashing to wall and caulk across entire length of top see Figure 2 8 For additional mounting rigidity the return air and supply air frames or collars can be drilled and screwed or...

Page 7: ...Entrance Air Panel Drain Heater Disconnect Entrance 4 Pitch Inlet Access Panel Economizer Rain Hood Low Voltage Electrical Air Intake Hood C Breaker High Voltage Economizer Controls H A D J C I 2 13...

Page 8: ...TOP TOP WALL OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE OPENING TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER DUCT Wall Opening and Hole Location View Right Side...

Page 9: ...CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER ACCESS...

Page 10: ...1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SI...

Page 11: ...ls This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible materia...

Page 12: ...TURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH...

Page 13: ...sure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to...

Page 14: ...or 3 Replace filter 4 Press Reset button 5 Verify filter light is off 6 Replace filter door 7 Turn on unit power For units equipped with economizer 1 Turn off unit power 2 Remove hood cover 3 Remove m...

Page 15: ...t composition during multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant cha...

Page 16: ...ll models covered by this manual The compressor control module is an anti short cycle lockout timer with high and low pressure switch monitoring and alarm relay output Adjustable Delay on Make and Del...

Page 17: ...losed Dry Contacts Alarm Signal 4 11 Filter Switch Normally Closed Dry Contacts Alarm Signal 5 12 Blade Switch Delay Relay Normally Closed Dry Contacts Economizer Only 8 13 Blade Switch Delay Relay No...

Page 18: ...this refrigerant charge quantity The pressure table on the following page shows nominal pressures for the units Since many installation specific situations can affect the pressure readings this inform...

Page 19: ...38 587 80 67 Low Side High Side 125 331 128 355 130 379 133 404 136 430 138 457 140 485 143 513 145 542 147 572 148 602 85 72 Low Side High Side 129 343 132 367 135 392 138 418 141 445 143 473 145 502...

Page 20: ...2 34 34 58 84 110 50 50 60 90 125 8 8 6 4 2 10 10 10 8 6 58 58 26 52 60 60 30 60 6 6 10 6 10 10 10 10 H60AA A00 A0Z A05 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 38 38 60 86 112 60 60 60 90 125 8 8 6...

Page 21: ...1565 1820 1770 1600 1540 1970 1885 1400 1315 0 3 835 800 1180 1100 860 850 1735 1665 1530 1450 1720 1605 1500 1425 1895 1800 1300 1220 0 4 750 720 1080 1010 800 785 1615 1565 1425 1350 1575 1500 1375...

Page 22: ...HWA02 A10LB X EHWA03 A05LB X EHWA03 A10LB X EHWA03 A15LB X EHW4TA A05L X X X EHWA05 A10LB X X X EHWA05 A15LB X X X Circuit Breakers WMCB Pull Disconnects WMPD WMCB 03A X WMCB 05A X WMCB 08A X X WMCB 0...

Page 23: ...osed Dry Contacts MV Signals Blade Switch Fail Alarm 8 on Relay Board 8 13 Blade Switch Delay Relay Normally Closed Dry Contacts MV Signals Blade Switch Fail Alarm 9 on Relay Board 9 14 Occupied Signa...

Page 24: ...h Delay Relay Normally Closed Dry Contacts Not Used on MC 8 13 Blade Switch Delay Relay Normally Closed Dry Contacts Not Used on MC 9 14 Occupied Signal Input Econ Emergency Open Open Blade 100 Unit R...

Page 25: ...Contacts Not Used 4 11 Filter Switch Normally Closed Dry Contacts Not Used 5 12 Blade Switch Delay Relay Normally Closed Dry Contacts Not Used 8 13 Blade Switch Delay Relay Normally Closed Dry Contact...

Page 26: ...2 13 4 8 18 6 33 20 104 14 109 2 110 16 111 11 112 3 113 9 117 7 118 21 116 5 121 19 136 Dual Can Capacitor LOUT 5 ECON LOUT DAMPER 128 103 B 128 3 Black White Light 113 124 Terminal Black Black Black...

Page 27: ...NC 3 2 1 NO 12 PIN PLUG COM DAMPER MOTOR DAMPER BLADE IN RED BLACK BLACK IS SHOWN WITH THE CONTACT POSITION IAQ AUX1 O Y2 I 8 S BUS ACT 24V ACT RED YELLOW IAQ R MAT PLUG PLUG PLUG PLUG BROWN WHITE GR...

Page 28: ...Vent Plug Pin 2 on Vent Plug Pin 5 on Vent Plug Pin 7 on Vent Plug Pin 10 on Vent Plug Time Delay Relay T1 T2 Y HPC Lo Press Sw LPC LPC Alarm Relay ALR CC Comp Control Module R MV Controller C 4 5 W...

Reviews: